12.01.2013 Views

Design and Installation Guide - CT.gov

Design and Installation Guide - CT.gov

Design and Installation Guide - CT.gov

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Section 3: System Configuration<br />

40<br />

August 2010<br />

SIZING RUN “B”<br />

Run “B” is sized by the load of the supplied appliance <strong>and</strong> the section length<br />

The load of the furnace is 80CFH<br />

The section length to the furnace is 15ft<br />

Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 80CFH load, 1/2" CSST has a drop of 0.035"WC / ft.<br />

The pressure drop over Run “B” is: 0.035" x 15ft = 0.525"WC<br />

The available pressure at the end of run “B” is 6.055"WC - 0.525"WC = 5.530"WC<br />

SIZING RUN “C”<br />

Run “C” is sized by the load of the supplied appliance <strong>and</strong> the section length<br />

The load of the water heater is 36CFH<br />

The section length is 10ft<br />

Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 40CFH load, 3/8" CSST has a drop of 0.075"WC / ft.<br />

The pressure drop over Run “C” is: 0.075" x 10ft = 0.750"WC<br />

The available pressure at the end of run “C” is 6.055"WC - 0.750"WC = 5.305"WC<br />

SIZING RUN “D”<br />

Run “D” is sized by the load of the supplied appliance <strong>and</strong> the section length<br />

The load of the range is 52CFH<br />

The section length is 20ft<br />

Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 60CFH load, 1/2" CSST has a drop of 0.020"WC / ft.<br />

The pressure drop over Run “D” is: 0.020" x 20ft = 0.400"WC<br />

The available pressure at the end of run “D” is 6.055"WC - 0.400"WC = 5.655"WC<br />

SIZING RUN “E”<br />

Run “E” is sized by the total load of all supplied appliances <strong>and</strong> the section length<br />

The total load of the BBQ <strong>and</strong> the dryer is 25 + 28 = 53CFH<br />

The section length is 20ft<br />

Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 60CFH load, 1/2" CSST has a drop of 0.020"WC / ft.<br />

The pressure drop over Run “E” is: 0.020" x 20ft = 0.400"WC<br />

The available pressure at the end of run “E” is 6.055"WC - 0.400"WC = 5.655"WC<br />

SIZING RUN “F”<br />

Run “F” is sized by the load of the supplied appliance <strong>and</strong> the section length<br />

The load of the dryer is 28CFH<br />

The section length 5ft<br />

Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 30CFH load, 3/8" CSST has a drop of 0.044"WC / ft.<br />

The pressure drop over Run “F” is: 0.044" x 5ft = 0.220"WC<br />

The available pressure at the end of run “F” is 5.655"WC - 0.220"WC = 5.435"WC<br />

SIZING RUN “G”<br />

Run “G” is sized by the total load of the supplied appliance <strong>and</strong> the section length<br />

The load of the BBQ is 25CFH<br />

The section length 5ft<br />

Referring to Table 7-19 (Pressure drop for Gastite ® CSST): for a 30CFH load, 3/8" CSST has a drop of 0.044"WC / ft.<br />

The pressure drop over Run “G” is: 0.044" x 5ft = 0.220"WC<br />

The available pressure at the end of run “G” is 5.655"WC - 0.220"WC = 5.435"WC<br />

Gastite Division<br />

603 Hendee Street / Springfield, MA 01104<br />

800.662.0208 / www.gastite.com / gastite@gastite.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!