Functions<br />

12<br />

L1<br />

L2<br />

L3<br />

<strong>71</strong> <strong>Series</strong> - <strong>Monitoring</strong> <strong>relays</strong> <strong>10</strong> A<br />

Type <strong>71</strong>.31.8.400.2000 Switch off<br />

A1 A2 A3<br />

1 3 5 7 9<br />

3~U ASY<br />

2 4 6 8 <strong>10</strong><br />

14 12 11<br />

U= 400 V AC 3~<br />

(50/60 Hz )<br />

Type <strong>71</strong>.41.8.230.<strong>10</strong>21 Switch off<br />

ULo – mode<br />

If the monitored value is<br />

Programmable<br />

less than the lowerlimit<br />

and, time T has<br />

expired.<br />

MEMORY ON MEMORY OFF<br />

U Lo...U Lo + Hys U Up...U Up – Hys U Up...U Lo<br />

*RESET MEMORY = Pressing “SET/RESET“ > 1 s<br />

Phase asymmetry<br />

Incorrect phase rotation<br />

Phase loss<br />

LED ASY yellow<br />

Phase asymmetry<br />

LED DEF red<br />

Voltage to A1 (1) and/or<br />

A2 (5) > 1.11 U N<br />

LED ON green<br />

<strong>Monitoring</strong> system is<br />

active and 400 V supply<br />

voltage is connected to<br />

1-5 or A1-A2.<br />

C = output contact<br />

Normally open 11-14<br />

(6-2) closed.<br />

U Up – mode<br />

If the monitored value is<br />

higher than the<br />

upper limit, and<br />

time T has expired.<br />

U Lo U Up – mode<br />

If the monitored value<br />

of voltage is outside<br />

of the upper or lower<br />

voltage limits, and<br />

time T has expired.<br />

Voltage dips < T do<br />

not result in output<br />

relay switching off.<br />

Switch on<br />

U Lo or U Up – modes<br />

When passing the<br />

hysteresis value.<br />

U Lo U Up – mode<br />

When passing the<br />

U Lo or U Up value.<br />

RESET MEMORY<br />

Pressing “SET/RESET”<br />

> 1 sec.<br />

C = output contact<br />

Normally open 11-14<br />

(6-2) closed.<br />