12<br />

6. Built in requirements<br />

In this chapter you will find some sketches of the outer<br />

dimensions of the components and how to mount<br />

these components. The ways of mounting given in this<br />

document are just some examples and other ways of<br />

mounting are possible.<br />

The ActiLume 1-<strong>10V</strong> Sensor has flying leads of 25.4 in.<br />

(100 cm) and is designed to be built into a luminaire. The<br />

following chapters will explain on how the sensor can be<br />

mounted into a luminaire.<br />

Furthermore the sensor should be installed above a<br />

surface where the light level is representative of the area<br />

to be monitored. The maximum installation height is 12<br />

feet (3.5 meters) from the ceiling to the floor.<br />

If the diaphragm is set to its default position (in the center),<br />

the output of the light sensor will be approximately 5V at<br />

50 footcandles on floor if the reflection factor is 0.3 (the<br />

average reflection factor of an average surface). While<br />

for other surface, the exact dimming curve is related to its<br />

reflection factor.<br />

6.1. Dimensions ActiLume 1-<strong>10V</strong> Sensor<br />

Below you will find some sketches on the most important<br />

dimensions of the Sensor.<br />

Dimensions: inches (mm)<br />

LRI1655<br />

0.08 (2)<br />

0.79 (20)<br />

0.65 (16.6)<br />

0.78 (19.8)<br />

1.73 (44)<br />

<strong>Philips</strong> ActiLume 1-<strong>10V</strong> OEM Application Guide<br />

15<br />

1 30<br />

0.74 (18.9)<br />

0.67 (17)<br />

1.84 (46.8)<br />

6.2 Mounting of the ActiLume 1-<strong>10V</strong> Sensor<br />

The sensor can be<br />

mounted into a<br />

luminaire in different<br />

ways. The following<br />

3 options are the most<br />

commonly used ways of<br />

mounting the sensor.<br />

The most simple way<br />

of mounting the sensor<br />

into the luminaire, is by using a metal clip. The clip<br />

can be mounted on the backside of the sensor and<br />

then as a composition it can be clipped onto a linear<br />

fluorescent lamp.<br />

There are 2 different clips available, one for TL-D<br />

(T8) lamps and one for TL5 (T5) lamps. The TLD<br />

version is called the LCA8002. The TL5 version of the<br />

clip is called the LCA8003. Both types can be ordered<br />

separately and are packed in boxes of 50 pieces.<br />

Please contact your local sales representative for<br />

more info on ordering these clips.<br />

Dimensions: inches (mm)<br />

0.89 (22.6)<br />

LCA8003<br />

1.51 (38.3)<br />

0.43 (11)<br />

0.18 (4.5)<br />

0.63 (16)<br />

Dimensions: inches (mm)<br />

0.89 (22.6)<br />

LCA8002<br />

1.51 (38.3)<br />

0.28 (7)<br />

0.18 (4.5)<br />

0.39 (10)<br />

0.46 (11)<br />

0.65 (16.6)<br />

1.24 (31.6)<br />

1.07 (27.1)<br />

1.37 (34.7)<br />

1.19 (30.3)