6.3 Further information on various parameters<br />
Parameter 1: Boiler temperature<br />
Used to display the boiler water temperature.<br />
Parameter 2: Flow temperature B<br />
Used to display the boiler water outlet temperature on the valve circuit.<br />
Parameter 3: Gradient of the heating circuit A<br />
The factory setting of the heating curve is 1.5<br />
<br />
30<br />
Maximum boiler temperature<br />
Factory setting: 75 °C<br />
Minimum boiler temperature in comfort mode: 30 °C (Factory<br />
setting)<br />
X Outside temperature<br />
Y Water flow temperature<br />
Parameter 4: Gradient of the heating circuit B<br />
The factory setting of the heating curve is 0.7<br />
<br />
<br />
<br />
Maximum start temperature after valve<br />
Factory setting: 50 °C<br />
Maximum outlet temperature after valve<br />
Factory setting: 20 °C<br />
X Outside temperature<br />
Y Valve start temperature<br />
Parameter 5: Maximum heating circuit<br />
temperature<br />
The flow temperature for the heating circuit can be limited.<br />
For a standard installation without outside sensor, we<br />
recommend to set the maximum temperature of the<br />
heating circuit to a value less than or equal to 75°C.<br />
Parameter 6: Maximum outlet temperature after<br />
valve B<br />
For circuit B, this setting limits the outlet temperature on the<br />
corresponding circuit.<br />
If using underfloor heating, it is imperative to keep the<br />
factory setting of the maximum outlet temperature after the<br />
mixing valve at 50°C.<br />
The regulations also impose an independent safety device<br />
which must cut off the supply of heat to the underfloor<br />
heating circuit when the maximum temperature of the<br />
liquid reaches 65°C. To meet this requirement, a safety<br />
thermostat must be electrically connected to the TS<br />
contact on the pump connector.<br />
Parameter 7: Self-adaptivity<br />
- Enabled (setting 1): automatic setting of the heating curve is<br />
enabled.<br />
- Blocked (setting 0): the heating curve is fixed. It can only be<br />
modified manually.<br />
Parameter 8: Influence of the room sensor<br />
Enables to adjust the influence of the room sensor on the boiler water<br />
temperature.<br />
0: the room sensor is ignored (for example: badly positioned remote<br />
control).<br />
1: Slight influence.<br />
3: Average influence (recommended).<br />
10: operating like room thermostat.<br />
<strong>AD224</strong> - <strong>RS</strong> <strong>100</strong> R 20/04/09 - 300010273-001-B