<strong>LCC1653</strong>/<strong>01</strong>, <strong>LRI1653</strong>/<strong>01</strong><br />
ActiLume DALI System<br />
ActiLume DALI<br />
15.8<br />
Sensor <strong>LRI1653</strong>/<strong>01</strong>dimensions in mm<br />
79.4<br />
16.4<br />
Controller <strong>LCC1653</strong>/<strong>01</strong>, LCC1656/00 dimensions in mm<br />
44.7<br />
30<br />
22.2<br />
Product description<br />
The <strong>Philips</strong> ActiLume lighting control system consists of a small,<br />
lightweight sensor and controller, designed for easy integration into<br />
luminaires. ActiLume is a true Plug and Play solution for open plan<br />
(up to 11 luminaires) or cell offices (e.g. 4 luminaires). It is used in<br />
a master/slave luminaire concept, easy to use and easy to install.<br />
Application brochures are available to help specify and apply<br />
the system in an optimal way.<br />
Features and benefits<br />
• <strong>Philips</strong> ActiLume is a DALI based lighting control system designed for<br />
maximum comfort and energy savings up to 75% (in fully automatic<br />
mode and when used in combination with <strong>Philips</strong> HF-Regulator Touch<br />
and DALI ballasts).<br />
• ActiLume is a Plug & Play system; no specific lighting control training<br />
is needed. Moreover, the system is supported with simple, dedicated<br />
application and installation sheets.<br />
• The ActiLume system consists out of three state-of-art miniature<br />
sensors combined with a controller containing a series of<br />
pre-programmed modes.<br />
• The two most applied modes, cell and open plan offices, can be<br />
selected via a single push on the service button.<br />
• The light sensor is sensitive for visible radiation (matching the human<br />
eye) providing automatic savings with daylight depending regulation,<br />
without any visible discomfort for the user.<br />
• The movement detector is very sensitive to human movements and<br />
contains a 15 minutes delay to provide optimal functionality whilst<br />
maximizing energy saving during absence.<br />
• Personal control solutions can be created by connecting a mains<br />
rated spring-back switch to the controller or by using an infrared<br />
remote control unit.<br />
• In addition ActiLume offers the possibility to select so called “comfort<br />
modes” in line with the EN 12464 indoor lighting norm. These modes<br />
can be recalled by using a simple mode selection tool IRT8099/20.<br />
• If needed further customization can easily be established by changing<br />
the factory settings with the mode selection tool IRT8099/20.<br />
• The ActiLume controller contains two DALI outputs.These outputs<br />
are pre-programmed (factory setting) as a window and corridor row<br />
with a fixed light offset.<br />
• The system can be extended with 1 or 2 additional movement<br />
detectors, LRM8118/00 and/or LRM8119/00 to maximize movement<br />
coverage. This respectively reduces the number of ballasts per<br />
controller to 10 or 9.<br />
• Factory light level setting is at 600 lux at a reflection factor of 0.3.<br />
1/8
<strong>LCC1653</strong>/<strong>01</strong>, <strong>LRI1653</strong>/<strong>01</strong><br />
ActiLume DALI System<br />
Applications<br />
The ActiLume system is designed for all office applications, from open<br />
plan to cell offices, lobbies or toilets, and from corridor to small meeting<br />
rooms.<br />
It offers dedicated modes, e.g. for schools, light-lines and direct/indirect<br />
lighting concepts.<br />
It even contains a specific comfort mode combining maximum energy<br />
savings and additional comfort based on a practical EN 12464 solution<br />
(mode 4, 5 or 9).<br />
Plug & Play control regimes<br />
