22.12.2012 Views

Oklahoma Gas & Electric Muskogee Generating Station Best ...

Oklahoma Gas & Electric Muskogee Generating Station Best ...

Oklahoma Gas & Electric Muskogee Generating Station Best ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Oklahoma</strong> <strong>Gas</strong> & <strong>Electric</strong><br />

<strong>Muskogee</strong> <strong>Generating</strong> <strong>Station</strong> – BART Determination<br />

May 28, 2008<br />

Table 3-2 continued<br />

Control Technology<br />

Controlled NOx<br />

Emission Rate<br />

(lb/mmBtu)<br />

In Service on<br />

Existing PC<br />

Boilers<br />

21<br />

In Service on<br />

Other<br />

Combustion<br />

Sources?<br />

Technically Feasible on<br />

<strong>Muskogee</strong> Units 4 & 5?<br />

Rotamix (SNCR) NA X Yes Rotamix control systems have been<br />

demonstrated on small coal-fired<br />

boilers. However, there are several<br />

currently unresolved technical<br />

difficulties associated with<br />

applying SNCR-type systems on a<br />

large subbituminous coal-fired<br />

boiler. Therefore, Rotamix is not<br />

considered an available retrofit<br />

control technology for <strong>Muskogee</strong><br />

Units 4 & 5.<br />

Pahlman Process NA X No Bench- and pilot-scale testing has<br />

been conducted on coal-fired<br />

boilers, however, there is limited<br />

data available assessing the<br />

technical feasibility of this system<br />

on large coal-fired boilers.<br />

Wet NOx Scrubbing NA X Yes The system has been used on<br />

refinery fluid catalytic cracking<br />

units and small coal-fired boilers,<br />

but has not been used on large<br />

coal-fired boilers. Wet NOx<br />

scrubbing systems are not<br />

commercially available or<br />

technically feasible for <strong>Muskogee</strong><br />

Units 4 & 5.