Electrical Data - 3 Comp High Efficiency<br />
YCIV E/V<br />
See page 138 for Electrical Data footnotes.<br />
122<br />
0267<br />
Model No./Nameplate<br />
Input Volts<br />
Input Freq<br />
(9)<br />
System 1 System 2<br />
Std. & Ultra Quiet Cond. Fans High Head/Static Cond. Fans Two-<strong>Speed</strong> Cond. Fans Std. & Ultra Quiet Cond. Fans<br />
Comp. Condenser Fans Comp. Condenser Fans Comp. Condenser Fans Comp. Condenser Fans<br />
rLA (5) Qty. FLA (EA) rLA (5) Qty. FLA (EA) rLA (5) Qty. FLA (EA) rLA (5) Qty. FLA (EA)<br />
460 60 142 5 2.8 142 5 2.8<br />
380 60 179 5 3.5 179 5 9.3 179 4 3.5<br />
1050 400 50 170 5 3.1 170 5 9.3 180 5 3.8 170 5 3.1<br />
0287<br />
460 60 137 5 2.8 137 5 2.8<br />
380 60 173 5 3.5 173 5 9.3 173 5 3.5<br />
1120 400 50 164 5 3.1 164 5 9.3 173 5 3.8 164 5 3.1<br />
0327<br />
460 60 152 5 2.8 152 5 2.8<br />
380 60 193 5 3.5 193 5 9.3 193 5 3.5<br />
1220 400 50 183 5 3.1 183 5 9.3 194 5 3.8 183 5 3.1<br />
0357<br />
460 60 181 6 2.8 181 6 2.8<br />
380 60 229 6 3.5 229 6 9.3 229 6 3.5<br />
1380 400 50 218 6 3.1 218 6 9.3 229 6 3.8 218 6 3.1<br />
YCIV S/P<br />
0287<br />
Control<br />
KVA (7)<br />
Unit Short Circuit<br />
Withstand (KA)<br />
Terminal Block<br />
(STD)<br />
Circuit Breaker<br />
(OPT)<br />
Minimum Ckt.<br />
Ampacity (MCA)<br />
(3)<br />
Field Wiring & Protection<br />
Std. & Ultra Quiet Cond. Fans High Head/High Static Fans<br />
Recommended<br />
Fuse/Ckt.<br />
Breaker Rating<br />
(4)<br />
Max. Inverse<br />
Time Ckt. Brkr.<br />
rating (2)<br />
Max Dual<br />
Element Fuse<br />
Size (2)<br />
2.4 30KA 65KA 463 600 600 600<br />
Minimum Ckt.<br />
Ampacity (MCA)<br />
(3)<br />
Recommended<br />
Fuse/Ckt.<br />
Breaker Rating<br />
(4)<br />
2.4 30KA 65KA 581 700 700 700 632 800<br />
1070 2.4 30KA 65KA 552 600 700 700 639 700<br />
0307<br />
2.4 30KA 65KA 486 600 600 600<br />
2.4 30KA 65KA 610 700 700 700 659 800<br />
1180 2.4 30KA 65KA 580 700 700 700 673 800<br />
0357<br />
2.4 30KA 65KA 528 600 600 600<br />
2.4 30KA 65KA 667 800 800 800 728 800<br />
1340 2.4 30KA 65KA 631 700 800 800 730 800<br />
0397<br />
2.4 30KA 65KA 598 700 700 700<br />
2.4 30KA 65KA 755 800 800 800 818 1000<br />
1500 2.4 30KA 65KA 713 800 800 800 824 1000<br />