2.5 SCOPE:<br />

06 SECTION II-: SPECIFIC TECHNICAL REQUIREMENT OF<br />

66KV PTS<br />

2.2.2 This section covers the specific technical requirements, climatic <strong>and</strong> isoccraunic conditions<br />

<strong>and</strong> systems particulars for which POTENTIAL transformers shall be <strong>of</strong>fered as per the<br />

general technical requirements given under section-I <strong>of</strong> this specification <strong>and</strong> the schedule <strong>of</strong><br />

requirements specified herein for various substations.<br />

2.6 CLIMATIC & ISOCERAUNIC CONDITIONS:<br />

2.6.1 The climatic conditions, under which the equipment shall operate satisfactorily are as<br />

follows:<br />

a) Maximum ambient temperature <strong>of</strong> air in Shade (C) 50C<br />

b) Minimum ambient temperature <strong>of</strong> air in shade (C) 4C<br />

c) Maximum daily average ambient temperature (C) 40C<br />

d) Maximum yearly average ambient temperature (C) 30C<br />

e) Maximum relative humidity (%) 95%<br />

f) Average number <strong>of</strong> thunderstorm days / annum. 15<br />

g) Average annual rainfall 150 cms.<br />

h) Maximum wind pressure 150 Kg/m2<br />

i) Height above mean seal level Not exceeding 1000mtrs.<br />

2.6.2 Since the substations may be near seashore, the equipment <strong>of</strong>fered shall be suitable for<br />

heavily polluted atmosphere.<br />

2.7 SYSTEM DETAILS:<br />

i) Nominal system voltage 66 KV<br />

ii) Maximum rated voltage 72.5 KV<br />

iii) Frequency 50Hz.<br />

iv) Number <strong>of</strong> phases 3<br />

v) Neutral earthing Solidly Earthed<br />

2.8 TYPE & RATING OF POTENTIAL RANSFORMER:<br />

2.8.1 The 66 KV Potential transformer shall have the rating as given below:<br />

1) PT Ratio : 66 kV / RT3 / / 110V / RT 3 / / 110V / RT3<br />

2) No <strong>of</strong> Cores : Two<br />

Core – I Core – II<br />

3) Application Metering protection<br />

3) Rated burden (VA) 100 50<br />

4) Class <strong>of</strong> accuracy CL 0.5 CL 0.5<br />

5) Voltage Factor : .2 continuous, 1.5 for 8 hours<br />

6) Max. temp. Rise over design Ambient<br />

Temp. at rated voltage & frequency : Max 50 over 50 Deg. Cent.<br />

7) 1.2 / 50 microsecond lightning impulse : 350<br />

withst<strong>and</strong> voltage (kV peak)<br />

8) Power frequency withst<strong>and</strong> voltage for : 140<br />

one minute (kV rms) dry & wet<br />

9) Minimum total for creepage distance for : 1810 mm<br />

heavily polluted atmosphere<br />

10) Reference st<strong>and</strong>ard for PTS : I.S 3156, 1992<br />

11) Reference st<strong>and</strong>ard for oil : I.S 335, 1993<br />

12) Max. temp. Rise over design Ambient<br />

Temp. at rated voltage & frequency : Max 50 over 50 Deg. Cent.<br />

13) The 66kv PTS shall be outdoor type, single phase, 50 HZ, oil filled, Hermetically<br />