Section 3: System Configuration<br />
40<br />
August 2010<br />
SIZING RUN “B”<br />
Run “B” is sized by the load of the supplied appliance <strong>and</strong> the section length<br />
The load of the furnace is 80CFH<br />
The section length to the furnace is 15ft<br />
Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 80CFH load, 1/2" CSST has a drop of 0.035"WC / ft.<br />
The pressure drop over Run “B” is: 0.035" x 15ft = 0.525"WC<br />
The available pressure at the end of run “B” is 6.055"WC - 0.525"WC = 5.530"WC<br />
SIZING RUN “C”<br />
Run “C” is sized by the load of the supplied appliance <strong>and</strong> the section length<br />
The load of the water heater is 36CFH<br />
The section length is 10ft<br />
Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 40CFH load, 3/8" CSST has a drop of 0.075"WC / ft.<br />
The pressure drop over Run “C” is: 0.075" x 10ft = 0.750"WC<br />
The available pressure at the end of run “C” is 6.055"WC - 0.750"WC = 5.305"WC<br />
SIZING RUN “D”<br />
Run “D” is sized by the load of the supplied appliance <strong>and</strong> the section length<br />
The load of the range is 52CFH<br />
The section length is 20ft<br />
Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 60CFH load, 1/2" CSST has a drop of 0.020"WC / ft.<br />
The pressure drop over Run “D” is: 0.020" x 20ft = 0.400"WC<br />
The available pressure at the end of run “D” is 6.055"WC - 0.400"WC = 5.655"WC<br />
SIZING RUN “E”<br />
Run “E” is sized by the total load of all supplied appliances <strong>and</strong> the section length<br />
The total load of the BBQ <strong>and</strong> the dryer is 25 + 28 = 53CFH<br />
The section length is 20ft<br />
Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 60CFH load, 1/2" CSST has a drop of 0.020"WC / ft.<br />
The pressure drop over Run “E” is: 0.020" x 20ft = 0.400"WC<br />
The available pressure at the end of run “E” is 6.055"WC - 0.400"WC = 5.655"WC<br />
SIZING RUN “F”<br />
Run “F” is sized by the load of the supplied appliance <strong>and</strong> the section length<br />
The load of the dryer is 28CFH<br />
The section length 5ft<br />
Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 30CFH load, 3/8" CSST has a drop of 0.044"WC / ft.<br />
The pressure drop over Run “F” is: 0.044" x 5ft = 0.220"WC<br />
The available pressure at the end of run “F” is 5.655"WC - 0.220"WC = 5.435"WC<br />
SIZING RUN “G”<br />
Run “G” is sized by the total load of the supplied appliance <strong>and</strong> the section length<br />
The load of the BBQ is 25CFH<br />
The section length 5ft<br />
Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 30CFH load, 3/8" CSST has a drop of 0.044"WC / ft.<br />
The pressure drop over Run “G” is: 0.044" x 5ft = 0.220"WC<br />
The available pressure at the end of run “G” is 5.655"WC - 0.220"WC = 5.435"WC<br />
Gastite Division<br />
603 Hendee Street / Springfield, MA 01104<br />