12.04.2013 Views

Alternative Approach to Improving SAIDI and SAIFI - Schneider Electric

Alternative Approach to Improving SAIDI and SAIFI - Schneider Electric

Alternative Approach to Improving SAIDI and SAIFI - Schneider Electric

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

An <strong>Alternative</strong> <strong>Approach</strong><br />

<strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong><br />

<strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

Philippe Deschamps - <strong>Schneider</strong> <strong>Electric</strong> Industries - France<br />

Jean-Chris<strong>to</strong>phe Orsini - <strong>Schneider</strong> <strong>Electric</strong> Industries - France<br />

Kaare Seest Rasmussen - DONG Energy - Denmark


Summary<br />

Abstract ......................................................................................................p 1<br />

Introduction .................................................................................................p 2<br />

DONG Energy's network .............................................................................p 3<br />

The concept of a SACSe substation ............................................................p 4<br />

SACSe control unit architecture ...................................................................p 7<br />

F200C: Possible further enhancement .........................................................p 8<br />

Conclusion ..................................................................................................p 9<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 June 2009


Abstract<br />

Under the pressure of regulating authorities, utilities are being challenged <strong>to</strong><br />

improve their <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> indica<strong>to</strong>rs. Usually, <strong>to</strong> reach this goal, more<br />

intelligence is put inside DMS, increasing at the same time the amount<br />

of data <strong>to</strong> be processed <strong>and</strong> the importance of communication in the<br />

network. An alternative way, discussed in this paper, consists of using local<br />

au<strong>to</strong>mation, allowing faster reactions, <strong>and</strong> therefore a drastic reduction of the<br />

number of cus<strong>to</strong>mers affected by permanent faults, without requiring heavy<br />

communication infrastructure. In addition, this paper introduces a further<br />

enhancement allowing a faster power res<strong>to</strong>ration for the remaining affected<br />

cus<strong>to</strong>mers.<br />

An <strong>Alternative</strong> <strong>Approach</strong> <strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 8-11 June 2009<br />

Paper 0635 | 1


Introduction<br />

Challenged by the Danish authorities, DONG Energy has for a long time<br />

experimented with several methods <strong>to</strong> optimize network management <strong>and</strong><br />

particularly increase power availability. An important step was reached when<br />

it was decided <strong>to</strong> reduce the maximum time <strong>to</strong> reenergize a faulty location <strong>to</strong><br />

less than a minute <strong>to</strong> avoid the outage <strong>to</strong> be counted as a long one, that is<br />

degrading the <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> indexes.<br />

An <strong>Alternative</strong> <strong>Approach</strong> <strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 8-11 June 2009<br />

Paper 0635 | 2


DONG Energy's network<br />

DONG Energy is a major DNO in Denmark, however this experience involves only one part of its<br />

network.<br />

FLA10-622<br />

FLA04<br />

3383<br />

4033<br />

FLA10-6202<br />

FLA10-3722<br />

FLA10-7007<br />

FLA10-3369<br />

2017<br />

FLA09-3024<br />

FLA09-5562<br />

4956<br />

2928<br />

2365<br />

5199<br />

Fig.1 - Typical feeder (neighbouring feeders in white)<br />

823<br />

3304<br />

3320<br />

2367<br />

The 10 kV grid in DONG Energy North, is a 100<br />

per cent underground radial network, with a high<br />

degree of access <strong>to</strong> neighbouring feeders for<br />

backup, as shown in Fig. 1.<br />

FLA03-4554<br />

FLA03-4553<br />

2366<br />

3568<br />

2726<br />

104<br />

FLA03-3972<br />

FLA03-3971<br />

FLA03-3970<br />

The grid is mainly urban <strong>and</strong> consists of<br />

approximately 7000 substations on 600 feeders.<br />

An <strong>Alternative</strong> <strong>Approach</strong> <strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 8-11 June 2009<br />

Paper 0635 | 3<br />

4916<br />

4915<br />

FLA03-4524<br />

FLA03-4914<br />

FLA15-998


The concept of a SACSe substation<br />

First of all, let’s clarify the management of<br />

phase-<strong>to</strong>-phase <strong>and</strong> phase-<strong>to</strong>-earth faults in the<br />

