Chapter 5 Program Configuration and Operation Method<br />

2) Interrupt Operation (Time-driven, Internal Device)<br />

This is the method that stops the program operation in proceeding temporarily and carries out the<br />

operation processing which corresponds to interrupt program immediately in case that there occurs the<br />

status to process emergently during PLC program execution.<br />

The signal to inform this kind of urgent status to CPU module is called ‘interrupt signal’ and there is a timedriven<br />

method that operates program every appointed time. Besides, there is an internal device start<br />

program that starts according to the state change of device assigned inside.<br />

3) Constant Scan (Fixed Period)<br />

This is the operation method that performs the scan program every appointed time. This stands by for a<br />

while after performing all the scan program, and starts again the program scan when it reaches to the<br />

appointed time. The difference from constant program is the update of input/output and the thing to<br />

perform with synchronization.<br />

At constant operation, the scan time indicates the net program processing time where the standby time is<br />

deducted. In case that scan time is bigger than ‘constant’, ‘_CONSTANT_ER [F0005C]’ flag shall be ‘ON’.<br />

5.1.2 Operation Processing during Momentary Power Failure<br />

CPU module detects the momentary power failure when input power voltage supplied to power module is<br />

lower than the standard. If CPU module detects the momentary power failure , it carries out the operation<br />

processing as follows.<br />

1) Momentary power failure within 20ms<br />

Input power<br />

Within 20ms momentary power failure<br />

(1) Stops the operation in the output state when<br />

momentary power failure occurred.<br />

(2) If momentary power failure is released, the<br />

operation continues.<br />

(3) Output voltage of power module keeps the value<br />

within the standard.<br />

(4) Even if the operation stops by momentary<br />

power failure, timer measurement and interrupt<br />

timer measurement shall be executed normally.<br />

2) Momentary power failure exceeding 20ms<br />

• Restart processing like at power input shall be<br />

performed.<br />

Input power<br />

Momentary power failure exceeding 20ms momentary<br />

power failure exceed<br />

Notes<br />

1) Momentary power failure?<br />

This means the state that the voltage of supply power at power condition designated by PLC is<br />

lowered as it exceeds the allowable variable range and the short time (some ms ~ some <strong>do</strong>zens ms)<br />

interruption is called ‘momentary power failure ).<br />

5 - 2