57F<br />

120 F<br />

39 F<br />

Suction<br />

Cooling<br />

Load<br />

Heating<br />

Load<br />

44F<br />

125 F<br />

Condensing<br />

105 F<br />

Simultaneous<br />

Heating & Cooling<br />

Compressor Lift = 86 F<br />

VME II Simultaneous Load Performance Summary<br />

300 Ton Data Room Cooling Load & 4,736 MBH Simultaneous Heating Load (VME I)<br />

Geothermal<br />

Water Cooling Heating Cooling<br />

Heating Heating<br />

Temperature Efficiency Efficiency Capacity Cooling Power Capacity Power Total Power<br />

F kW/Ton MBH/kW Tons kW MBH kW<br />

90 0.8589 16.2465 300 257.67 4736 291.5 549.2<br />

70 0.6340 14.0818 300 190.2 4736 336.3 526.5<br />

48 0.5264 10.8519 300 157.92 4736 436.4 594.3<br />

300 Ton Data Room Cooling Load & 4,736 MBH Simultaneous Heating Load (VME II)<br />

Geothermal<br />

Water<br />

Temperature<br />

Combined<br />

DHRC<br />

Efficiency<br />

Cooling Total<br />

Capacity Power<br />

F kW/Ton Tons kW<br />

90 1.1107 300 333.21 39.3%<br />

70 1.1107 300 333.21 36.7%<br />

48 1.1107 300 333.21 43.9%<br />

Efficiency<br />

Improvement<br />

5/16/2012<br />