programmation table of choice for M<br />

remote signalisation module<br />

6 RELAY OUTPUTS<br />

DATA TRANSMISSION OUTPUTS<br />

+ 2 RELAY OUTPUTS<br />

module<br />

terminals number<br />

512 522 532 542 552 562<br />

basic version<br />

M01 Ir Im/I — AS — —<br />

other versions<br />

M02 Ir Im/I Ic 1 Ic2 max.Ic 1 max. Ic2<br />

M03 Ir Im/I Ic 1 Ic2 max.Ic 1 recon. Ic2<br />

M04 Ir Im/I Ic 1 AS max.Ic 1 max. Ic2<br />

M05 Ic2 Im/I Ic 1 AS max.Ic 1 max. Ic2<br />

M06 Ir Im/I Ic 1 AS max.Ic 1 recon. Ic2<br />

M07 Ir Im/I Ih Ic1 max.Ic 1 max. Ic2<br />

M08 Ir Im/I Ih AS Ic 1 Z<br />

M09 Ir Im/I Ih AS max.Ic 1 max. Ic2<br />

M10 Ir Im/I Ih Z max.Ic 1 max. Ic2<br />

M11 Ic 2 Im/I Ih Ic1 max.Ic 1 max. Ic2<br />

M12 Ir Im/I Ih Z max.Ic 1 recon. Ic2<br />

M13 Ic 1 Im/I Ih AS max.Ic 1 max. Ic2<br />

M14 Ic 1 Im/I Ih Z max.Ic 1 max. Ic2<br />

M15 Z Im/I Ih AS max.Ic 1 recon. Ic2<br />

M16 (*) Ir Im I AS Ih –<br />

512 522 532 542 552 562<br />

M17 Im/I Ir<br />

M18 Im/I AS<br />

M19 Ih Im/I<br />

M20 Ih AS<br />

M21 Ih Z<br />

M22 Z AS<br />

M23 Z Ic 1<br />

datatransmission<br />

M24 Z max. Ic 1 e+ e– r+ r–<br />

M25 Ih max. Ic 1 output output input input<br />

M26 Im/I Ic 1<br />

M27 Im/I max. Ic 1<br />

M28 Ic 2 Ic 1<br />

M29 max. Ic 2 max. Ic 1<br />

M30 recon. Ic 2 max. Ic 1<br />

M31 max. Ic 1 AS<br />

M32 — — — — — —<br />

protection<br />

— Ir<br />

➙<br />

long time trip indication<br />

— Im/I<br />

➙<br />

short time or instantaneous<br />

trip indication<br />

— Ih<br />

➙<br />

ground fault trip indication<br />

— Z<br />

➙<br />

zone selective interlocking<br />

output<br />

load monitoring<br />

— Ic 1<br />

➙<br />

indication of Ic 1 threshold<br />

overrun<br />

— Ic 2<br />

➙<br />

indication of Ic 2 threshold<br />

overrun<br />

— max. Ic 1<br />

➙<br />

load monitoring command<br />

according to Ic 1 setting<br />

— max. Ic 2<br />

➙<br />

load monitoring command<br />

according to Ic 2 setting<br />

— recon. Ic 2<br />

➙<br />

load reconnection<br />

command according to<br />

Ic 2 setting<br />

self-monitoring<br />

— AS<br />

➙<br />

indication on control unit<br />

fault or over temperature<br />

(*) The DEMAND current function is not available<br />

with the M16 module.<br />

T2<br />

T1<br />

T21<br />

T22<br />

processing<br />

unit<br />

M17<br />

to<br />

M32<br />

datatransmission<br />

e + e – r + r –<br />

F1<br />

F2<br />

F12<br />

F11 512 522<br />

532<br />

542 552 562<br />

+<br />

–<br />

power supply<br />

(2)<br />

1<br />

2 3 4<br />

(3)<br />

0V<br />

24V<br />

(3)<br />

ET 44 interface (1)<br />

S1 (4) S2 (4)<br />

4<br />

5<br />

8<br />

9<br />

RD–<br />

TD–<br />

RD+<br />

TD+<br />

Sub D 9<br />

connector<br />

(5)<br />

1 3 2 1 3 2<br />

(3)<br />

(1) communication interface for RS 485-9600 bit/s<br />

network.<br />

(2) power supply for M option and ET 44 interface<br />

(AD module).<br />

(3) provided connectors, not provided cable.<br />

(4) remote controlled relay outputs<br />

(10A/220V AC).<br />

(5) JBUS - RS 485-9600 bit/s network.<br />