<strong>Moeller</strong> <strong>Wiring</strong> <strong>Manual</strong> <strong>02</strong>/<strong>05</strong><br />

Contactors and Relays<br />

ZEV electronic motor-protective system<br />

Tripping characteristics Tripping characteristics for 3 phase loads<br />

Seconds Minutes<br />

2h<br />

100<br />

15<br />

10<br />

5<br />

2<br />

1<br />

ZEV 3 pole<br />

CLASS 40<br />

35<br />

30<br />

25<br />

20<br />

20<br />

10<br />

7<br />

15<br />

5 10<br />

3<br />

CLASS 5<br />

2<br />

11<br />

2 3 4 5 6 78910 x Setting current<br />

Tripping limits for 3 pole balanced load<br />

Response time<br />

< 30 min. at up to 115 % of the set current<br />

> 2 h at up to 1<strong>05</strong> % of the set current from cold<br />

These tripping characteristics show the<br />

relationship between the tripping time from cold<br />

to the current (multiples of set current IE ). After<br />

preloading with 100 % of the set current and the<br />

temperature rise to the operational warm state<br />

associated with it, the stated tripping delays are<br />

reduced to approx. 15 %.<br />