06.01.2013 Views

Series 100 Single Package Units, Engineering Guide, 100.50-EG7

Series 100 Single Package Units, Engineering Guide, 100.50-EG7

Series 100 Single Package Units, Engineering Guide, 100.50-EG7

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Application Data (continued)<br />

ECONOMIZER<br />

The economizer section is used for ventilation of the<br />

conditioned space to maintain indoor air quality, and<br />

also to reduce energy consumption by using outdoor<br />

air cooling in lieu of mechanical cooling. If outdoor air is<br />

appropriate for cooling, but not suffi cient for the cooling<br />

demand, mechanical cooling will stage on as necessary<br />

until the cooling load is met.<br />

Dual (comparative or differential) enthalpy operation is<br />

the most accurate and effi cient means of economizer<br />

operation. The IPU controller monitors the return and<br />

outside air energy content, and selects the lower of the<br />

two for operation.<br />

VAV SUPPLY AIR PRESSURE CONTROL<br />

Traditional packaged single package unit systems<br />

use inlet guide vanes (IGVs) for duct static pressure<br />

control. These control supply duct pressure by modulating<br />

dampers (introducing losses and ineffi ciencies)<br />

on the inlet of the fan, open and closed. JOHNSON<br />

CONTROLS variable frequency drives (VFDs) offer<br />

superior fan speed control and quieter, energy effi cient<br />

operation.<br />

FIG 1: TRADITIONAL OVERHEAD VAV AIR<br />

DELIVERY SYSTEM<br />

For VAV applications, the JOHNSON CONTROLS <strong>Series</strong><br />

<strong>100</strong> unit uses a VFD to modulate fan speed and<br />

maintain a constant duct static pressure. VFDs offer<br />

superior control over the operation of the unit at part<br />

load, and offer the additional benefi ts of quieter and<br />

more effi cient operation when compared to IGV.<br />

FLEXSYS<br />

The traditional approach to HVAC design in commercial<br />

buildings has been to supply conditioned air through<br />

14<br />

FORM <strong>100</strong>.50-<strong>EG7</strong> (1110)<br />

extensive overhead duct networks to an array of diffusers<br />

spaced evenly in the ceiling. In Figure 1, the conditioned<br />

air is both supplied and returned at ceiling level. Ceiling<br />

plenums must be designed large enough to accommodate<br />

the supply ducts that run through them. Return air<br />

is typically confi gured as ceiling plenum return without<br />

any ductwork. This type of air distribution, known as the<br />

“well-mixed” type, is the most common system in use.<br />

This conventional HVAC system is designed to promote<br />

complete mixing of supply air with room air, thereby<br />

maintaining the entire volume of all air in the space (from<br />

fl oor to ceiling) at the desired space setpoint temperature.<br />

In addition, to meet IAQ requirements, an adequate<br />

supply of fresh outside air must be introduced to this mix.<br />

A key disadvantage to this control strategy is that it has<br />

no provisions to accommodate different temperature<br />

preferences among the building occupants or to provide<br />

preferential ventilation in the occupied zone.<br />

FIG. 2: JOHNSON CONTROLS FLEXSYS UNDER-<br />

FLOOR AIR DELIVERY SYSTEM<br />

With the JOHNSON CONTROLS FlexSys Underfl oor<br />

Air System, conditioned air from the air handling unit<br />

(AHU) is ducted to the underfl oor plenum. As shown in<br />

Figure 2, this conditioned air fl ows freely throughout<br />

the plenum to individual supply discharge outlets. Unlike<br />

the larger single supply duct outlets typical of overhead<br />

systems, underfl oor systems are confi gured to<br />

have a large number of smaller supply outlets, in close<br />

proximity to the building occupants. These adjustable<br />

outlets provide an opportunity for nearby occupants to<br />

have some amount of control over thermal comfort<br />

conditions in their local environment. Air is returned from<br />

the room at ceiling level (unducted plenum return is<br />

shown). The resulting overall fl oor-to-ceiling air fl ow<br />

pattern takes advantage of the natural buoyancy produced<br />

by heat sources in the space and more effi -<br />

ciently removes heat loads and contaminants from the<br />

space, particularly for cooling applications. In fact, some<br />

of the most important advantages of underfl oor systems<br />

JOHNSON CONTROLS

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!