• Mode 1: Switching light off when the area is not occupied, saving<br />
maximum energy in a cell office situation.<br />
• Mode 2: Maintaining a (lower) light level when the area is not<br />
occupied, avoiding dark areas in an open plan office.<br />
• Next to the modes the following functions can be changed<br />
independently:<br />
- Power up behavior<br />
- Default light level<br />
- Background level<br />
<strong>Philips</strong> quality<br />
This ensures quality with respect to:<br />
• System supplier<br />
• As manufacturer of lamps, electronic control gear and lighting control<br />
equipment, <strong>Philips</strong> ensures that, from the earliest development stage,<br />
optimum performance is maintained.<br />
• International standards<br />
• <strong>Philips</strong> lighting control equipment complies with all relevant<br />
international rules and regulations.<br />
Compliances and approvals<br />
RFI 9kHz to 30MHz EN 55<strong>01</strong>5<br />
RFI 30MHz to 1000MHz EN 55022 A<br />
Immunity EN 61547<br />
Safety EN 61347-1<br />
EN 61374-2-11<br />
Quality standard ISO 90<strong>01</strong><br />
Environmental standard ISO 140<strong>01</strong><br />
Approval marks ENEC<br />
CE marking<br />
Technical data for installation<br />
Mains operation<br />
Rated mains voltage 220 - 240 V<br />
Tolerances for performance -8% - +6% (202 - 254 V)<br />
With tolerances for safety +/- 10% (198 - 264 V)<br />
Mains frequency 50/60 Hz<br />
Input power (system) 0.8 - 1.3 W<br />
Number of ballasts Number of extension sensors<br />
LRM8118/00 and/or LRM8119/00<br />
11 0<br />
10 1<br />
9 2<br />
Technical data for design and mounting in fixtures<br />
Operating conditions<br />
Ambient temperature 0 ºC to 55 ºC<br />
Sensor and controller<br />
Rel. humidity 20% to 85%,<br />
no condensation<br />
T case Controller 75 ºC<br />
Sensor 55 ºC<br />
Storage conditions<br />
Temperature -25 ºC to +85 ºC<br />
Rel. humidity 10% to 95% (Non condensing)<br />
Sensor <strong>LRI1653</strong>/<strong>01</strong><br />
Connection RJ-10 4-Pole fixed to<br />
<strong>LRI1653</strong>/<strong>01</strong>, 100cm cable<br />
RJ-10 (4P4C)<br />
Housing (casing)<br />
Material Polycarbonate UL94V-0<br />
Glow wire test 850 °C /5s<br />
Safety basic insulation ≥ 1500V<br />
When placed at a height of 3m the following values are valid:<br />
Infrared receiver Signal range r = 2.5<br />
Light sensor Ambient light monitoring<br />
Monitoring 25 to 350 lux at<br />
sensor<br />
Monitoring area r = 2.5<br />
2/8
<strong>LCC1653</strong>/<strong>01</strong>, <strong>LRI1653</strong>/<strong>01</strong><br />
ActiLume DALI System<br />
Movement detector Passive Infra Red (PIR)<br />
Detection area at 2.5m height: 4x4m<br />
(sensitive for small movements)<br />
6x5m<br />
(sensitive for large movements)<br />
6 m<br />
4 m<br />
Mounting<br />
4 m<br />
5 m<br />
Large movement<br />
detection area<br />
Small movement<br />
detection area<br />
Maximum height PIR: 3.5 m<br />
X-angle PIR: 82°<br />
Y-angle PIR: 100°<br />
The sensor has latching rills on the back so it can easily be mounted. It<br />
can also be mounted onto a lamp by means of a clip LCA8002/00 or<br />
LCA8003/00.There is an additional clip, LCA8005/00, for mounting the<br />
sensor in the luminaire housing.<br />
60 mm<br />
R0-0.5 mm (4x)<br />
1. Required Luminaires opening dimension: 60 x 22 (mm)<br />
2. Thickness �tness of Luminaires �xture: 0.5~2.5 (mm)<br />
22 mm<br />
Service button<br />
The service button can be used to:<br />
b. Adjust the factory set reference light level.<br />
Pressing the service button (>3 seconds) until the lamp gives a light<br />
flash (wink) will start the automatic calibration procedure.<br />
