13.01.2013 Views

Air-Cooled Screw Liquid Chillers with Variable Speed ... - Aireyork

Air-Cooled Screw Liquid Chillers with Variable Speed ... - Aireyork

Air-Cooled Screw Liquid Chillers with Variable Speed ... - Aireyork

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

MODEL: YCIV0197E/V<br />

NOTES:<br />

JOHNSON CONTROLS<br />

AIR TEMPERATURE ON - CONDENSER (°C)<br />

FORM 201.23-EG1 (209)<br />

LCWT<br />

25 30 35 40 45 46<br />

(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP<br />

5.0 672.7 158.3 3.8 661.6 182.6 3.3 648.7 210.3 2.9 631.4 241.5 2.4 607.1 260.8 2.2 599.3 263.5 2.1<br />

6.0 691.7 159.3 3.9 680.1 183.1 3.4 666.7 210.7 2.9 647.0 241.1 2.5 621.7 260.9 2.2 613.7 263.7 2.2<br />

7.0 711.0 160.5 4.0 699.0 183.7 3.5 685.1 211.1 3.0 662.9 240.6 2.6 636.5 260.9 2.3 628.4 263.8 2.2<br />

8.0 730.8 162.0 4.1 718.3 184.6 3.6 703.9 211.6 3.1 678.8 240.1 2.6 651.7 260.7 2.4 643.3 263.7 2.3<br />

9.0 750.9 163.6 4.2 737.9 185.6 3.7 723.0 212.2 3.2 695.2 239.6 2.7 667.2 260.4 2.4 658.5 263.4 2.4<br />

10.0 771.3 165.6 4.2 758.0 186.7 3.7 742.4 213.0 3.2 711.9 239.0 2.8 682.9 260.0 2.5 674.0 263.1 2.4<br />

11.0 792.1 167.8 4.3 778.4 188.1 3.8 762.2 213.9 3.3 728.8 238.5 2.9 698.9 259.5 2.5 689.7 262.7 2.5<br />

12.0 813.3 170.2 4.4 799.1 189.8 3.9 782.4 214.9 3.4 745.9 238.1 2.9 715.0 259.0 2.6 705.0 261.7 2.5<br />

13.0 834.9 172.9 4.4 820.2 191.6 3.9 803.0 216.1 3.5 763.0 237.8 3.0 731.6 258.5 2.7 710.9 255.0 2.6<br />

MODEL: YCIV0207E/V<br />

AIR TEMPERATURE ON - CONDENSER (°C)<br />

LCWT<br />

25 30 35 40 45 46<br />

(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP<br />

5.0 715.1 166.5 3.9 703.9 191.2 3.4 691.1 219.2 2.9 672.4 250.0 2.5 652.7 273.2 2.2 644.7 276.1 2.2<br />

6.0 735.3 167.7 4.0 723.6 191.9 3.4 710.2 219.8 3.0 689.7 250.2 2.6 668.3 273.3 2.3 660.0 276.3 2.2<br />

7.0 755.9 169.0 4.0 743.7 192.7 3.5 729.7 220.4 3.1 707.4 250.3 2.6 684.3 273.3 2.4 675.7 276.4 2.3<br />

8.0 776.9 170.5 4.1 764.2 193.7 3.6 749.5 221.1 3.1 725.4 250.4 2.7 700.4 273.2 2.4 691.7 276.3 2.4<br />

9.0 798.4 172.3 4.2 785.1 194.9 3.7 769.8 222.0 3.2 743.7 250.5 2.8 717.0 272.9 2.5 707.9 276.1 2.4<br />

10.0 820.2 174.2 4.3 806.4 196.2 3.8 790.5 222.9 3.3 762.5 250.6 2.8 733.7 272.6 2.5 716.0 270.7 2.5<br />

11.0 842.4 176.4 4.3 828.1 197.7 3.8 811.6 223.9 3.4 781.3 250.8 2.9 750.9 272.3 2.6 722.8 264.2 2.6<br />

12.0 864.5 178.7 4.4 850.1 199.4 3.9 833.1 225.2 3.4 799.5 250.5 3.0 768.2 271.9 2.7 729.6 257.7 2.6<br />

13.0 887.0 181.3 4.4 872.1 201.3 4.0 854.8 226.6 3.5 818.1 250.3 3.0 780.0 267.9 2.7 735.8 251.0 2.7<br />

MODEL: YCIV0227E/V<br />

AIR TEMPERATURE ON - CONDENSER (°C)<br />

LCWT<br />

25 30 35 40 45 46<br />

(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi<br />

COP<br />

5.0 743.0 172.5 3.9 731.8 196.6 3.4 718.8 223.9 3.0 703.0 255.9 2.6 685.2 280.8 2.3 676.9 283.8 2.2<br />

6.0 764.0 173.7 3.9 752.3 197.7 3.5 738.8 224.8 3.0 722.2 256.8 2.6 701.8 280.9 2.3 693.2 284.0 2.3<br />

7.0 785.4 175.2 4.0 773.3 198.8 3.5 759.2 225.7 3.1 741.8 257.9 2.7 718.6 281.0 2.4 709.9 284.2 2.3<br />

8.0 807.2 176.7 4.1 794.7 200.0 3.6 780.0 226.8 3.2 761.9 259.0 2.7 735.8 281.1 2.4 726.7 284.3 2.4<br />

9.0 829.4 178.3 4.2 816.5 201.3 3.7 801.2 227.9 3.2 782.3 260.0 2.8 753.3 281.1 2.5 744.0 284.3 2.4<br />

10.0 851.7 180.1 4.3 838.7 202.8 3.8 822.9 229.1 3.3 801.1 260.0 2.9 771.2 281.0 2.6 761.5 284.2 2.5<br />

11.0 874.2 182.1 4.3 860.8 204.3 3.8 844.9 230.4 3.4 820.0 260.1 2.9 789.1 281.0 2.6 779.4 284.2 2.6<br />

12.0 897.1 184.2 4.4 883.2 206.0 3.9 866.8 231.9 3.4 839.3 260.1 3.0 807.6 280.9 2.7 797.4 284.1 2.6<br />

13.0 920.3 186.4 4.5 906.1 207.7 4.0 889.1 233.4 3.5 858.7 260.2 3.1 826.3 280.8 2.8 815.9 284.0 2.7<br />

1. kW = Compressor Input Power<br />

2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KW)<br />

3. LCWT = Leaving Chilled Water Temperature<br />

4. Ratings based on 2.4 GPM cooler water per ton<br />

5. Rated IAW ARI Standard 550/590-98. ARI 550/590 does not provide certification for 50Hz ratings. The unique use of the YCIV variable speed drive allows compressor operation at the output<br />

speed regardless of the input power frequency. This allows for common unit/heat exchanger configurations between 60Hz and 50Hz <strong>with</strong> closely matching capacity.<br />

29