USER AND REAL SETTINGS<br />
It is important to well understand the logic operations in sending a new data configuration (we intend a new group of<br />
data the chamber has to use, for example new temperature settings, new RUN/STOP status and so on).<br />
In effect, this operation can be seen as <strong>com</strong>posed of 2 different stages:<br />
1. the user prepares the new set of data and send it to the controller (user settings)<br />
2. the controller acts properly to work with the new set (if possible) (real settings)<br />
From the above description you can understand that the final result of the entire operation can or cannot be the same<br />
as requested by the user depending on the chamber and controller status. For example, suppose that an alarm is<br />
present in the system, so the chamber is in alarm condition. If the user send a new set of data in order to change the<br />
status of the RUN bit (the user want the chamber running), no action will take place, beacuase of the alarm.<br />
In other words, we have a “user setting” group of data in which the RUN bit is in ON status, while the same bit in the<br />
“real settings” will be in OFF status.<br />
USER SETTINGS<br />
ADDRESS CHAMBERS DCTC<br />
2056.0 Run Run<br />
2056.1 Alarm Reset Alarm Reset<br />
2056.2 Program(1) Manual(0) Programme(1) Manual(0)<br />
2056.3 Local(1) Remote(0) Local(1) Remote(0)<br />
2056.4 Pause Pause<br />
2056.5 Freeze Freeze<br />
2056.6<br />
2056.7<br />
2056.8 Channel activation 0 (Temperature) Channel activation 0 (Temperature)<br />
2056.9 Channel activation 1 (Rel. Humidity) Channel activation 1 (Rel.Humidity)<br />
2056.10 Channel activation 2 Channel activation 2 (Humid. Temperature)<br />
2056.11 Channel activation 3 Channel activation 3 (H2O temperature)<br />
2056.12 Channel activation 4 Channel activation 4<br />
2056.13 Channel activation 5 Channel activation 5<br />
2056.14 Channel activation 6 Channel activation 6<br />
2056.15 Channel activation 7 Channel activation 7<br />
2057.0 Forced Dehumidification Spraying with humidified air<br />
2057.1 Vibrator Spraying with not humidified air<br />
2057.2 DUT Purging with air (Centrifugal)<br />
2057.3 U.V. Lamp Dry (Compressed air)<br />
2057.4 Water recharge Flooding with Air temperature control<br />
2057.5 Flooding with air+water control (Refrigerator)<br />
2057.6<br />
2057.7 Humidity special control Humidity special control<br />
2057.8 Aux 1 Aux 1<br />
2057.9 Aux 2 Aux 2<br />
2057.10 Aux 3 Aux 3<br />
2057.11 Aux 4 Aux 4<br />
2057.12 Aux 5 Aux 5<br />
2057.13 Aux 6 Aux 6<br />
2057.14 Aux 7 Aux 7<br />
2057.15 Aux 8 Aux 8<br />
2058<br />
2059<br />
<strong>Serial</strong> <strong>com</strong>munications protocol vers. 2.02 Angelantoni Industrie Spa Massa Martana (PG) Italy