4 Installing the boiler<br />

4.9 Installing the aquastat and burner sensors<br />

This pellet boiler/burner system is equipped with an outdoor<br />

sensor to provide outdoor temperature control for system<br />

efficiency optimization. The boiler is equipped with a 3/4”<br />

well for boiler water sensing near the boiler supply tapping.<br />

A Honeywell L4006E aquastat (Fig. 10a) is supplied as a<br />

manual reset high limit control to shut down burner in case of<br />

a high temperature condition.<br />

DANGER: Risk of fatal injury due to electric<br />

shock!<br />

�V<br />

Electrical work may only be carried out by<br />

qualified technicians.<br />

V� Before opening or working on any electrical<br />

equipment isolate it from the power supply<br />

and take steps to ensure it cannot be inadvertently<br />

reconnected.<br />

Warning: Fire hazard from hot boiler components<br />

may damage electrical cables.<br />

V� Make sure that all cables are sheilded in that<br />

way that they cannot come in to contact<br />

with hot boiler parts and are not placed in<br />

hot zones (ie. boiler front door).<br />

V �<br />

Make sure that the boiler is electrically grounded<br />

to NEC requirements.<br />

�V<br />

Identify the boiler sensor as part of the Janfire NH burner<br />

package. Slide contact sleeve (supplied in B-kit) around<br />

PT100 Sensor (Fig. 10b).<br />

�V<br />

Route and insert the boiler sensor under the jacket panels<br />

into the well. Ensure fit to bottom of well.<br />

V� Remove adapter clam off of aquastat. Use the two screws<br />

provided in B-kit to secure aquastat to top rear jacket panel.<br />

V� Uncoil the capillary of the Honeywell and insert into the<br />

well.<br />

V � Use 2 90 degree spacers furnished with the B-kit to<br />

carefully block in the capillary and sensor. Make sure<br />

that boiler sensor and capillary are fully inserted into the<br />

immersion well.<br />

V � Drill holes to fit the aquastat on the boiler jacket.<br />

V � Refer to page 42 in this manual for detailed wiring<br />

instructions of supplied safety componenets.<br />

.�1<br />

Fig. 10a: Aquastat bracket, aquastat and<br />

PT100 boiler sensor installation<br />

mounting.<br />

Set L4006E at 200 degrees F.<br />

PT100<br />

Sensor<br />

Fig. 10b: Sensor and capiallary sensor details<br />

<strong>MESys</strong> <strong>4000</strong> - 6000 Series- Technical specifications are subject to change without prior notice.<br />

Aquastat bulb<br />

Corrugated spaces<br />