The light output of the luminaires connected to the window side<br />
(DALI 1) is set to 80%.The light output of the luminaires connected<br />
to the corridor side (DALI 2) is set to 100%.<br />
After 30 seconds the ActiLume controller is saving the actual light<br />
level as new reference light level (indicated by a second flash).<br />
This 30 seconds time delay is required to have sufficient time to step<br />
aside or remove a stepladder.<br />
Controller unit <strong>LCC1653</strong>/<strong>01</strong><br />
DALI Output In user mode 1 and user mode 2 the system<br />
is programmed as one channel. When enough<br />
daylight enters the room, the amount of artificial<br />
light will be automatically reduced and the DALI<br />
2 output (corridor row) is programmed with a<br />
light offset of 30%.<br />
In other modes (which can be recalled with the<br />
IRT8099/20) ActiLume can use two channels<br />
depending the applications functionality.<br />
Mains switch By connecting a mains rated springback switch<br />
to connect Ls (Line-switched), dimming and<br />
switching on/off will be possible according the<br />
Touch and Dim functionality (Maximum 1 switch<br />
per controller).<br />
Switch to be connected to the controller!<br />
Remote control It is also possible to use remote control<br />
IRT8<strong>01</strong>0/00, IRT8030/00 or IRT8050/00.The<br />
IRT8<strong>01</strong>0/00 needs to be pointed to the sensor.<br />
The IRT8030/00 and IRT8050/00 have a X-Y-Z<br />
beam direction, making it suitable for wall<br />
mounting and table top use.<br />
Glow wire test 850 ºC / 5 s<br />
Safety, basic insulation ≥ 1500 V<br />
Material Polycarbonate UL94 V-0<br />
Mounting The controller housing contains snap-in pins for<br />
quick fixation. The diameter of the fixation holes<br />
should be maximum 4.5 mm.<br />
The snap-in pins are designed for a metal<br />
thickness of maximum 0.8 mm.<br />
The distance between the fixation holes is 78 mm.<br />
3/8<br />
a. To select the user mode 1 and 2.<br />
The user mode can be toggled between mode<br />
1 and 2 by means of a short push on the service<br />
button (
<strong>LCC1653</strong>/<strong>01</strong>, <strong>LRI1653</strong>/<strong>01</strong><br />
ActiLume DALI System<br />
Connector type<br />
Connection wiring is greatly simplified through use of WAGO 251<br />
universal connector.<br />
Suitable for both automatic wiring (IDC and ADS) and manual wiring.<br />
WAGO 251 universal connector.<br />
Wiring<br />
DALI distribution block<br />
Corridor = DALI 2 (Offset channel)<br />
Corridor<br />
Window<br />
T&D<br />
230VAC<br />
DA<br />
DA<br />
DA<br />
DA<br />
Ls<br />
Ns<br />
N<br />
GND<br />
L<br />
Mains distribution block<br />
IDC connection<br />
ADS/Manual connection<br />
Release: rotate and pull<br />
Remark: release all wires one by one<br />
DALI distribution block<br />
Window = DALI 1 (Master channel)<br />
Ls DALI 1<br />
Ns<br />
N DALI 2<br />
L<br />
Sensor<br />
Mains input connector<br />
PCB terminal block<br />
WAGO, series 251-104<br />
ActiLume<br />
Sensor<br />
Wire cross-section<br />
IDC connection 0.5 mm – 0.75 mm 2<br />
including stranded wiring<br />
ADS manual connection 0.5 mm - 1.0 mm 2<br />
Strip length 8.0 – 9.0 mm<br />
DA / N<br />
DA / Ls<br />
~<br />
~<br />
Master Luminaire<br />
DALI Ballast<br />
4/8
<strong>LCC1653</strong>/<strong>01</strong>, <strong>LRI1653</strong>/<strong>01</strong><br />
ActiLume DALI System<br />
ActiLume Modes<br />
Besides the two Plug and Play modes for cell office and open plan office,<br />
it is possible to recall 8 other application modes as mentioned below.<br />
This makes the ActiLume system very flexible for all different kinds of<br />
