27.03.2013 Views

Technical Application Papers No.10 Photovoltaic plants - ABB

Technical Application Papers No.10 Photovoltaic plants - ABB

Technical Application Papers No.10 Photovoltaic plants - ABB

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

6.1.2 Protection of the strings against reverse<br />

current<br />

Due to shading or fault a string becomes passive, absorbing<br />

and dissipating the electric power generated by the other<br />

strings connected in parallel to the same inverter through<br />

a current which flows through the string under consideration<br />

in a reverse direction with respect to that of standard<br />

operation, with possible damages to the modules.<br />

These are able to withstand a reverse current ranging<br />

from 2.5 and 3 I (IEC TS 62257-7-1). Since with x strings<br />

sc<br />

in parallel connected to the same inverter the highest<br />

reverse current is equal to I = (x-1) . 1.25 . I , it is not<br />

inv sc<br />

necessary to protect the strings if I ≤ 2.5 . I that is<br />

inv sc<br />

(x-1) . 1.25 ≤ 2.5 ⇒ x ≤ 33 .<br />

6.1.3 Behaviour of the inverter<br />

The contribution to the short-circuit on the DC side of the<br />

inverter may come from the grid and from the discharge<br />

of the capacitors inside the inverter.<br />

The grid current is due to the recirculating diodes of the<br />

bridge inverter which in this case act as a bridge rectifier.<br />

Such current is limited by the impedances of the<br />

transformer and of the inductors belonging to the output<br />

circuit and by the protection fuses of the inverter on the<br />

AC side chosen so that they can limit the thermal effects<br />

of possible internal faults on the semiconductors. As a<br />

consequence the I 2 t passing through will be normally<br />

reduced. Indicatively a final current value (internal capacitors<br />

completely discharged) of 10In can be an upper<br />

limit value. This current is present in case of inverter with<br />

galvanic insulation at 50Hz, while it is null in case of inverter<br />

without transformer. In fact these inverters usually<br />

have an input DC/DC converter so that the operation on<br />

a wide voltage range of the PV generator is guaranteed;<br />

this converter, due to its constructive typology, includes at<br />

least one blocking diode which prevents the contribution<br />

of the grid current to the short-circuit.<br />

The discharge current of the capacitors is limited by the<br />

cables between inverter and fault and exhausts itself with<br />

exponential trend: the lowest the impedance of the cable<br />

stretch, the highest the initial current, but the lowest the<br />

time constant of the discharge. The energy which flows<br />

is limited to that one initially stored in the capacitors.<br />

Moreover, if a blocking diode or other similar device is in<br />

3 The blocking diodes can be used, but they do not replace the protections against<br />

overcurrent (IEC TS 62257-7-1), since it is taken into consideration the possibility that<br />

the blocking diode does not work properly and is short-circuited. Moreover the diodes<br />

introduce a loss of power due to the voltage drop on the junction, a loss which can be<br />

reduced by using Schottky diodes with 0.4V drop instead of 0.7V of conventional diodes.<br />

However the rated reverse voltage of the diodes shall be ≥ 2 U oc and the rated current ≥<br />

1.25 I sc (CEI Guide 82-25).<br />

series with one of the two poles, this contribution to the<br />

short-circuit is null.<br />

In each case, the short-circuit on the DC side causes<br />

a drop of the direct voltage, the inverter certainly shuts<br />

down and probably is disconnected from the grid. Normally<br />

the shut down times of the inverter are of the order<br />

of some milliseconds, while the disconnection times may<br />

be of the order of some dozens of milliseconds. In the<br />

interval between the shut down and the disconnection,<br />

the grid might cause the above mentioned effect, while<br />

the internal capacitors, if involved, participate up to their<br />

complete discharge.<br />

However, the influences of both the grid and the internal<br />

capacitors on the short-circuit have only a transient nature<br />

and they are usually not such as to affect the sizing<br />

of the protection, switching and disconnection devices<br />

positioned on the DC side.<br />

6.1.4 Choice of the protective devices<br />

As regards the protection against the short-circuits on the<br />

DC side, the devices shall be obviously suitable for DC<br />

use and have a rated service voltage Ue equal or higher<br />

than the maximum voltage of the PV generator which is<br />

4 equal to 1.2 U (IEC TS 62257-7-1).<br />

oc<br />

Moreover the protection devices shall be positioned at<br />

the end of the circuit to be protected, proceeding from<br />

the strings towards the inverter, that is in the various<br />

subfield switchboards and inverter switchboards since<br />

the short-circuit currents come from the other strings,<br />

that is from the load side and not from the supply side<br />

(IEC TS 62257-7-1).<br />

In order to avoid unwanted tripping under standard operation<br />

conditions, the protective devices positioned in the<br />

subfield switchboards (device A in the Figure 6.1) shall<br />

5 have a rated current I : n<br />

I n ≥ 1.25 . I sc<br />

[6.1]<br />

These devices shall protect:<br />

• every single string against the reverse current;<br />

• the connection cable 6 string to subswitchboard (cable<br />

1 of Figure 6.1) if the latter has a current carrying capacity<br />

lower than the maximum short-circuit current of<br />

the other x-1 strings connected to the same inverter<br />

switchboard 7 , i.e. if:<br />

I z < I sc2 = (x - 1) . 1.25 . I sc<br />

4 Uoc is the no load voltage coming out of the strings (see Chapter 3).<br />

[6.2]<br />

5 For thermomagnetic circuit-breakers the [6.1] becomes I1 ≥ 1.25 . I sc , while for magnetic<br />

only circuit-breakers I u ≥ 1.25 . I sc so that their overheating can be avoided.<br />

6 Protection against short-circuit only because Iz ≥ 1.25 . I sc .<br />

7 The short-circuit Isc1 = 1.25 . I sc (fig. 6.1) (Figure 6.1) is unimportant because the string<br />

cable has a current carrying capacity not lower than 1.25 . I sc .<br />

<strong>Photovoltaic</strong> <strong>plants</strong><br />

43<br />

6 Protection against overcurrents and overvoltages

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!