DONG Energy network:<br />

• phase-<strong>to</strong>-phase faults: these cause the<br />

tripping of a breaker <strong>and</strong> therefore an outage<br />

which explains how SACSe limits the number of<br />

cus<strong>to</strong>mers affected<br />

• phase-<strong>to</strong>-earth faults: the network is<br />

Petersen-coil grounded, allowing temporary<br />

operation with single earth fault. However, SACSe<br />

provides an earth-fault localization information<br />

because a second earth fault would cause a<br />

tripping.<br />

SACSe means "Sectionalizing And Changeover<br />

System enhanced". The concept of SACSe<br />

described below is the latest evolution of the<br />

network, which has already seen significant<br />

improvement over the last 10 years.<br />

A first step was taken by deploying circuit breakers<br />

in the network [1].<br />

SACSe - Main principle<br />

First of all, in a given feeder, one or two substations<br />

are selected <strong>to</strong> support the au<strong>to</strong>mation. They are<br />

chosen because of their location: they divide the<br />

feeder in<strong>to</strong> two or three segments, each supplying<br />

roughly the same number of cus<strong>to</strong>mers. They are<br />

also chosen because of the ease of upgrading<br />

them. The principle of layout in the network of<br />

these substations is described in the ref [2].<br />

Second, a backup line coming from the neighbour<br />

feeder is connected <strong>to</strong> these strategic MV/LV<br />

substations <strong>to</strong> allow a backup supply if required<br />

(Fig. 2).<br />

Incoming/outgoing/backup<br />

MV/LV<br />

transformer<br />

Fig. 3 - Typical make-up of a switchgear in a SACSe MV/LV<br />

substation<br />

The goal is <strong>to</strong> put in one strategic MV/LV<br />

substation, a line circuit breaker intended <strong>to</strong> split<br />

the feeder in<strong>to</strong> 2 segments in order <strong>to</strong> minimize<br />

the number of cus<strong>to</strong>mers affected by a fault, if it<br />

happens on the downstream side. Time selectivity<br />

is used <strong>to</strong> prevent primary substation CB from<br />

tripping simultaneously. In some cases, there<br />

could be up <strong>to</strong> two line CBs on the feeder: in such<br />

a case they would use the same setting <strong>and</strong> trip<br />

simultaneously.<br />

The second concept is a step further. In case<br />

of a phase-<strong>to</strong>-phase fault upstream in the same<br />

substation, it allows the faulty segment <strong>to</strong> be<br />

au<strong>to</strong>matically isolated <strong>and</strong> the healthy ones <strong>to</strong> be<br />

au<strong>to</strong>matically resupplied. This process is based on<br />

local au<strong>to</strong>mation, allowing a fast reaction, <strong>and</strong> not<br />

needing any human intervention or communication<br />

infrastructure. The solution was developed in<br />

collaboration with <strong>Schneider</strong> <strong>Electric</strong>, which offers<br />

a wide range of products for network au<strong>to</strong>mation.<br />

HV/MV sub<br />

Feeder 1<br />

Feeder 2<br />

Feeder n<br />

Fig. 2 - Principle of a SACSe substation layout in DONG<br />

Energy’s network<br />

These substations are equipped with a fourfunction<br />

switchgear (Fig. 3):<br />

• 1 fuse switch or circuit breaker for the<br />

transformer protection. It can be forgotten since it<br />

has no role in the concept.<br />

• 2 circuit breakers <strong>and</strong> 1 switch distributed<br />

among the incoming, the outgoing, <strong>and</strong> the<br />

backup lines. There are two circuit breakers among<br />

the three <strong>to</strong> be sure that there will be at least one in<br />

the circuit in all network configuration cases.<br />

An <strong>Alternative</strong> <strong>Approach</strong> <strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

Backup line<br />

MV/LV sub<br />

SACSe MV/LV sub<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 8-11 June 2009<br />

Paper 0635 | 4


If a fault occurs downstream, the breaker opens<br />

instantaneously, isolating the downstream<br />

segment(s). The status of the switchgear is then<br />

sent <strong>to</strong> the SCADA. If a fault occurs upstream, the<br />

switchgear acts as an au<strong>to</strong> changeover (ACO):<br />

the circuit breaker will not trip, but the lack of<br />

voltage releases the au<strong>to</strong> changeover process,<br />

ordering the incoming <strong>to</strong> open <strong>and</strong> the backup<br />

