32324 - PanelView Plus Communications with MicroLogix

32324 - PanelView Plus Communications with MicroLogix

32324 - PanelView Plus Communications with MicroLogix

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

5. Make a note of your IP address and subnet mask.<br />

6. On your <strong>PanelView</strong> <strong>Plus</strong>, go to the main configuration screen.<br />

7. Go to the following location:<br />

Terminal Settings -> Networks and <strong>Communications</strong> -> Network Connections -><br />

Network Adaptors -> Built in Ethernet Controller.<br />

8. Press the IP Address Button.<br />

9. You will enter your PC's IP Address that you located in step 5 above,<br />

EXCEPT for the last digit.<br />

If there is any other device on the network, make sure it has a different IP address to<br />

these by changing its final digit to one that is not already in use.<br />

10. For Subnet Mask, do the same procedure as you did in step 9, using<br />

Subnet Mask you located in step 5.<br />

11. For the Gateway, leave the default (0.0.0.0)/<br />

12. To apply the changes to your IP address and Subnet Mask, reset your<br />

<strong>PanelView</strong> <strong>Plus</strong>.<br />

RSView Studio:<br />

Open the RSView ME project you wish to use, or create a new one.<br />

1. First, set up communications.<br />

In the Application Explorer, double-click on the following:<br />

RSLinx Enterprise -> Communication setup.<br />

<strong>Plus</strong>.<br />

2. Select the Create a New Configuration option.<br />

3. Delete any drivers except the Ethernet driver.<br />

4. Under the Local Tab, create a Serial DF1 driver by doing the following:<br />

a. Right-click on the name of your computer.<br />

b. Select Add Driver.<br />

5. Select the Comm Port you're using.<br />

6. Under the Device field, select SLC or <strong>MicroLogix</strong>.<br />

7. Select Auto-Configuration.<br />

8. Press OK.<br />

9. Verify as follows::<br />

a. Open the new driver. You should see our <strong>MicroLogix</strong> Device.<br />

b. Under the Ethernet driver, you should be able to see the <strong>PanelView</strong><br />

If you see both, skip to step 10.<br />

c. If not, for either device, do the following: