Installation Manual
Installation Manual 1
Specification of Neu Plus
1. Electrical 4. Wiring
Type of Measurement
Direct
Wire size
14~24 AWG
Distribution
Maximum phase
Voltage
2-phase 3 wire
3-phase 4 wire
278 V
Strip length
Screw size
Screw Torque
7 mm
M2
0.2 Nm
Maximum Current *
100 A
Terminal Block Series
TBP02P1-381
Frequency
50 or 60 Hz
Material
PA66 (UL94V-0)
Supply voltage
12V DC 1.5 A
Pitch
3.81 mm
2. Mechanical
Dimensions
Weight
Housing material
99 mm x 93.5 mm x
34.2 mm
250 g
PET G
5. Environmental
Operation Temperature 0 °C to 64 °C
6. Storage
Available storage
14 GB
Data transfer interval
5 min
3. Communication
Connection
Wi-Fi or Ethernet
Protocol
802.11 b/g/n
Frequency
2.4 GHz
7. Measurements
Sampling rate
Instant values
1 second
Active energy,
reactive energy,
voltage, current,
power factor,
frequency,
timestamp.
Specification of Neu Plus
10,5
99,0 34,5
10,3
85,1
59,5
93,5
26,2
Safety Precautions
Warning
The Neu Plus device is connected to high and
dangerous voltages. An installation without
caution and safety can be dangerous or
even fatal. Please assure to follow strictly the
following guidelines:
The Neu Plus meter must be installed by
a qualified professional and authorized by
Neu Energy Colombia (or Brazil, depending
on the country)
Questions?
Contact help.neu.energu
Designed by Neu Energy in Medellin, CO
@2021 Neu Energy CO (Razão Social)
Personal Protective Equipment must be
used along the installation of the Current
Transformers and at moments where the
installer exposes his self to hazardous
tensions.
Do not try to open the Neu Plus device,
touch on its internal parts or repair. In case
something is wrong, contact the Neu Plus
representatives.
If you understand that the Current
Transformers, Cables or any equipments
were damaged, do not use them in the
installation.
Install the Neu Plus where there is no
direct sunlight or at extremely high or low
temperatures (0-50ºC). The meter also
should not be exposed to water.
Installation Manual 4
Final
Final Results Preview
V I1 I2 I3
1 2 3 N + - + - + - B A - +
1
2
3
0
4
5
6
7
8
9
0 0 0
0
1
2
3
4
S2
5
6
7
8
R
S2
9
OFF
ON
S
S2
T
Installation Manual 5
Tools Required
(A)Cutting Pliers
(B) Wire Stripping Pliers
Tools Required for Installation
(C) Ferrule Pliers
(D)Electronic Tools Kit
(Or Screw Driver M2)
(E)Screwdriver M6
(C) Ferrule Pliers
Rubber Gloves and Boots Protection Glasses Flashlight
Installation Manual 6
Equipment
(1) 3D Printed Wall
Adapter x1
(2) Power Source x1
Specification of Equipment
(3) Current
Transformers x3
(4) Short Circuit Breaker
x3
(5) Breaker (6) DIN Rail
Installation Manual 7
Specification of Equipment
(7) Outlet (8) Duplex Wire – 2x
2mm
(9) Spiral for Cables
(10) Plastic Straps – 10
mm
(11) Cable White - 5mm (12) Cable Black - 5mm
(13) Cable Identifiers
(14) Double Sided Tape
(15) Self Drilling Screws
M4 x Lenght 16 mm x2
1 2 3
Installation Manual 8
(16) Philps Screws M4
x 2
(17) Fork Terminals – M5
X Cable Diameter 5mm
Specification of Equipment
(18) Insulated Ferrules
(A)
1 Cable Connection
Cable Diameter: 5mm
Pin Length: 8 mm
Pin Diameter: 2 mm
Warning
Neu Plus monitor uses specific electricity material in the
installation and works in high tension voltages. Install only
with the approval of Neu Energy permission and carefully
follow all the instructions of this manual.
(B)
2 Cable Connection
Cable Diameter: 6mm
Pin Length: 12 mm
Pin Diameter: 3 mm
Installation Manual 9
Phase 1: Preparation Of Equipments
1.0 – Preparation
Before we start, it is important to prepare all
the materials and equipment. This involves:
1. Cables measurement, cutting and stripping;
2. Terminals installations
3. Equipment connections.
1.1 – Voltage – Preparing the (11) White Cables
(a) 3x Cut: Neu Plus - Circuit Breaker [5]:
Connect the Insulated Ferrule [18a] at both
ends.
(b) 3x Cut: Circuit Breaker [5] - Voltage
Phases: Connect the Insulated Ferrule [18a]
on one end and the other end with Fork
Terminals [17].
(c)1x Cut: Neu Plus - GDN Line: Connect the
Insulated Ferrule [18a] on one end and the
Fork terminals [17] on the other end.
