Section 3: System Configuration<br />
34<br />
August 2010<br />
SIZING RUN “E”<br />
Run “E” is sized by the load of all supplied appliances <strong>and</strong> the run length from the meter to the farthest regulator<br />
The total load of all appliances is 28 + 25 = 53CFH<br />
The run length to the farthest regulator is 45 + 20 = 65ft<br />
Referring to Table 7-10 (2psi with a 1psi drop): for a 70-ft run, 3/8" CSST has a capacity over 53CFH (93 actual)<br />
NOTE: Gastite ® recommends that trunk lines be 1/2" minimum. Therefore, this trunk run should be upsized to 1/2".<br />