<strong>to</strong> close, which supplies the healthy downstream<br />

segment. This is the general principle. Two cases<br />

are shown in Fig. 4. Since the breaker in the HV/<br />

MV substation is delayed <strong>and</strong> those in the SACSe<br />

are not, the breaker in the HV/MV sub will only trip<br />

when the fault is in the first segment<br />

(Fig. 4 - case 1).<br />

In a particular case (2 SACSe on the same feeder),<br />

a fault downstream in the second SACSe results<br />

in both SACSe circuit breakers tripping. In order<br />

<strong>to</strong> resupply the segment between the two SACSe<br />

circuit breakers, the downstream one will act as a<br />

Reverse Au<strong>to</strong> Changeover (RACO): based on the<br />

CB tripping information, it will keep the incoming<br />

closed, <strong>and</strong> order the backup <strong>to</strong> close, therefore<br />

resupplying the upstream segment<br />

(Fig. 5).<br />

Fig. 5 - ACO - principle of fault res<strong>to</strong>ration<br />

Trip<br />

Trip<br />

+<br />

reserve<br />

backup<br />

Fig. 4 - ACO - principle of fault res<strong>to</strong>ration<br />

In all cases, the time required <strong>to</strong> reconfigure is less<br />

than 20 seconds, saving au<strong>to</strong>matically up <strong>to</strong> 2/3 of<br />

the cus<strong>to</strong>mers normally affected by such a fault.<br />

In addition, several logic processes are embedded<br />

in the au<strong>to</strong>mation in order <strong>to</strong> avoid any improper<br />

action in certain cases:<br />

• once the ACO/RACO has operated, it is blocked<br />

until there is some human interaction from the<br />

control center <strong>to</strong> prevent further action in a nonst<strong>and</strong>ard<br />

network configuration<br />

• a logic process is in action <strong>to</strong> avoid any ACO<br />

<strong>and</strong>/or RACO action if the network is subject <strong>to</strong><br />

a global outage, from the transport for instance.<br />

This event is detected by moni<strong>to</strong>ring the voltage<br />

presence on the backup line. If an absence of<br />

voltage is observed on both incoming <strong>and</strong> backup<br />

lines, then no action is taken<br />

• in case of a frequency drop, a recovery process<br />

exists in the HV/MV substation <strong>and</strong> it, it reacts by<br />

switching off some feeders. So in this case, the<br />

ACO/RACO is inhibited <strong>to</strong> allow the load-shedding<br />

process <strong>to</strong> be prioritized.<br />

An <strong>Alternative</strong> <strong>Approach</strong> <strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

Case 1 Case 2<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 8-11 June 2009<br />

Paper 0635 | 5<br />

Trip<br />

Open<br />

+<br />

backup<br />

Trip<br />

Open<br />

+<br />

backup


Infrastructure<br />

Basically, the system does not require any means<br />

of communication <strong>to</strong> react properly <strong>and</strong> fulfil its<br />

purpose. In fact this is even an advantage in terms<br />

of security <strong>and</strong> reliability. But of course, it is linked<br />

with the SCADA <strong>to</strong> report the outage on the faulty<br />

segment, in order <strong>to</strong> res<strong>to</strong>re the power. In addition,<br />

it reports its status <strong>to</strong> the operating staff, as Danish<br />

regulations require the opera<strong>to</strong>r<br />

Earth fault<br />

As explained above, SACSe also integrates<br />

directional fault passage indica<strong>to</strong>rs (FPIs). These<br />

FPIs allow the staff <strong>to</strong> locate the fault in the field<br />

more accurately <strong>and</strong> faster, <strong>and</strong> therefore prevent a<br />

tripping due <strong>to</strong> a second fault.<br />

<strong>to</strong> know the real status of all switches <strong>and</strong><br />

breakers in the network all times. By these<br />

means, other information available in the MV/LV<br />

substation can also be transmitted. In this case,<br />

<strong>and</strong> thanks <strong>to</strong> good coverage of the area by GSM<br />

infrastructure, GPRS has been chosen <strong>to</strong> transfer<br />

data in a very economical way.<br />

All these features are embedded in a single box<br />

provided by <strong>Schneider</strong> <strong>Electric</strong>, which is described<br />

below.<br />

An <strong>Alternative</strong> <strong>Approach</strong> <strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 8-11 June 2009<br />