(d) Using the Cable Identifiers [13] enumerate
them as it is shown in the next image.
1.2 – Currents – Preparing the (12) Black Cables
(a) 6x Cut: Neu Plus - Short Circuit Terminal
[4]: Connect the Insulated Ferrule [18a] at
one end.
(b) 6x Cut: Circuit Terminal [3] - Voltage
Phase: Connect the Insulated Ferrule [18a] at
one end and connect the outputs S1 and S2 of
Current Transformers [3].
(c) 3x Cut: Short Circuit Terminal [4] - Earth:
Connect a Fork terminals [17] to the end of
each cable.
(d) Using the Cable Identifiers [13] enumerate
them as it is shown in the next image.
*Even numbers are positive sides, odd numbers
are negative*
Installation Manual 10
Phase 1: Preparation of Equipments
1.3 – Duplex Wire [8] for Power Source
(a) Cut (1x) Outlet [7] – Voltage & GDN Line.
14x [11]
6x [12]
40x [13]
7x [17]
22x [18A]
Final
1
2
V I1 I2 I3
1 2 3 N + - + - + - B A - +
3
0
4
5
6
7
8
0 0 0
9
0
1
2
3
4
S2
5
6
7
8
R
S2
9
OFF
ON
S
S2
T
Installation Manual 11
Phase 2: Preparation of the Installation
2.0 – Installation of DIN Rail
Pick up the DIN Rail [6] and with the Self
Drilling Screws [14] fix it in an appropriate
space in the wall
Aftet that, clip the disjuntor in the DIN Rail.
1x [5]
1x [6]
2x [15]
1.0
2.1 – Connection of the outlet
and Neu Plus Basis
(A) Pick up the Duplex Wire [8] and the
Outlet [7].
Connect the duplex Wire in the Outlet.
(B) Plug the Neu Plus into its Base [1] and
fix it with the Phillips Screw [15].
1x [1]
1x [7]
1x [8]
2x [16]
1.1.1
1.1
1.1.2
1.2
Installation Manual 12
Phase 1: Preparation of the Installation
2.2 – Connection of Tension Cables
For each fase and Cable [1,2,3] do the
following:
Connect one the other White Cable [11], in
the exit of the Breaker[7].
Connect one of the ends of the White Cable
[11], in the tension’s exit 1 of Neu Plus and in
the exit of the Breaker[7].
1.2
V
Repeat the process for the other White
Cables [11].
I1
I2 I3
1 2 3 N + - + - +
1
2
3
1
2
3
Installation Manual 13
2.3 – Connections of the Short Circuit Terminal
Phase 2: Preparation of the Installation
*Read the Short Circuit Borne Management
Considerations before accomplishing this step*
For Black Cables [12] numbered #4 to #9,
follow the instructions below:
Make sure the Short Circuit Terminal [4] is
closed before making the connection.
Join the two terminalless ends of the Black
Cables #4 [12] in an Insulated Terminal
[18b] and connect them to one of the
inputs of the Short Circuit Terminal [4]
3x [4]
1x [11]
3x [17]
6x [18B]
I3
1.3.1
-
4 B A -
4
Join the two terminalless ends of the Black
Cables #5 [12] with a Black Cable #0
[12] on an Insulated Terminal [18b] and
connect them to the other inputs of the
Short Circuit Terminal [4].
Connect the other end of the Black Cable
#0 [12] to a Fork Terminal [17] and connect
it to ground.
Repeat the process for Black Cables #6 to
#9 [12].
5
0
5
Installation Manual 14
Phase 2: Preparation of the Installation
Short Circuit Borne Management
The installation of the Short Circuit Bornes must be done very carefully.
So certify to follow closely the instructions.
a) Closed Short Circuit Borne b) Opened Short Circuit Borne
1.3.2
CURRENT FLOW
To open: Drill the screw and
move the bar to the left side and
lock.
To close: Drill the screw and
move the bar to the left side
and lock.
*Notice that When the borne is closed, the current is allower to flow through
it, making it safe to procede with the Current Transformer Installation*.
Installation Manual 15
Phase 2: Preparation of the Installation
2.4 – Connection of the cables to the CT
*Read the Current Transformers Management
Considerations before accomplishing this step*
For each Current Transformer [3], follow the
instructions below:
Open the S1 and S2 inputs of the CTs for
cable entry.
1.4.1
Connect the Black Cable #4 [12] to the S1
input of the CT.
Connect the Black Cable #5 [12] to the S2
output of the CT.
Repeat the process for the remaining CTs
and Cables.
4
5
4
5
S1
S2
2.2
Installation Manual 16
V
I1
I2
Phase 2: Preparation of the Installation
1.4.2
Current Transformers Management Considerations
S1
S2
CURRENT R CURRENT S CURRENT T
S1
S2
S1
S2
S1
S2
I32.3.1
All of them must be installaed at the same side.