applications.<br />
Mode 1 - Cell of�ce<br />
Auto on<br />
Auto off<br />
Mode 3 - School, classroom<br />
Manual on<br />
Auto off<br />
Mode 5 - Cell of�ce<br />
Comfort mode<br />
EN 12464<br />
Auto on<br />
Auto off<br />
Mode 7 - Toilets<br />
Auto on<br />
Auto off<br />
No DLR<br />
Mode 9 - Open plan of�ce<br />
Always light<br />
Auto on<br />
Auto off<br />
Modes<br />
With the use of the advanced mode selection tool IRT8099/20 all<br />
10 different modes can be selected..<br />
Once selected, the mode can be stored and copied via a point and<br />
shoot method.<br />
Even when the luminaires are switched off for a longer period, stored<br />
parameters are kept.<br />
For more detailed information, please be referred to the <strong>Philips</strong><br />
ActiLume OEM Application guide<br />
15 min.<br />
Mode 2 - Open plan of�ce<br />
Auto on<br />
Auto off<br />
15 min. 120 min.<br />
15 min.<br />
Mode 4 - Open plan of�ce<br />
Comfort mode<br />
EN 12464<br />
15 min. 120 min.<br />
Auto on<br />
Auto off<br />
15 min.<br />
Mode 6 - Corridor<br />
Auto on<br />
Auto off<br />
15 min. 60 min.<br />
15 min. 15 min.<br />
15 min. ∞<br />
Mode 8 - Meeting rooms<br />
Manual on<br />
Auto off<br />
Mode 10 - Open plan of�ce<br />
Comfort mode,<br />
always light<br />
Auto on<br />
Auto off<br />
Only task<br />
light DLR<br />
15 min. ∞<br />
15 min.<br />
5/8
<strong>LCC1653</strong>/<strong>01</strong>, <strong>LRI1653</strong>/<strong>01</strong><br />
ActiLume DALI System<br />
<strong>LCC1653</strong>/<strong>01</strong> Controller<br />
The controller from the ActiLume system.<br />
The ActiLume system is a plug & play,<br />
DALI-based control system which fulfills the<br />
basic needs in offices with maximum energy<br />
saving options by daylight harvesting and<br />
presence detection.<br />
LCC1656/00 Controller<br />
Same as the <strong>LCC1653</strong>/<strong>01</strong>, but designed for<br />
free floor standing luminaires. When the<br />
mains is connected the light switches on<br />
(Powerstage On).<br />
<strong>LRI1653</strong>/<strong>01</strong> Sensor<br />
The multi sensor from the ActiLume<br />
system.<br />
IRT8098/00 Simple mode selection tool<br />
Simple mode selection tool for ActiLume<br />
(mode 1 and mode 2 selection). Light set<br />
point calibrator, easy to use. Batteries are<br />
included.<br />
IRT8099/20 Advanced mode selection tool<br />
Commissioning tool for OccuSwitch DALI<br />
(OccuPlus), OccuSwitch, Saber sensors and<br />
luminaires with ActiLume. Easy to use and<br />
inexpensive tool to adjust the functionality,<br />
perform an installation test and/or calibrate<br />
light levels. The functionality is depending<br />
on the product it is used with. Batteries are<br />
included.<br />
LRM8119/00 ActiLume movement<br />
extension sensor, luminaire based<br />
Compact luminaire based movement<br />
detector to be used to expand the<br />
detection area for ActiLume and<br />
OccuSwitch DALI (OccuPlus) solutions.The<br />
sensor is connected to the DALI line from<br />
the controller (luminaire) and does not<br />
require external power. Mounting height is<br />
between 2.5 and 3.5 m.<br />
LRM8118/00 Extension sensor<br />
Compact movement detector to be used<br />
to expand the detection area for ActiLume<br />
and OccuSwitch DALI (OccuPlus) solutions.<br />
The sensor is connected to the DALI<br />
line from the controller (luminaire) and<br />
does not require external power. The<br />
sensor is suitable for both recessed and<br />
surface mounting (in combination with the<br />
LRH8100/00). Mounting height is between<br />
2.5 and 3.5 m.<br />
6/8<br />
LRH8100/00 Surface mount adaptor<br />
