13.01.2013 Views

Air-Cooled Screw Liquid Chillers with Variable Speed ... - Aireyork

Air-Cooled Screw Liquid Chillers with Variable Speed ... - Aireyork

Air-Cooled Screw Liquid Chillers with Variable Speed ... - Aireyork

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

MODEL: YCIV0760E/V<br />

NOTES:<br />

1. kWo = Unit kW Cooling Capacity Output<br />

JOHNSON CONTROLS<br />

AIR TEMPERATURE ON - CONDENSER (°C)<br />

FORM 201.23-EG1 (209)<br />

LCWT<br />

25.0 30.0 35.0 40.0 45.0 46.0<br />

(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP<br />

5.0 672.7 155.1 3.9 661.6 178.9 3.4 648.7 206.1 2.9 631.4 236.7 2.5 607.1 255.6 2.2 599.3 258.2 2.2<br />

6.0 691.7 156.1 4.0 680.1 179.4 3.5 666.7 206.4 3.0 647.0 236.3 2.6 621.7 255.7 2.3 613.7 258.5 2.2<br />

7.0 711.0 157.3 4.1 699.0 180.0 3.6 685.1 206.8 3.1 662.9 235.8 2.6 636.5 255.7 2.3 628.4 258.5 2.3<br />

8.0 730.8 158.7 4.2 718.3 180.9 3.6 703.9 207.3 3.1 678.8 235.3 2.7 651.7 255.5 2.4 643.3 258.4 2.3<br />

9.0 750.9 160.4 4.2 737.9 181.8 3.7 723.0 207.9 3.2 695.2 234.8 2.8 667.2 255.2 2.5 658.5 258.2 2.4<br />

10.0 771.3 162.3 4.3 758.0 183.0 3.8 742.4 208.8 3.3 711.9 234.3 2.8 682.9 254.8 2.5 674.0 257.8 2.5<br />

11.0 792.1 164.4 4.4 778.4 184.3 3.9 762.2 209.6 3.4 728.8 233.8 2.9 698.9 254.3 2.6 689.7 257.4 2.5<br />

12.0 813.3 166.8 4.4 799.1 186.0 3.9 782.4 210.6 3.4 745.9 233.3 3.0 715.0 253.9 2.6 705.0 256.5 2.6<br />

13.0 834.9 169.5 4.5 820.2 187.8 4.0 803.0 211.8 3.5 763.0 233.0 3.1 731.6 253.3 2.7 710.9 249.9 2.7<br />

MODEL: YCIV0800E/V<br />

AIR TEMPERATURE ON - CONDENSER (°C)<br />

LCWT<br />

25.0 30.0 35.0 40.0 45.0 46.0<br />

(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP<br />

5.0 715.1 163.2 3.9 703.9 187.3 3.4 691.1 214.8 3.0 672.4 245.0 2.6 652.7 267.8 2.3 644.7 270.6 2.2<br />

6.0 735.3 164.3 4.0 723.6 188.0 3.5 710.2 215.4 3.0 689.7 245.2 2.6 668.3 267.9 2.3 660.0 270.8 2.3<br />

7.0 755.9 165.6 4.1 743.7 188.9 3.6 729.7 216.0 3.1 707.4 245.3 2.7 684.3 267.8 2.4 675.7 270.9 2.3<br />

8.0 776.9 167.1 4.2 764.2 189.8 3.7 749.5 216.7 3.2 725.4 245.4 2.8 700.4 267.7 2.5 691.7 270.8 2.4<br />

9.0 798.4 168.8 4.3 785.1 191.0 3.8 769.8 217.5 3.3 743.7 245.5 2.8 717.0 267.5 2.5 707.9 270.6 2.5<br />

10.0 820.2 170.7 4.3 806.4 192.3 3.8 790.5 218.4 3.3 762.5 245.6 2.9 733.7 267.2 2.6 716.0 265.3 2.5<br />

11.0 842.4 172.9 4.4 828.1 193.8 3.9 811.6 219.5 3.4 781.3 245.8 3.0 750.9 266.8 2.6 722.8 258.9 2.6<br />

12.0 864.5 175.1 4.5 850.1 195.4 4.0 833.1 220.7 3.5 799.5 245.5 3.0 768.2 266.5 2.7 729.6 252.5 2.7<br />

13.0 887.0 177.7 4.5 872.1 197.2 4.0 854.8 222.1 3.6 818.1 245.3 3.1 780.0 262.5 2.8 735.8 246.0 2.8<br />

MODEL: YCIV0830E/V<br />

AIR TEMPERATURE ON - CONDENSER (°C)<br />

LCWT<br />

25.0 30.0 35.0 40.0 45.0 46.0<br />

(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi<br />

COP<br />

5.0 743.0 169.0 3.9 731.8 192.7 3.4 718.8 219.4 3.0 703.0 250.7 2.6 685.2 275.1 2.3 676.9 278.2 2.3<br />

6.0 764.0 170.2 4.0 752.3 193.7 3.5 738.8 220.3 3.1 722.2 251.7 2.7 701.8 275.3 2.4 693.2 278.4 2.3<br />

7.0 785.4 171.7 4.1 773.3 194.8 3.6 759.2 221.2 3.2 741.8 252.8 2.7 718.6 275.4 2.4 709.9 278.5 2.4<br />

8.0 807.2 173.1 4.2 794.7 196.0 3.7 780.0 222.3 3.2 761.9 253.8 2.8 735.8 275.5 2.5 726.7 278.6 2.4<br />

9.0 829.4 174.8 4.3 816.5 197.2 3.8 801.2 223.4 3.3 782.3 254.8 2.9 753.3 275.4 2.6 744.0 278.6 2.5<br />

10.0 851.7 176.5 4.3 838.7 198.7 3.8 822.9 224.6 3.4 801.1 254.8 2.9 771.2 275.4 2.6 761.5 278.5 2.6<br />

11.0 874.2 178.4 4.4 860.8 200.2 3.9 844.9 225.8 3.4 820.0 254.9 3.0 789.1 275.4 2.7 779.4 278.5 2.6<br />

12.0 897.1 180.5 4.5 883.2 201.8 4.0 866.8 227.3 3.5 839.3 254.9 3.1 807.6 275.3 2.7 797.4 278.4 2.7<br />

13.0 920.3 182.6 4.5 906.1 203.6 4.1 889.1 228.7 3.6 858.7 255.0 3.1 826.3 275.2 2.8 815.9 278.3 2.7<br />

2. kWi = Compressor kW Input<br />

3. COP = Coefficient of Performance (includes condenser fan power)<br />

4. LCWT = Leaving Chilled Water Temperature<br />

5. Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m 2 – °C)/kW<br />

6. ARI 550/590 does not provide certification for 50Hz ratings. The unique use of the YCIV variable speed drive allows compressor operation at the output speed regardless of the input<br />

power frequency. This allows for common unit/heat exchanger configurations between 60Hz and 50Hz <strong>with</strong> closely matching capacity.<br />