Section 3: System Configuration<br />

3.2.11 Example 10 - Commercial Elevated Pressure Series System – 2PSI<br />

44<br />

August 2010<br />

Figure 3-18 below shows a typical commercial rooftop installation with four (4) appliances. The piping is arranged in series<br />

with a main run branching at the appliances. The utility company’s supply pressure (downstream of the meter) is 2psi. The<br />

utility company advises that the specific gravity of the gas delivered will be 0.60 <strong>and</strong> the energy content is 1 CFH = 1000<br />

BTUH. The 2psi line pressure chart with a pressure drop of 1psi can be used. This will supply the regulators with the 1psi<br />

inlet pressure required for full capacity flow.<br />

Fig. 3-18<br />

Table 3-11<br />

Section Description Load Delivered by Section Section Length Run Length Tube Size<br />

“A” – Trunk 1250 CFH = 1,250,000 BTUH 15 feet 60 feet 1-1/4" CSST<br />

“B” – Trunk 1000 CFH = 1,000,000 BTUH 15 feet 60 feet 1" CSST<br />

“C” – Trunk 750 CFH = 750,000 BTUH 15 feet 60 feet 1" CSST<br />

“D” – Air H<strong>and</strong>ler 500 CFH = 500,000 BTUH 15 feet 60 feet 1" CSST<br />

“E” – Make-Up Air Unit 250 CFH = 250,000 BTUH 10 feet 25 feet 1/2" CSST<br />

“F” – Make-Up Air Unit 250 CFH = 250,000 BTUH 10 feet 55 feet 1/2" CSST<br />

“G” – Make-Up Air Unit 250 CFH = 250,000 BTUH 10 feet 40 feet 1/2" CSST<br />

Run Length for Trunk Sections = Distance from meter to furthest appliance (Longest Run)<br />

Run Length for Appliance Sections = Distance from meter to each appliance<br />

SIZING RUN “A”<br />

Run “A” is sized by the total load of all appliances <strong>and</strong> the run length from the meter to the furthest appliance<br />

The total load of all appliances is 250 + 250 + 250 + 500 = 1250CFH<br />

The run length to the Air H<strong>and</strong>ler (furthest appliance) is 15 + 15 + 15 + 15 = 60ft<br />

Referring to Table 7-10 (2psi line pressure, 1psi pressure drop): for a 60ft run, 1-1/4" CSST has a capacity over 1250CFH<br />

(actual: 1838)<br />

Gastite Division<br />

603 Hendee Street / Springfield, MA 01104<br />

800.662.0208 / www.gastite.com / gastite@gastite.com