<strong>Portier</strong> <strong>Grand</strong> Water, PGW/PGDW & PGWV/PGDWV<br />
Output power and temperature increase<br />
Fan pos. 95/70 80/60 70/50 60/40 55 /35<br />
t[¡°C] [∆T] [kW] [∆T] [kW] [∆T] [kW] [∆T] [kW] [∆T] [kW]<br />
0 1 49.2 17.7 41.6 15.0 35.3 12.8 29.1 10.5 25.9 9.4<br />
2 45.1 21.2 38.2 17.9 32.4 15.2 26.6 12.5 23.7 11.1<br />
3 39.3 26.9 33.3 23.5 28.2 19.3 23.1 15.9 20.6 14.1<br />
10 1 43.6 15.2 35.9 12.5 29.6 10.3 23.3 8.1 20.1 7.0<br />
2 40.0 18.1 33.0 14.9 27.2 12.3 21.3 9.6 18.3 8.3<br />
3 34.9 23.0 28.8 19.0 23.6 15.6 18.4 12.2 15.8 10.5<br />
15 1 40.7 13.9 33.0 11.3 26.7 9.1 20.3 6.9 17.0 5.8<br />
2 37.4 16.6 30.3 13.5 24.4 10.9 18.5 8.2 15.5 6.9<br />
3 32.6 21.2 26.4 17.2 21.3 13.8 16.0 10.4 13.4 8.7<br />
20 1 37.9 12.7 30.1 10.1 23.7 8.0 17.2 5.8 13.9 4.7<br />
2 34.7 15.2 27.6 12.1 21.7 9.5 15.7 6.9 12.6 5.5<br />
3 30.3 19.3 24.1 15.4 18.9 12.1 13.6 8.7 10.9 6.9<br />
t¡°C = Temperature inlet air<br />
<strong>Portier</strong> <strong>Grand</strong> L Water, PGLW/PGDLW & PGLWV/PGDLWV<br />
Output power and temperature increase<br />
Fan pos. 95/70 80/60 70/50 60/40 55 /35<br />
t[¡°C] [∆T] [kW] [∆T] [kW] [∆T] [kW] [∆T] [kW] [∆T] [kW]<br />
0 1 46.2 33.3 39.1 28.2 33.2 24.0 27.3 19.7 23.3 16.8<br />
2 43.4 37.6 36.7 31.8 31.2 27.0 25.6 22.2 21.8 18.9<br />
3 39.0 45.1 32.7 37.7 28.0 32.3 23.0 26.5 19.6 22.6<br />
10 1 41.0 28.5 33.8 23.5 27.9 19.4 21.9 15.2 17.8 12.4<br />
2 38.5 32.1 31.7 26.5 26.1 21.8 20.5 17.1 16.6 13.9<br />
3 34.6 38.6 28.5 31.8 23.5 26.1 18.4 20.4 14.9 16.6<br />
15 1 38.3 26.2 31.1 21.2 25.1 17.2 19.0 13.0 14.9 10.2<br />
2 36.0 29.5 29.2 24.0 23.6 19.3 17.9 14.7 14.0 11.5<br />
3 32.4 35.4 26.3 28.7 21.1 23.1 16.0 17.5 12.5 13.7<br />
20 1 35.6 23.9 28.3 19.0 22.3 15.0 16.2 10.9 12.0 8.1<br />
2 33.4 27.0 26.6 21.5 20.9 16.9 15.1 12.2 11.2 9.1<br />
3 30.1 32.4 23.9 25.7 18.8 20.2 13.5 14.6 10.1 10.8<br />
t¡°C = Temperature inlet air<br />
Accessories<br />
MP30 & MP32 – control box<br />
MP30 is used for air curtains without<br />
electric heating elements or<br />
with hot water coil and has one<br />
switch only to control the fan<br />
speed (three speeds). MP32 is used<br />
for air curtains with electric heating<br />
elements. It has two switches –<br />
one for regulating the fan speed<br />
and one for regulating the electric heating<br />
power (two positions). One MP can control<br />
up to 4 air curtains.<br />
Enclosure class IP 44<br />
Item numbers MP30/1130, MP32/1140<br />
SR 12 – electrical thermostat<br />
SR12 is a two step electronic thermostat<br />
with internal setting. It<br />
should be connected to the MP<br />
control box.<br />
Enclosure class IP 44<br />
Item number 1120<br />
PBS – wall mounting set<br />
Item number 10695<br />
HDGL – door switch<br />
Position 2<br />
(21-22)<br />
Position 2<br />
(21-22)<br />
RT-0-30 – room thermostat<br />
41 0<br />
30 0<br />
Position 1<br />
(13-14)<br />
-30 0<br />
-41 0<br />
HDGL is an adjustablelength<br />
roller lever with<br />
two positions for regulation<br />
air flow on/off, or<br />
high/low, if combined<br />
with RT 0-30, see below.<br />
Enclosure class IP67<br />
Item number 10016<br />
PGT – joining kit<br />
PGT joins several <strong>Portier</strong> <strong>Grand</strong><br />
air curtains together in order to<br />
make an air curtain of any length<br />
or height. The PGT consists of a<br />
plate and a bracket in metal.<br />
Item number 10612<br />
PBH – pendulum set<br />
<strong>Portier</strong> <strong>Grand</strong> – <strong>Portier</strong> <strong>Grand</strong> D<br />
Pendulum set with adjustable length for<br />
ceiling installations. The rods have a length<br />
of 1000 mm but can be cut for shorter<br />
installations. Item number 10697<br />
Enclosure class IP 30<br />
Item number 5151<br />
Pressure drop [kPa]<br />
Pressure drop PGW/PGLW<br />
PGMBV – vertical<br />
mounting set<br />
PGMBV is<br />
used for vertical<br />
mounting<br />
between the floor and<br />
the first PG/PGD.<br />
Item number 10611<br />
Good ideas when mounting and<br />
installing your <strong>Portier</strong> <strong>Grand</strong> (D)<br />
A = min 80 mm<br />
B = min ~0<br />
Water flow [m 3 /h]<br />
Water flow [l/s]<br />
Remember the<br />
minimum distance<br />
to the ceiling.<br />
For high ceilings when the pendulum set,<br />
PBH, can't be used the air curtain can be<br />
mounted using chains, threaded rods (M6)<br />
or wires.<br />
For wide entrances the joining kit, PGT,<br />
joins several air curtains together although<br />
it looks like it is only one single air curtain.<br />
When vertically mounted it is desired<br />
to put up a stopping wall/plate for best<br />
functionality and comfort.<br />
Stoppi<br />
The airflow direction can be adjusted by<br />
tilting the output lamellas. The electrical<br />
thermostat SR12 – should be put just<br />
beside the entrance.<br />
Wiring diagrams for PG/PGD are found<br />
on page 11.<br />
9<br />
Pressure drop [bar]