<strong>Features</strong><br />

Universal voltage or current detecting and<br />

monitoring relay<br />

<strong>71</strong>.41.8.230.<strong>10</strong>21 - Voltage monitoring<br />

<strong>71</strong>.51.8.230.<strong>10</strong>21 - Current monitoring<br />

• Zero voltage memory according to<br />

EN 60204-7-5<br />

• Programmable for DC or AC detection level:<br />

- range detecting: upper and lower value<br />

- upper set point minus hysteresis range<br />

(5...50)% for switch on<br />

- lower set point plus hysteresis range<br />

(5...50)% for switch on<br />

• Fault memory<br />

• Electrical isolation between measuring<br />

and supply circuits<br />

• Immune to supply interruptions of < 200 ms<br />

• Wide detecting range:<br />

- voltage: DC (15...700)V, AC (15...480)V<br />

• 35 mm rail (EN 60<strong>71</strong>5) mounting<br />

Contact specification<br />

Contact configuration<br />

Rated current/Maximum peak current A<br />

Rated voltage/Maximum switching voltage V AC<br />

Rated load AC1 VA<br />

Rated load AC15 (230 V AC) VA<br />

Single phase motor rating (230 V AC) kW<br />

Breaking capacity DC1: 30/1<strong>10</strong>/220 V A<br />

Minimum switching load mW (V/mA)<br />

Standard contact material<br />

Supply specification<br />

Nominal voltage (UN) V AC (50/60 Hz)<br />

V DC<br />

Rated power AC/DC VA (50 Hz)/W<br />

Operating range AC<br />

DC<br />

Technical data<br />

Electrical life at rated load AC1 cycles<br />

Detection levels AC(50/60 Hz)/DC<br />

Switch-off/reaction/Start delay<br />

Switch-on level of the detecting level %<br />

Fault memory - programmable<br />

Electrical isolation: Supply to Measuring circuits<br />

Ambient temperature range °C<br />

Protection category<br />

Approvals (according to type)<br />

4<br />

• Programmable universal voltage monitoring<br />

relay<br />

• AC/DC voltage detection - adjustable<br />

• AC (50/60 Hz) (15…480)V<br />

• DC (15...700)V<br />

• Switch-on hysteresis (5…50)%<br />

• Switch-off delay (0.1…12)s<br />

• Programmable universal current monitoring relay<br />

• Usable with current transformer 50/5, <strong>10</strong>0/5,<br />

150/5, 250/5, 300/5, 400/5 or 600/5<br />

1 CO (SPDT) 1 CO (SPDT)<br />

<strong>10</strong>/15 <strong>10</strong>/15<br />

250/400 250/400<br />

2,500 2,500<br />

500 500<br />

0.5 0.5<br />

<strong>10</strong>/0.3/0.12 <strong>10</strong>/0.3/0.12<br />

300 (5/5) 300 (5/5)<br />

AgCdO AgCdO<br />

230 230<br />

— —<br />

4 / — 4 / —<br />

(0.85...1.15)UN (0.85...1.15)UN — —<br />

<strong>10</strong>0 · <strong>10</strong> 3<br />

<strong>71</strong> <strong>Series</strong> - <strong>Monitoring</strong> <strong>relays</strong> <strong>10</strong> A<br />

<strong>71</strong>.41.8.230.<strong>10</strong>21 <strong>71</strong>.51.8.230.<strong>10</strong>21<br />

• AC/DC current detection - adjustable<br />

• AC(50/60Hz) (0.1...<strong>10</strong>)A with current<br />

transformer to 600A<br />

• DC (0.1...<strong>10</strong>)A<br />

• Switch-on hysteresis (5...50)%<br />

• Switch-off delay (0.1…12)s<br />

• Start delay (0.1…20)s<br />

programmable programmable<br />

<strong>10</strong>0 · <strong>10</strong> 3<br />

(15...480)V/(15...700)V (0.1…<strong>10</strong>)A at transducer to 600A / (0.1…<strong>10</strong>)A<br />

(0.1…12)s / < 0.35 s / < 0.5 s (0.1…12)s / < 0.35 s / (0.1…20)s<br />

5…50 5…50<br />

Yes Yes<br />

Yes Yes<br />

–20…+55 –20…+55<br />

IP 20 IP 20<br />

XI-2012, www.findernet.com