Section 3: System Configuration<br />

28<br />

August 2010<br />

SIZING RUN “C”<br />

Run “C” is sized by the load of the supplied appliance <strong>and</strong> the run length to the supplied appliance<br />

The load of the water heater is 36CFH<br />

The run length to the water heater is 45 + 10 = 55ft<br />

Referring to Table 7-2 (1.0"WC pressure drop) for a 60ft run, 1/2" CSST has a capacity over 36CFH (actual: 54)<br />

SIZING RUN “D”<br />

Run “D” is sized by the load of the supplied appliance <strong>and</strong> the run length to the supplied appliance<br />

The load of the range is 52CFH<br />

The run length to the range is 45 + 20 = 65ft<br />

Referring to Table 7-2 (1.0"WC pressure drop) for a 70ft run, 3/4" CSST has a capacity over 52CFH (actual: 89)<br />

SIZING RUN “E”<br />

Run “E” is sized by the total load of all supplied appliances <strong>and</strong> the run length from the meter to the furthest appliance<br />

The total load of the BBQ <strong>and</strong> the dryer is 25 + 28 = 53CFH<br />

The run length to the BBQ (furthest appliance) is 45 + 20 + 5 = 70ft<br />

Referring to Table 7-2 (1.0"WC pressure drop) for a 70ft run, 3/4" CSST has a capacity over 53CFH (actual: 89)<br />

SIZING RUN “F”<br />

Run “F” is sized by the load of the supplied appliance <strong>and</strong> the run length to the supplied appliance<br />

The load of the dryer is 28CFH<br />

The run length to the dryer is 45 + 20 + 5 = 70ft<br />

Referring to Table 7-2 (1.0"WC pressure drop) for a 70ft run, 1/2" CSST has a capacity over 28CFH (actual: 50)<br />

SIZING RUN “G”<br />

Run “G” is sized by the total load of the supplied appliance <strong>and</strong> the run length from the meter to the furthest appliance<br />

The load of the BBQ is 25CFH<br />

The run length to the BBQ is 45 + 20 + 5 = 70ft<br />

Referring to Table 7-2 (1.0"WC pressure drop) for a 70ft run, 1/2" CSST has a capacity over 25CFH (actual: 50)<br />

Gastite Division<br />

603 Hendee Street / Springfield, MA 01104<br />

800.662.0208 / www.gastite.com / gastite@gastite.com