- 32 -<br />

SETPOINTS READING<br />

The values reported here are the setpoint values actually used by the regulators inside the chamber controller.<br />

Note that the final setpoint equals the current setpoint only in case of maintenances or slopes at max. speed.<br />

They will be different in case of controlled slopes (gradient different from 0).<br />

For standard chambers (Challenge and Hygros) the values are multiplied by 100.<br />

As previously stated, in the standard chambers channel 0 is the Temperature regulator, while channel 1 is the Rel.<br />

Humidity regulator.<br />

ADDRESS MEANING<br />

2064-2065 User Final Setpoint Channel 0 * 100<br />

2066-2067 Current Setpoint User Channel 0 * 100<br />

2068 Gradient Channel 0 * 100<br />

2069-2070 Final Setpoint user Channel 1 * 100<br />

2071-2072 Current Setpoint user Channel 1 * 100<br />

2073 Gradient Channel 1 * 100<br />

2074-2075 Final Setpoint user Channel 2 * 100<br />

2076-2077 Current Setpoint user Channel 2 * 100<br />

2078 Gradient Channel 2 * 100<br />

2079-2080 Final Setpoint user Channel 3 * 100<br />

2081-2082 Current Setpoint user Channel 3 * 100<br />

2083 Gradient Channel 3 * 100<br />

2084-2085 Final Setpoint user Channel 4 * 100<br />

2086-2087 Current Setpoint user Channel 4 * 100<br />

2088 Gradient Channel 4 * 100<br />

2089-2090 Final Setpoint user Channel 5 * 100<br />

2091-2092 Current Setpoint user Channel 5 * 100<br />

2093 Gradient Channel 5 * 100<br />

2094-2095 Final Setpoint user Channel 6 * 100<br />

2096-2097 Current Setpoint user Channel 6 * 100<br />

2098 Gradient Channel 6 * 100<br />

2099-2100 Final Setpoint user Channel 7 * 100<br />

2101-2102 Current Setpoint user channel 7 * 100<br />

2103 Gradient channel 7 * 100<br />