Multistack - Trane
Multistack - Trane
Multistack - Trane
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
57F<br />
120 F<br />
39 F<br />
Suction<br />
Cooling<br />
Load<br />
Heating<br />
Load<br />
44F<br />
125 F<br />
Condensing<br />
105 F<br />
Simultaneous<br />
Heating & Cooling<br />
Compressor Lift = 86 F<br />
VME II Simultaneous Load Performance Summary<br />
300 Ton Data Room Cooling Load & 4,736 MBH Simultaneous Heating Load (VME I)<br />
Geothermal<br />
Water Cooling Heating Cooling<br />
Heating Heating<br />
Temperature Efficiency Efficiency Capacity Cooling Power Capacity Power Total Power<br />
F kW/Ton MBH/kW Tons kW MBH kW<br />
90 0.8589 16.2465 300 257.67 4736 291.5 549.2<br />
70 0.6340 14.0818 300 190.2 4736 336.3 526.5<br />
48 0.5264 10.8519 300 157.92 4736 436.4 594.3<br />
300 Ton Data Room Cooling Load & 4,736 MBH Simultaneous Heating Load (VME II)<br />
Geothermal<br />
Water<br />
Temperature<br />
Combined<br />
DHRC<br />
Efficiency<br />
Cooling Total<br />
Capacity Power<br />
F kW/Ton Tons kW<br />
90 1.1107 300 333.21 39.3%<br />
70 1.1107 300 333.21 36.7%<br />
48 1.1107 300 333.21 43.9%<br />
Efficiency<br />
Improvement<br />
5/16/2012<br />
24