ENGLISH<br />
13<br />
DIL 1<br />
ON<br />
OFF<br />
Overview of DIL Switch Functions<br />
Single or double-leaf operation<br />
Single-leaf operation<br />
Double-leaf operation<br />
DIL 2<br />
ON<br />
OFF<br />
With/without leaf offset (only with double-leaf operation)<br />
Without leaf offset: leaf A and B open and close simultaneously<br />
With leaf offset: leaf A opens before leaf B and leaf B closes before leaf A<br />
DIL 3<br />
ON<br />
OFF<br />
Leaf selection/size of leaf offset<br />
Leaf B/small leaf offset<br />
Leaf A/large leaf offset<br />
DIL 4<br />
ON<br />
OFF<br />
Normal operation/setup operation<br />
Set-up mode<br />
Normal mode in press-and-release operation<br />
DIL 5 Safety device SE1 in the CLOSE direction (connection at terminal 73)<br />
ON 2-wire photocell<br />
OFF<br />
No safety equipment<br />
DIL 6 DIL 7 Operator function Option relay function<br />
ON ON Automatic timed closing, pre-warning time<br />
for each leaf movement<br />
Relay clocks rapidly during the pre-warning time,<br />
normally during the travel phase and is OFF during<br />
the hold-open phase<br />
OFF ON No automatic timed closing, pre-warning<br />
time for each leaf movement<br />
Relay clocks rapidly during the pre-warning time,<br />
normally during the travel phase<br />
ON OFF Automatic timed closing, pre-warning time<br />
only for automatic timed closing<br />
Relay clocks rapidly during the pre-warning time,<br />
normally during the travel phase and is OFF during<br />
the hold-open phase<br />
OFF OFF No special function Relay picks up in the CLOSE end-of-travel position<br />
DIL 8<br />
ON<br />
OFF<br />
Normal/slow travel speed for all runs<br />
Slow travel speed for all runs<br />
Normal travel speed for all runs<br />