Installation and Wiring<br />

The valves should be installed in the horizontal line. Allow 6" for the<br />

cover removal and 16" for complete actuator removal. These actuators<br />

should never be mounted underneath the valve as condensation<br />

can build up and result in a failure of the actuator. Full instructions are<br />

supplied with the product.<br />

Line<br />

Volts<br />

24 VAC Transformer<br />

2 to 10 VDC (-)<br />

Control Signal (+)<br />

2 to 10 VDC (-)<br />

Feedback Signal (+)<br />

24 VAC Transformer<br />

Line<br />

Volts<br />

4 to 20 mA (-)<br />

Control Signal (+)<br />

2 to 10 VDC (-)<br />

Feedback Signal (+)<br />

500<br />

MFT typical 2 to 10 VDC or 4 to 20 mA wiring<br />

Differential Pressures (psi)<br />

Blk (1)<br />

Red (2)<br />

Wht (3)<br />

Wht (5)<br />

NVF24-MFT-US<br />

NVF24-MFT-E-US<br />

Blk (1)<br />

Red (2)<br />

Wht (3)<br />

Wht (5)<br />

NVF24-MFT-US<br />

NVF24-MFT-E-US<br />

Common -<br />

+ Hot<br />

Y 1 Input, 2 to 10V<br />

U Output, 2 to 10V<br />

Common -<br />

+ Hot<br />

Y 1 Input, 2 to 10V<br />

U Output, 2 to 10V<br />

Dimensions and Weights<br />

Weight 4lb (1.8kg)<br />

Dimensions See below<br />

Note: Due to temperature capability limitations, maximum saturated steam inlet pressure is 50 psig. For reduced capacity valves, use the differential<br />

pressures for the next valve size down.<br />

B Series 2-Way and 3-Way Control Valves<br />

ANSI/FCI 70-2 Class IV Shut-off (metal seated trim) for 2-way valves and Class III for 3-way valves<br />

Model 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"<br />

NVF24-MFT-US 150 150 150 92 56 34<br />

NVF24-MFT-E-US 150 150 150 92 56 34<br />

NVG24-MFT-US 150 150 150 150 140 88<br />

ANSI/FCI 70-2 Class VI Shut-off (PTFE soft-seated trim)<br />

Model 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"<br />

NVF24-MFT-US 150 150 150 150 87 62<br />

NVF24-MFT-E-US 150 150 150 150 87 62<br />

NVG24-MFT-US 150 150 150 150 150 135<br />

SPIRA-TROL L and K Series Control Valves<br />

ANSI/FCI 70-2 Class IV Shut-off (metal seated trim)<br />

Model 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"<br />

NVF24-MFT-US 288 206 109 91 13 -<br />

NVF24-MFT-E-US 288 206 109 91 13 -<br />

NVG24-MFT-US 725 661 414 327 115 72<br />

SPIRA-TROL L and K Series Control Valves<br />

ANSI/FCI 70-2 Class VI Shut-off (PTFE soft-seated trim)<br />

Model 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"<br />

NVF24-MFT-US 500 395 263 204 87 62<br />

NVF24-MFT-E-US 500 395 263 204 87 62<br />

NVG24-MFT-US 725 725 568 440 189 135<br />

Spares<br />

No spare parts are available for this actuator range<br />

<strong>Spirax</strong> <strong>Sarco</strong>, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-518-US 08.07<br />

11.0" [279.4mm]<br />

7.05" [179mm]<br />

4.35" [110mm]<br />

Control<br />

Valves<br />

Linear<br />

Actuators<br />

175