Chapter 1 Introduction<br />
1.2 Characteristics<br />
<strong>XGK</strong> system has the features as below.<br />
1) Compact size<br />
The function is extended to large sized but the size is reduced innovatively to make the installation in the<br />
small space for any purpose easily.<br />
2) High speed processing<br />
(1) <strong>XGK</strong>-CPUUN<br />
• Sequence command: 8.5 ns<br />
• MOV command: 25.5 ns<br />
• Floating point arithmetic operation(the operation for the single real number and <strong>do</strong>uble real number<br />
accuracy is profoundly improved)<br />
Classification + − × ÷<br />
Single Real 183 ns 183 ns 336 ns 345 ns<br />
Double Real 327 ns 327 ns 727 ns 808 ns<br />
(2) <strong>XGK</strong>-CPUU<br />
• Sequence command: 28 ns<br />
• MOV command: 84 ns<br />
• Floating point arithmetic operation<br />
Classification + − × ÷<br />
Single Real 602 ns 602 ns 1,106 ns 1,134 ns<br />
Double Real 1,078 ns 1,078 ns 2,394 ns 2,660 ns<br />
(3) Improvement of data transfer speed between modules through base.<br />
• 16 point I/O module data process: 200 ns ~ 800 ns<br />
• Analogue 1 Ch data process: 200 ns ~ 800 ns<br />
• 1 KB communication module data process: 12,800 ns<br />
• Parallel process by I/O data auto refresh during programming<br />
3) Convenience to use Analog Data<br />
Analog module enforced the precision and stability and provides the convenience as below :<br />
• Program simplification by providing analog data dedicated ‘U ‘ device<br />
• Setting without memory map of special module is available by providing parameter setting method.<br />
4) System Configuration<br />
Various convenient functions are provided to meet the demands of users.<br />
• Filter value adjustment of input module<br />
• Output hold at emergency time<br />
• Varistor built-in relay output module with strong durability<br />
• Total extension length of expanded base shall be 15m.<br />
• Provides system RUN contact to power module.<br />
• Cost efficiency of setup, startup and maintenance/repair by enforced self-diagnosis function<br />