08.11.2022 Views

ELMARK-ELECTRICAL-EQUIPMENT-2024-GR

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

In)<br />

6<br />

10<br />

AUTOMATION | MOULDED CASE CIRCUIT BREAKERS<br />

YEARS TOTAL<br />

7WARRANTY<br />

+<br />

7 standard<br />

0 extended<br />

* for industrial usage<br />

3 years warranty<br />

7 7<br />

8 5<br />

8<br />

4<br />

Ii ( xIn)<br />

10<br />

OFF<br />

11<br />

14<br />

12<br />

13<br />

HIGH BREAKING CAPACITY LEVEL MOULDED CASE CIRCUIT BREAKERS (MCCB) DS-3E 1000<br />

AND 1250A-ELECTRONIC TYPE<br />

The feature discriminating electronic circuit breakers from thermal-magnetic breakers is to control the over current releases with electronic<br />

circuits. Electronic control is performed via microprocessor. During design of the electronic circuit, worst possibilities to encounter in operation<br />

have been taken into consideration. In high circuit currents, direct opening has been ensured without operating electronic circuit.<br />

Rated and Instant opening current adjustment areas of electronic circuit breakers are quite wide. This feature allows wide use opportunity to<br />

the breaker Furthermore, electronic circuit breakers are not affected by ambient temperatures.<br />

FEATURES<br />

FEATURES<br />

160<br />

140 180 4<br />

125<br />

300<br />

3<br />

500<br />

In (A)<br />

250 225<br />

1<br />

2<br />

TEST<br />

9<br />

10<br />

2.5<br />

2<br />

Isd ( xIn)<br />

Tripping test port (TEST):<br />

1 Tripping test input DC12V (+)<br />

2 Tripping test input DC12V (-)<br />

5<br />

12<br />

6<br />

10<br />

7 7<br />

8 5<br />

8<br />

4<br />

Ii ( xIn)<br />

10<br />

OFF<br />

7 5 3 1<br />

8 6 4<br />

COM<br />

2<br />

11<br />

14<br />

12<br />

13<br />

• Rated operating voltage: 230/400V 50/60Hz<br />

• Electromagnetic coil 100VA for breakers up<br />

to 400A<br />

• Electromagnetic coil 150VA for breakers<br />

630-800A<br />

• Available joining conductors<br />

TECHNICAL DATA<br />

• Rated voltage: 400V AC<br />

• Automatic relay: Electronic type<br />

• Rated isolating voltage: 1000V<br />

• Short-circuit breaking capacity(KA)Icu/Ics:<br />

65/50<br />

• Electrical life: 1000<br />

• Mechanical life: 4000<br />

• Pole number: 3P<br />

• Rated current: 1000A and 1250A<br />

• Weight: 5,7kg<br />

• Dimension (LxHxD): 210x257x155mm<br />

PANEL ADJUSTMENT KNOB AS FOLLOWS IN<br />

TURN:<br />

• IR(A) Isd(x IR) Ii (x IR)<br />

• IR: Overload long delay tripping setting<br />

current; 1 Isd: 9Short-circuit 7 5 short 3 delay 1 tripping<br />

setting current;<br />

• Ii:<br />

2 10 8 6 4 2<br />

Short-circuit instantaneous tripping setting<br />

current. TEST<br />

COM<br />

Catalogue<br />

number<br />

Type<br />

Number<br />

of poles<br />

Rated<br />

current<br />

In (A)<br />

• Altitude up to 2000m;<br />

• Ambient medium temperature should be<br />

within -10°C to +55°C;<br />

• It can withstand the effect of damp air;<br />

• It can withstand the effect of salt fog or oil<br />

mist;<br />

• It can withstand the effect of moulds;<br />

• It can withstand the effect of nuclear radiation;<br />

• The max inclination is 22.5°C.<br />

• It still can work reliably when to normal<br />

vibration;<br />

• It can still work reliably if the product subjects<br />

to the earthquake (4g).<br />

• Places where the surrounding medium is free<br />

from explosion danger, and far away from gas<br />

or conductive dust that would erode the metal<br />

or destroy the insulation;<br />

• Keep away from rain or snow.<br />

FACTORY SETTINGS:<br />

• IR(A) Isd(x IR) Ii (x IR)<br />

• Overload long delay setting time, factory<br />

default: 60s;<br />

• tsd: Short-circuit short delay setting time,<br />

factory default: 0.1s;<br />

• Ip: Overload pre-alarm setting current, factory<br />

default: 0.85*IR.<br />

Operating<br />

breaking<br />

capacity<br />

(kA) Ics<br />

Max.<br />

breaking<br />

capacity<br />

(kA) Icu<br />

Electrical Packing/<br />

adjustment Box (pcs)<br />

44930 DS-3 1000A 3P 1000 50 65 630-1000A 1<br />

44931 DS-3 1250A 3P 1250 50 65 850-1250A 1<br />

46<br />

<strong>ELMARK</strong><br />

Download BUSINESS APP from www.elmarkholding.eu or for mobile from or

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!