12) Minimum total for creepage distance for :1810<br />

heavily polluted atmosphere: (mm)<br />

13) Reference st<strong>and</strong>ard for PTS : I.S 2705, 1992<br />

14) Reference st<strong>and</strong>ard for oil : I.S 335, 1993<br />

15) Max. temp. Rise over design Ambient<br />

Temp. at rated current & frequency : Max 50 over 50 Deg. Cent.<br />

16) The 66kv PTS shall be outdoor type, single phase, 50 HZ, oil filled, Hermetically<br />

sealed with SS bellow, dead tank suitable for Hot line washing.<br />

2.4.2 The ratings specified shall be guaranteed at all primary connections. Any changes in the<br />

particulars <strong>of</strong> the CTs that may be required for the protective relays (protective relays being<br />

procured separately) actually shall have to be met by the supplier <strong>of</strong> CTs without any extra<br />

cost.<br />

2.4.3 All current transformers shall meet the requirements <strong>of</strong> this specification for 3% variation<br />

in rated system frequency <strong>of</strong> 50 Hz.<br />

2.4.4 EARTH QUAKE & WIND DESIGN LOADS:<br />

Each CT, including its supporting structure shall be designed to withst<strong>and</strong> repeated<br />

earthquake acceleration <strong>of</strong> 0.08 x 2g with wind loads <strong>of</strong> 150 kg/m2 on the projected are (nonsimultaneous)<br />

without damage to component parts <strong>and</strong> without impairment <strong>of</strong> operation.<br />

2.4.5 The class insulation will be A or better.<br />

* * * * * * * * * * * * * * *<br />