6.3 Further information on various parameters<br />

Parameter 1: Boiler temperature<br />

Used to display the boiler water temperature.<br />

Parameter 2: Flow temperature B<br />

Used to display the boiler water outlet temperature on the valve circuit.<br />

Parameter 3: Gradient of the heating circuit A<br />

The factory setting of the heating curve is 1.5<br />

<br />

30<br />

Maximum boiler temperature<br />

Factory setting: 75 °C<br />

Minimum boiler temperature in comfort mode: 30 °C (Factory<br />

setting)<br />

X Outside temperature<br />

Y Water flow temperature<br />

Parameter 4: Gradient of the heating circuit B<br />

The factory setting of the heating curve is 0.7<br />

<br />

<br />

<br />

Maximum start temperature after valve<br />

Factory setting: 50 °C<br />

Maximum outlet temperature after valve<br />

Factory setting: 20 °C<br />

X Outside temperature<br />

Y Valve start temperature<br />

Parameter 5: Maximum heating circuit<br />

temperature<br />

The flow temperature for the heating circuit can be limited.<br />

For a standard installation without outside sensor, we<br />

recommend to set the maximum temperature of the<br />

heating circuit to a value less than or equal to 75°C.<br />

Parameter 6: Maximum outlet temperature after<br />

valve B<br />

For circuit B, this setting limits the outlet temperature on the<br />

corresponding circuit.<br />

If using underfloor heating, it is imperative to keep the<br />

factory setting of the maximum outlet temperature after the<br />

mixing valve at 50°C.<br />

The regulations also impose an independent safety device<br />

which must cut off the supply of heat to the underfloor<br />

heating circuit when the maximum temperature of the<br />

liquid reaches 65°C. To meet this requirement, a safety<br />

thermostat must be electrically connected to the TS<br />

contact on the pump connector.<br />

Parameter 7: Self-adaptivity<br />

- Enabled (setting 1): automatic setting of the heating curve is<br />

enabled.<br />

- Blocked (setting 0): the heating curve is fixed. It can only be<br />

modified manually.<br />

Parameter 8: Influence of the room sensor<br />

Enables to adjust the influence of the room sensor on the boiler water<br />

temperature.<br />

0: the room sensor is ignored (for example: badly positioned remote<br />

control).<br />

1: Slight influence.<br />

3: Average influence (recommended).<br />

10: operating like room thermostat.<br />

<strong>AD224</strong> - <strong>RS</strong> <strong>100</strong> R 20/04/09 - 300010273-001-B