14<br />
4<br />
Installing the boiler<br />
4.2 Burner door opening<br />
To open the burner door, electrically disconnect<br />
the burner first if burner is already mounted on the<br />
boiler.<br />
- Remove the 2 hex bolts (Fig. 4a, item 2) below the<br />
burner door opening.<br />
- Swing the burner door open<br />
- Now use top handle to open access door to flue passages.<br />
4.3 Flue gas collector installation<br />
If not pre-assembled, install collector by following steps below:<br />
– Loosen the mounting nuts.<br />
- Apply supplied sealing material on rear boiler<br />
section to tighten the exhaust collector on the<br />
rear section properly (Fig. 4b).<br />
– Mount the collector and tighten the nuts.<br />
- Do not use excessive force to avoid cracking the<br />
collector<br />
4.4 Flue pipe installation<br />
4.4.1 Chimney venting<br />
Refer to Table 11 to determine chimney size requirements<br />
based on boiler size, chimney height and internal flue chase.<br />
Always use a stainless steel chimney liner and cap off at the<br />
top of the chimney in the space between chimney interior<br />
and outside of chimney liner per NFPA 211 Section 12.4.1.2.<br />
Recommended chimney materials are Selkirk SureTemp or<br />
Supervent (JSC) venting materials, or Security Chimneys<br />
Secure Temp ASHT venting materials. All these materials<br />
are approved per UL-103HT.<br />
– Use heavy gauge (26ga. or better) black smoke pipe to<br />
connect to existing chimney.<br />
- Install factory supplied barometric near the boiler.<br />
Inspecting and cleaning existing flue<br />
- Remove blockages and dirt from chimney<br />
- Clean chimney<br />
- Repair or replace faulty sections<br />
- If necessary repair mortar and joints<br />
Minimum Size of Chimney<br />
Follow guidelines below in terms of minimum chimney height<br />
as a function of chimney diameter<br />
Chimney Size<br />
Min. Minimum Height clearance<br />
6" x 6" 17 ft.<br />
7" x 7" 16ft.<br />
8" x 8" 16 ft.<br />
6" round 19 ft.<br />
7" round 17 ft.<br />
Tab. 11 Minimum chimney height<br />
Fig. 4a Burner Door<br />
1.) Eye screws for burner mounting<br />
2.) Hex bolts for door closing<br />
Fig. 4b Flue gas collector installation<br />
To prevent down drafts extend chimney at least<br />
3 feet above the roof opening and at least 2 feet<br />
above any part of the roof within a radius of 10<br />
feet.<br />
Flue pipe Type Minimum clearance<br />
Double-wall L 9"<br />
Single-wall 26ga. 18"<br />
Application of<br />
sealing material<br />
Tab. 12 Minimum clearances to combustible objects for flue<br />
systems<br />
<strong>MESys</strong> <strong>4000</strong> - 6000 Series- Technical specifications are subject to change without prior notice.