Chapter 2 System Configuration<br />

Item<br />

Type<br />

Refresh<br />

Size<br />

Item<br />

Type<br />

Refresh<br />

Size<br />

XGF-PO3H 2<br />

XGL-FMEA 16<br />

XGF-PO4H 2 XGL-C22A 16<br />

XGF-PD1H 2 XGL-C42A 16<br />

APM module<br />

( Advanced Position<br />

module )<br />

XGF-PD2H 2 XGL-CH2A 16<br />

XGF-PD3H 2 XGL-EIMT 16<br />

Communication module<br />

XGF-PD4H 2 XGL-EIMH 16<br />

XGF-PN8A 3 XGL-EIMF 16<br />

XGF-PN8B 3 XGL-ES4T 16<br />

XGF-M16M 1 XGL-BBM 16<br />

XGF-M32E 4 XGL-EIPT 16<br />

2.3.5.2 Calculation of Data Refresh area’s size<br />

1) Limit of Data Refresh area’s size<br />

Sum of Data Refresh area’s size installed in system ≤ 1,024 words<br />

2) Example<br />

In a system, below modules are installed.<br />

XGI-D28A(20 EA), XGQ-D24A(10EA), XGF-AC8A(20EA), XGF-RD4A(10EA)<br />

→ (4 * 20) + (2 * 10) + (22 * 20) + (30 * 10) = 840 words ≤ 1,024 words<br />

Note<br />

1) Sum of Data Refresh area’s size must not exceed 1,024 words.<br />

2) If size of Data Refresh area exceeds 1,024 words, <strong>XGK</strong>/I system <strong>do</strong>esn’t operate properly.<br />