<strong>Portier</strong> <strong>Grand</strong> Water, PGW/PGDW & PGWV/PGDWV<br />

Output power and temperature increase<br />

Fan pos. 95/70 80/60 70/50 60/40 55 /35<br />

t[¡°C] [∆T] [kW] [∆T] [kW] [∆T] [kW] [∆T] [kW] [∆T] [kW]<br />

0 1 49.2 17.7 41.6 15.0 35.3 12.8 29.1 10.5 25.9 9.4<br />

2 45.1 21.2 38.2 17.9 32.4 15.2 26.6 12.5 23.7 11.1<br />

3 39.3 26.9 33.3 23.5 28.2 19.3 23.1 15.9 20.6 14.1<br />

10 1 43.6 15.2 35.9 12.5 29.6 10.3 23.3 8.1 20.1 7.0<br />

2 40.0 18.1 33.0 14.9 27.2 12.3 21.3 9.6 18.3 8.3<br />

3 34.9 23.0 28.8 19.0 23.6 15.6 18.4 12.2 15.8 10.5<br />

15 1 40.7 13.9 33.0 11.3 26.7 9.1 20.3 6.9 17.0 5.8<br />

2 37.4 16.6 30.3 13.5 24.4 10.9 18.5 8.2 15.5 6.9<br />

3 32.6 21.2 26.4 17.2 21.3 13.8 16.0 10.4 13.4 8.7<br />

20 1 37.9 12.7 30.1 10.1 23.7 8.0 17.2 5.8 13.9 4.7<br />

2 34.7 15.2 27.6 12.1 21.7 9.5 15.7 6.9 12.6 5.5<br />

3 30.3 19.3 24.1 15.4 18.9 12.1 13.6 8.7 10.9 6.9<br />

t¡°C = Temperature inlet air<br />

<strong>Portier</strong> <strong>Grand</strong> L Water, PGLW/PGDLW & PGLWV/PGDLWV<br />

Output power and temperature increase<br />

Fan pos. 95/70 80/60 70/50 60/40 55 /35<br />

t[¡°C] [∆T] [kW] [∆T] [kW] [∆T] [kW] [∆T] [kW] [∆T] [kW]<br />

0 1 46.2 33.3 39.1 28.2 33.2 24.0 27.3 19.7 23.3 16.8<br />

2 43.4 37.6 36.7 31.8 31.2 27.0 25.6 22.2 21.8 18.9<br />

3 39.0 45.1 32.7 37.7 28.0 32.3 23.0 26.5 19.6 22.6<br />

10 1 41.0 28.5 33.8 23.5 27.9 19.4 21.9 15.2 17.8 12.4<br />

2 38.5 32.1 31.7 26.5 26.1 21.8 20.5 17.1 16.6 13.9<br />

3 34.6 38.6 28.5 31.8 23.5 26.1 18.4 20.4 14.9 16.6<br />

15 1 38.3 26.2 31.1 21.2 25.1 17.2 19.0 13.0 14.9 10.2<br />

2 36.0 29.5 29.2 24.0 23.6 19.3 17.9 14.7 14.0 11.5<br />

3 32.4 35.4 26.3 28.7 21.1 23.1 16.0 17.5 12.5 13.7<br />

20 1 35.6 23.9 28.3 19.0 22.3 15.0 16.2 10.9 12.0 8.1<br />

2 33.4 27.0 26.6 21.5 20.9 16.9 15.1 12.2 11.2 9.1<br />

3 30.1 32.4 23.9 25.7 18.8 20.2 13.5 14.6 10.1 10.8<br />

t¡°C = Temperature inlet air<br />

Accessories<br />

MP30 & MP32 – control box<br />

MP30 is used for air curtains without<br />

electric heating elements or<br />

with hot water coil and has one<br />

switch only to control the fan<br />

speed (three speeds). MP32 is used<br />

for air curtains with electric heating<br />

elements. It has two switches –<br />

one for regulating the fan speed<br />

and one for regulating the electric heating<br />

power (two positions). One MP can control<br />

up to 4 air curtains.<br />

Enclosure class IP 44<br />

Item numbers MP30/1130, MP32/1140<br />

SR 12 – electrical thermostat<br />

SR12 is a two step electronic thermostat<br />

with internal setting. It<br />

should be connected to the MP<br />

control box.<br />

Enclosure class IP 44<br />

Item number 1120<br />

PBS – wall mounting set<br />

Item number 10695<br />

HDGL – door switch<br />

Position 2<br />

(21-22)<br />

Position 2<br />

(21-22)<br />

RT-0-30 – room thermostat<br />

41 0<br />

30 0<br />

Position 1<br />

(13-14)<br />

-30 0<br />

-41 0<br />

HDGL is an adjustablelength<br />

roller lever with<br />

two positions for regulation<br />

air flow on/off, or<br />

high/low, if combined<br />

with RT 0-30, see below.<br />

Enclosure class IP67<br />

Item number 10016<br />

PGT – joining kit<br />

PGT joins several <strong>Portier</strong> <strong>Grand</strong><br />

air curtains together in order to<br />

make an air curtain of any length<br />

or height. The PGT consists of a<br />

plate and a bracket in metal.<br />

Item number 10612<br />

PBH – pendulum set<br />

<strong>Portier</strong> <strong>Grand</strong> – <strong>Portier</strong> <strong>Grand</strong> D<br />

Pendulum set with adjustable length for<br />

ceiling installations. The rods have a length<br />

of 1000 mm but can be cut for shorter<br />

installations. Item number 10697<br />

Enclosure class IP 30<br />

Item number 5151<br />

Pressure drop [kPa]<br />

Pressure drop PGW/PGLW<br />

PGMBV – vertical<br />

mounting set<br />

PGMBV is<br />

used for vertical<br />

mounting<br />

between the floor and<br />

the first PG/PGD.<br />

Item number 10611<br />

Good ideas when mounting and<br />

installing your <strong>Portier</strong> <strong>Grand</strong> (D)<br />

A = min 80 mm<br />

B = min ~0<br />

Water flow [m 3 /h]<br />

Water flow [l/s]<br />

Remember the<br />

minimum distance<br />

to the ceiling.<br />

For high ceilings when the pendulum set,<br />

PBH, can't be used the air curtain can be<br />

mounted using chains, threaded rods (M6)<br />

or wires.<br />

For wide entrances the joining kit, PGT,<br />

joins several air curtains together although<br />

it looks like it is only one single air curtain.<br />

When vertically mounted it is desired<br />

to put up a stopping wall/plate for best<br />

functionality and comfort.<br />

Stoppi<br />

The airflow direction can be adjusted by<br />

tilting the output lamellas. The electrical<br />

thermostat SR12 – should be put just<br />

beside the entrance.<br />

Wiring diagrams for PG/PGD are found<br />

on page 11.<br />

9<br />

Pressure drop [bar]