Surface mounting box for the LRM8118<br />
extension sensor. Comes with cut-out holes<br />
for most common cable trunking systems.<br />
LCA8000/00 Cover ActiLume multi<br />
sensor<br />
Cover for the ActiLume multi sensor to<br />
obtain the same outer dimensions as<br />
the ActiLume MicroLuxSense and the<br />
ActiLume 1-10V sensor.<br />
LCA80<strong>01</strong>/00 Ring for ActiLume sensors<br />
Ring around the cover of the ActiLume<br />
multisensor + cover, ActiLume luminaire<br />
based extension sensor + cover, ActiLume<br />
1-10V sensor or ActiLume MicroLuxSense<br />
to fit in the micro-optics of a luminaire.<br />
LCA8002/00 ActiLume sensor clip for TL5<br />
Clip to be used for ActiLume multisensor,<br />
ActiLume Luminaire based extension<br />
sensor, ActiLume 1-10V sensor and the<br />
ActiLume MicroLuxSense .With this clip<br />
the sensor can be directly clicked on the<br />
TL5 lamp.<br />
LCA8003/00 ActiLume sensor clip for<br />
TL-D<br />
Clip to be used for ActiLume multisensor,<br />
ActiLume Luminaire based extension<br />
sensor, ActiLume 1-10V sensor and the<br />
ActiLume MicroLuxSense .With this clip<br />
the sensor can be directly clicked on the<br />
TL-D lamp.<br />
LCA8004/00 Cover ActiLume extension<br />
sensor<br />
Cover for the ActiLume luminaire based<br />
extension sensor to obtain the same outer<br />
dimensions as the ActiLume MicroLuxSense<br />
and the ActiLume 1-10V sensor.<br />
LCA8005/00 ActiLume mounting clip for<br />
use in luminaire.<br />
Clip to be used for ActiLume multisensor,<br />
ActiLume Luminaire based extension<br />
sensor, ActiLume 1-10V sensor and the<br />
ActiLume MicroLuxSense.With this clip the<br />
sensor can be mounted in the luminaire<br />
housing.
<strong>LCC1653</strong>/<strong>01</strong>, <strong>LRI1653</strong>/<strong>01</strong><br />
ActiLume DALI System<br />
IRT8<strong>01</strong>0/00 Hand-held two-key<br />
transmitter<br />
Hand-held two-key transmitter, for infrared<br />
control of various lighting control systems.<br />
ActiLume can also dim the lights (by<br />
pressing a button > 0.5 sec). The unit is<br />
supplied with batteries. A wall holder is<br />
separately available. This transmitter is not<br />
designed to be operated from the wall<br />
holder. For use in all <strong>Lighting</strong> Controls<br />
systems with IR interface excl. Dynalite.<br />
LRH8<strong>01</strong>0/00 Wall holder<br />
Wall holder for the IRT8<strong>01</strong>0/00 hand-held<br />
two-key transmitter.<br />
IRT8050/00 Two-key infrared remote<br />
control<br />
Two-key infrared remote control<br />
transmitter for wall mounting and table-top<br />
use. The unit can be used in combination<br />
with ActiLume. The actual function of the<br />
two large keys can be selected with a dip<br />
switch in the battery compartment. A dip<br />
switch is also used to select the group<br />
address. Batteries are included.<br />
7/8<br />
IRT8030/00 Four-preset hand-held<br />
transmitter<br />
Four-preset hand-held transmitter, suitable<br />
for infrared control of the ActiLume system<br />
specifically when using Mode 8 (Meeting<br />
room). It has 4 keys for presets and one<br />
key for “all off”. Keys for individual control<br />
and preset programming are located<br />
under a hinged cover at the bottom<br />
of the transmitter. The group address<br />
selector switch is contained in the battery<br />
compartment. The unit is supplied complete<br />
with wall holder and batteries.<br />
UID8510 IR User Interface<br />
The UID8510 IR user interface panel<br />
provides intuitive on/off and dimming<br />
functionality. It connects via infrared to the<br />
ActiLume system.<br />
Batteries are included.
