MODEL: YCIV1220E/V<br />

NOTES:<br />

1. kWo = Unit kW Cooling Capacity Output<br />

JOHNSON CONTROLS<br />

AIR TEMPERATURE ON - CONDENSER (°C)<br />

FORM 201.23-EG1 (209)<br />

LCWT<br />

25.0 30.0 35.0 40.0 45.0 46.0<br />

(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP<br />

5.0 1082.7 247.9 3.9 1064.7 284.7 3.4 1044.3 326.4 3.0 1013.0 371.0 2.6 979.4 403.3 2.3 967.0 407.5 2.2<br />

6.0 1113.5 249.6 4.0 1094.7 285.8 3.5 1073.2 327.3 3.0 1038.5 371.1 2.6 1002.8 403.6 2.3 989.8 407.9 2.3<br />

7.0 1145.0 251.6 4.1 1125.3 287.1 3.6 1102.8 328.3 3.1 1064.7 371.1 2.7 1026.6 403.6 2.4 1013.3 408.0 2.3<br />

8.0 1177.1 253.9 4.2 1156.5 288.5 3.7 1133.0 329.5 3.2 1091.4 371.0 2.7 1050.8 403.5 2.4 1037.2 408.0 2.4<br />

9.0 1209.8 256.5 4.3 1188.4 290.3 3.8 1164.0 330.7 3.3 1118.6 370.9 2.8 1075.6 403.2 2.5 1061.5 407.8 2.4<br />

10.0 1243.2 259.3 4.3 1221.0 292.3 3.8 1195.5 332.2 3.3 1146.4 370.9 2.9 1100.7 402.8 2.6 1074.3 400.4 2.5<br />

11.0 1277.2 262.6 4.4 1254.2 294.7 3.9 1227.8 333.8 3.4 1174.3 370.9 3.0 1126.5 402.3 2.6 1084.3 390.9 2.6<br />

12.0 1311.9 266.1 4.5 1288.1 297.2 4.0 1260.7 335.7 3.5 1201.8 370.4 3.0 1152.6 401.8 2.7 1094.4 381.4 2.7<br />

13.0 1347.3 270.1 4.5 1322.6 300.0 4.1 1294.1 337.9 3.6 1229.8 370.1 3.1 1170.5 396.1 2.8 1103.4 371.6 2.8<br />

MODEL: YCIV1380E/V<br />

AIR TEMPERATURE ON - CONDENSER (°C)<br />

LCWT<br />

25.0 30.0 35.0 40.0 45.0 46.0<br />

(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi<br />

COP<br />

5.0 1228.4 287.0 3.9 1206.7 325.4 3.4 1181.0 367.8 3.0 1146.5 415.9 2.6 1124.2 462.3 2.3 1113.1 469.5 2.2<br />

6.0 1263.2 289.6 4.0 1241.1 327.6 3.5 1214.5 370.0 3.0 1177.1 417.5 2.6 1152.5 463.6 2.3 1141.2 470.8 2.3<br />

7.0 1298.8 292.2 4.0 1276.1 330.0 3.5 1248.7 372.3 3.1 1208.5 419.0 2.7 1181.6 464.8 2.4 1169.7 472.1 2.3<br />

8.0 1334.9 295.0 4.1 1311.8 332.6 3.6 1283.4 374.9 3.2 1240.5 420.6 2.8 1211.3 466.0 2.4 1194.3 470.2 2.4<br />

9.0 1371.6 298.1 4.2 1348.0 335.4 3.7 1318.9 377.4 3.2 1273.1 422.2 2.8 1241.6 467.1 2.5 1205.5 459.4 2.5<br />

10.0 1409.1 301.3 4.3 1384.9 338.3 3.8 1355.0 380.2 3.3 1306.1 424.0 2.9 1272.4 468.4 2.6 1216.2 448.4 2.5<br />

11.0 1447.1 304.6 4.3 1422.5 341.3 3.8 1391.8 383.1 3.4 1339.8 425.7 2.9 1296.7 465.0 2.6 1226.4 437.2 2.6<br />

12.0 1485.7 308.3 4.4 1460.6 344.7 3.9 1429.2 386.1 3.4 1372.9 427.0 3.0 1307.9 453.3 2.7 1235.5 426.6 2.7<br />

13.0 1525.2 311.0 4.5 1499.4 348.1 4.0 1467.3 389.3 3.5 1406.5 428.4 3.1 1318.4 441.7 2.8 1244.3 416.6 2.8<br />

2. kWi = Compressor kW Input<br />

3. COP = Coefficient of Performance (includes condenser fan power)<br />

4. LCWT = Leaving Chilled Water Temperature<br />

5. Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m 2 – °C)/kW<br />

6. ARI 550/590 does not provide certification for 50Hz ratings. The unique use of the YCIV variable speed drive allows compressor operation at the output speed regardless of the input<br />

power frequency. This allows for common unit/heat exchanger configurations between 60Hz and 50Hz <strong>with</strong> closely matching capacity.<br />