Designing of Steam Tracing<br />

Recommended number of 1/2" tracers to meet average requirements<br />

Type A Type B Type C<br />

General frost Where solidi- When solidificaprotection<br />

or fication may tion may occur<br />

where solidi- occur at temps. at temps.<br />

fication may between 75 - between 150 -<br />

occur at temps. 150˚F 300˚F<br />

below 75˚F<br />

<strong>Product</strong> Number of Number of Number of<br />

Line Size 1/2" Tracers 1/2" Tracers 1/2" Tracers<br />

1" 1 1 1<br />

1-1/2" 1 1 2<br />

2" 1 1 2<br />

3" 1 1 3<br />

4" 1 2 3<br />

6" 2 2 3<br />

8" 2 2 3<br />

10"-12" 2 3 6<br />

14"-16" 2 3 8<br />

18"-20" 2 3 10<br />

As a general rule, length of tracers to 3/8" size should not exceed 60 ft. Larger<br />

size tracers should not exceed 150 ft. in length.<br />

Pressure Drop psi/100 ft<br />

15.0<br />

10.0<br />

9.0<br />

8.0<br />

7.0<br />

6.0<br />

5.0<br />

4.0<br />

3.0<br />

2.0<br />

1.0<br />

.9<br />

.8<br />

.7<br />

.6<br />

.5<br />

.4<br />

.3<br />

.2<br />

.1<br />

100<br />

Steam Tracing<br />

Steam Pipe Sizing<br />

Sizing for Pressure Drop per 100 ft. in Schedule 40 Pipe<br />

Divide “Allowable Drop" by pressure factor and use chart to select pipe size.<br />

Based on 100 psig saturated steam<br />

For other pressures, multiply chart ∆P by factor below<br />

Steam Flow lbs/h<br />

Steam Size Connections for Jacketed Lines<br />

<strong>Product</strong> Line Jacket Diameter<br />

Steam<br />

Connection<br />

2-1/2" 4" 1/2"<br />

3" 6" 3/4"<br />

4" 6" 3/4"<br />

6" 8" 3/4"<br />

8" 10" 1"<br />

10" 12" 1"<br />

Length of jacket should not exceed 20 ft. In most cases 1/2" condensate outlet<br />

would be adequate but it is usual to make this same size as the steam connection<br />

as it simplifies installation.<br />

Recommended Header Size<br />

for Supplying Steam Tracer Lines<br />

Header Size Number of 1/2" Tracers<br />

3/4" 2<br />

1" 3 to 5<br />

1-1/2" 6 to 15<br />

2" 16 to 30<br />

Recommended Header Size<br />

for Condensate Lines<br />

Header Size Number of 1/2" Tracers<br />

1" Up to 5<br />

1-1/2" 6 to 10<br />

2" 11 to 25<br />

psig 0 2 5 10 15 20 30 40 60 75 90 100 110 125 150 175 200 225 250 300<br />

factor 6.9 6.0 5.2 4.3 3.6 3.1 2.4 2.0 1.5 1.3 1.1 1.0 0.92 0.83 0.70 0.62 0.55 0.49 0.45 0.38<br />

1/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" 5" 7" 8" 10" 12" 14" 16" 18" 20"<br />

200 300 400 500 1,000 2 3 4 5 10,000 2 3 4 5 6 7 8 100,000 2 3 4 5 1,000,000 2<br />

<strong>Spirax</strong> <strong>Sarco</strong>, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222<br />

350 400 500 600<br />

0.33 0.29 0.23 0.19<br />

24"<br />

Engineering<br />

Data<br />

303