The S1 side must be turned from positive to negative of the current
flow. S2 side must be the exit side of the current flow.
Installation Manual 17
Phase 2: Preparation of the Installation
2.5 – Connection of Neu Plus Current Exits
Connect the Black Cables #4,6,8 [12] to
the Positive outputs of the Neu Plus.
Connect the Black Cables #5,7,9 [12] to
the Neu Plus Negative outputs.
Connect the Black Cables #0 [12] from the
terminal outputs to GDN Line.
1.5.1
Stick Neu Plus to the wall with Double
Sided Tape [14].
Fit the Short Circuit Terminals [4] on the
Rail [6].
At the end of Phase 2, your installation should
be in accordance with the figure on the next
page.
V I1 I2 I3
1 2 3 N + - + - + - B A - +
4
5
5
4
S2
2.3.2
Installation Manual 18
1.5.2
Phase 2: Preparation of the Installation
V I1 I2 I3
1 2 3 N + - + - + - B A - +
4
5
6
7
8
9
0 0 0
5
7
9
4
6
8
S2 S2 S2
2.4
Installation Manual 19
Phase 3: Installation
3.0 – Turn off the power!
Shut off the power of the main disjunctor.
Verify with you Multimeter [G] set as
tension mode if the power is really of.
2.0
3.1 – Connection of Tension
Cables
Connect the end of the White Cable #1,2,3
[11] into the Phases R, S y T of the main
Disjunctor.
2.1
OFF
ON
OFF
ON
1
2
3
R
OFF
ON
S
2.5
2.6
T
Installation Manual 20
Phase 3: Installation
3.2 – Connection of Neutral cable+
Connect the White Cable #0 [11] and connect to the Ground Line
1x [11]
1x [17]
2.2
V
I1
I2
1 2 3 N + - + -
1
2
3
0
GROUND
1
2
3
R
OFF
ON
S
T
Installation Manual 21
Phase 3: Installation
3.3 – Connect the CTs
For each Current Transformer [3], repeat the processes below:
*Pay attention to the CT fitting direction!*
Open the CT’s window.
Plug the CT with the phase R cable through
it and close the CT’s window.
I32.3.1
- B A -
R
S1
S2
R
Repeat the process for the phases S and T.
S1
S2
S1
S2
2.3.2
OFF
S1
S2
CURRENT R
CURRENT R
S2
S2
R
ON
S2
S
T
Installation Manual 22
Phase 3: Installation
3.4 – Connect the cables to the GND line
Connect the Black Cables #0 [12] from the Bornes to the GND lines.
2.4
GROUND
0 0 0
Installation Manual 23
Phase 3: Installation
3.5 – Outlet Connection
Connect one of the outputs of the Double
Wire of the Outlet mounted in step (2.1) to
one of the phases and the other toGND Line.
Use a Fork Terminal [17] for connections.
3.6 – Turn off the power!
2.6
Certify that all the steps were successfully
and attentiously executed.
Turn on the power.
With double-sided tape [14], glue the
socket to a location close to the Neu Plus.
2x [17]
2.5
OFF
ON
OFF
ON
GROUND
3.7 – Power Source – NEU Plus
2.7
Connect the Power Source [2] of Neu Plus
to the Outlet.
V I1 I2 I3
1 2 3 N + - + - + - B A - +
R
Installation Manual 24
3.8 – Open the Short Circuit Bornes
3.0
Don’t forget to open the Short Circuit Bornes you closed before the installation!
Phase 3: Installation
3.9 – Finalization and Organization
With Spiral for Cables [9] and Plastic Straps [10], organize and clean the installation.
Congratulations!
You finished the installation, now it’s up to us!
Installation Manual 25
Final Results
Final
V I1 I2 I3
1 2 3 N + - + - + - B A - +
1
2
3
0
4
5
6
7
8
9
0 0 0
0
1
2
3
4
S2
5
6
7
8
R
S2
9
OFF
ON
S
S2
T
Installation Manual 26
Final Results: Variation 1
Variation 1
V I1 I2 I3
1 2 3 N + - + - + - B A - +
1
2
0
4
6
8
0
3
0
0 0
1
2
3
4
S2
5
6
7
8
R
S2
9
OFF
ON
S
S2
T
Installation Manual 27
Final Results: Variation 2
Variation 2
V I1 I2 I3
1 2 3 N + - + - + - B A - +
1
2
0
4
6
8
0
3
0
0
1
2
3
4
S2
0
6
8
9
R
S2
0
OFF
ON
S
S2
T
Installation Manual 28
Final Results: Variation 3
Variation 3
V I1 I2 I3
1 2 3 N + - + - + - B A - +
1
2
0
4
6
8
0
3
0
0
0
1
2
4
6
8
3
S2
0
R
S2
0 0
OFF
ON
S
S2
T
Installation Manual 29
Your energy consumption
second by second
Installation Manual 30