<strong>LCC1653</strong>/<strong>01</strong>, <strong>LRI1653</strong>/<strong>01</strong><br />
ActiLume DALI System<br />
Packing data<br />
Type Box dimensions Qty/ Material Weight (Kg)<br />
(mm) Box net gross<br />
<strong>LCC1653</strong>/<strong>01</strong> 376 x 190 x 70 48 Cardboard 0.031 1.728<br />
LCC1656/00 376 x 190 x 70 48 Cardboard 0.031 1.728<br />
<strong>LRI1653</strong>/<strong>01</strong> 227 x 169 x 149 48 Cardboard 0.032 1.632<br />
LRM8118/00 80 x 72 x 40 1 Cardboard 0.076 0.083<br />
LRH8100/00 80 x 80 x 40 1 Plastic bag 0.027 0.033<br />
LRM8119/00 200 x 175 x 110 12 Cardboard 0.030 0.507<br />
IRT8098/00 240 x 135 x 87 1 Cardboard 0.060 0.100<br />
IRT8099/20 155 x 40 x 17 1 Cardboard 0.030 0.100<br />
LCA8000/00 216 x 93 x 70 100 Cardboard 0.228 0.293<br />
LCA80<strong>01</strong>/00 216 x 93 x 70 100 Cardboard 0.155 0.221<br />
LCA8002/00 216 x 93 x 70 50 Cardboard 0.450 0.455<br />
LCA8003/00 216 x 93 x 70 50 Cardboard 0.450 0.455<br />
LCA8004/00 216 x 93 x 70 50 Cardboard 0.186 0.218<br />
LCA8005/00 220 x 97 x 71 50 Cardboard 0.780 0.810<br />
Ordering Data<br />
Type MOQ Ordering number EAN code level 1 EAN code level 3 EOC<br />
<strong>LCC1653</strong>/<strong>01</strong> 12 9137 006 13772 8711500 910424 8711500 910431 910424 30<br />
LCC1656/00 12 9137 003 39803 8727900 921953 8727900 921960 921953 00<br />
<strong>LRI1653</strong>/<strong>01</strong> 12 9137 006 13872 8711500 910462 8711500 910479 910462 30<br />
LRM8118/00 1 9137 003 24703 8711559 730783 8711559 730790 730783 99<br />
LRH8100/00 1 9137 003 18903 8711559 519203 8711559 519210 519203 99<br />
LRM8119/00 12 9137 003 43703 8718291 139461 8718291 139478 139461 00<br />
IRT8098/00 1 9137 003 24803 8711559 730806 8711559 730813 730806 99<br />
IRT8099/20 1 9137 003 34203 8711559 732565 8711559 732572 732565 99<br />
LCA8000/00 1 9137 003 38403 8727900 882803 8727900 882810 882803 00<br />
LCA80<strong>01</strong>/00 1 9137 003 38303 8727900 882780 8727900 882797 882780 00<br />
LCA8002/00 1 9137 003 40803 8727900 952940 8727900 952957 952940 00<br />
LCA8003/00 1 9137 003 40903 8727900 952988 8727900 952995 952988 00<br />
LCA8004/00 1 9137 003 43803 8718291 139386 8718291 139393 139386 00<br />
LCA8005/00 1 9137 003 48803 8718291 196242 8718291 196259 196242 00<br />
3222 636 35122<br />
10/2<strong>01</strong>2<br />
Data subject to change<br />
www.philips.com/lightingcontrols<br />