<strong>Moeller</strong> <strong>Wiring</strong> <strong>Manual</strong> <strong>02</strong>/<strong>05</strong><br />

Electronic motor starters and drives<br />

Soft starters DS4<br />

LED displays<br />

The LEDs indicate the operational states as<br />

follows:<br />

Red LED Green LED Function<br />

Lit Lit Init, LEDs lit only briefly, Init itself takes about 2 seconds<br />

Depending on device:<br />

– All devices: LED briefly lit once<br />

– DC devices: after a brief pause, the LEDs briefly light up again<br />

Off Off Device is off<br />

Off Flashing at 2 s<br />

intervals<br />

Ready for operation, power supply OK, but no start signal<br />

Off Flashing at 0.5 s Device in operation, ramp is active (soft start or soft stop); on M(X)R<br />

interval<br />

the current rotating field direction is also indicated.<br />

Off Lit Device in operation, top-of-ramp reached; on M(X)R the current<br />

rotating field direction is also indicated.<br />

Flashing at<br />

0.5 s interval<br />

Off Fault<br />

U<br />

Ue<br />

A1, A2<br />

FWD, REV, 0<br />

U = 100 %<br />

out<br />

Run-<br />

(FWD/REV-) LED<br />

Error-LED<br />

Initialization Fault Ready for operation In ramp Top of ramp<br />

For 2-20Immediate<br />