Paper 0635 | 6


SACSe control unit architecture<br />

Functional description<br />

The unit integrates the following functions (Fig. 6):<br />

• phase-<strong>to</strong>-phase fault protection ensured by two<br />

protection relays, for the incoming/outgoing <strong>and</strong><br />

backup breakers<br />

• phase-<strong>to</strong>-earth fault detection ensured by two<br />

directional fault passage indica<strong>to</strong>rs on the same<br />

functions<br />

• voltage presence on incoming, outgoing, <strong>and</strong><br />

backup cables<br />

• au<strong>to</strong>mation ensuring the ACO/RACO logic<br />

• communication with the SCADA on the status of<br />

the substation<br />

• power supply with batteries <strong>to</strong> supply the unit<br />

under all conditions.<br />

In addition, LV <strong>and</strong> MV measurement features have<br />

been included in the unit <strong>to</strong> provide a much better<br />

knowledge of the substation <strong>and</strong> the network load.<br />

Design<br />

SACSe is designed as an industrial solution<br />

integrating existing or slightly modified products<br />

from the <strong>Schneider</strong> <strong>Electric</strong> Easergy offer:<br />

• relays from the SEPAM range<br />

• FPI for earth protection is based on the Flair<br />

range<br />

• au<strong>to</strong>mation is based on the Easergy T200 which<br />

includes peripheral functions such as backup/main<br />

power supply <strong>and</strong> modem.<br />

All these products were designed specifically<br />

for the network au<strong>to</strong>mation environment. As a<br />

consequence, they comply with the specificities<br />

of this application: harsh environment withst<strong>and</strong><br />

(temperature, EMC, electrical insulation -10 kV on<br />

mains, dust, humidity, etc.), allowing the high level<br />

Fig. 7 - SACSe<br />

control unit<br />

Phase<br />

I protection<br />

I<br />

Eart<br />

detection<br />

U<br />

Fig. 6 - General architecture of the SACSe system<br />

of robustness required by such an application,<br />

openness in terms of communication pro<strong>to</strong>cols,<br />

<strong>and</strong> a ready-<strong>to</strong>-use product <strong>to</strong> minimize the<br />

settings on-site during the installation. All these<br />

products are integrated in a single box (Fig. 7)<br />

in a way <strong>to</strong> make it easy <strong>to</strong> integrate in<strong>to</strong> DONG<br />

Energy's existing installed base. No assembling is<br />

needed on-site, just the mounting of one box, <strong>and</strong><br />

the connection of the sensors <strong>and</strong> the comm<strong>and</strong>s<br />

in the switchgear.<br />

In terms of size, the system is made <strong>to</strong> be<br />

mounted directly on the wall of the substation. The<br />

dimensions allow it <strong>to</strong> be used even in a compact<br />

substation with reduced volume available.<br />

Interfaces are designed <strong>to</strong> make installation<br />

simple <strong>and</strong> minimize the risk of mistakes by using<br />

prefabricated cables <strong>and</strong> connec<strong>to</strong>rs <strong>to</strong> link the<br />

unit with sensors.<br />

The box is equipped with a transparent window<br />

on the front door, allowing all indica<strong>to</strong>rs of the<br />

status of the system <strong>to</strong> be read locally. If needed,<br />

operating staff have access <strong>to</strong> the local operation<br />

by opening the front door.<br />

An <strong>Alternative</strong> <strong>Approach</strong> <strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 8-11 June 2009<br />

Paper 0635 | 7<br />

U I<br />

ACO<br />

RACO<br />

logic<br />

Com<br />

Power<br />

supply


Thanks <strong>to</strong> the unit presented above, the <strong>SAIDI</strong><br />

index is drastically reduced, but ultimate quality<br />

requires some additional instrumentation of the<br />

network:<br />

• In case of a phase fault, only half (if 1 SACSe) or<br />

one third (of 2 SACSe) of the feeder cus<strong>to</strong>mers are<br />

affected by an outage more than one minute.<br />

However, the half or third of cus<strong>to</strong>mers in the faulty<br />

segment still need <strong>to</strong> get power back as soon as<br />

possible.<br />

• In case of an earth fault, the SACSe control<br />

unit can indicate whether the fault is upstream or<br />

downstream the SACSe substation. But a more<br />

accurate localization is required in order <strong>to</strong> allow<br />

faulty cable isolation without power interruption<br />

for any cus<strong>to</strong>mer.<br />

Of course, for obvious cost <strong>and</strong> complexity<br />

reasons, more than two SACSe substations on<br />

a feeder are not possible. Increasing the number<br />

of SACSe substations is therefore not a way <strong>to</strong><br />

achieve ultimate quality.<br />

This means a device allowing accurate localization<br />

of both phase faults <strong>and</strong> earth faults is needed<br />

in the other substations, both upstream <strong>and</strong><br />

downstream from the SACSe.<br />

Accurate localization would ideally mean knowing<br />

which cable between the two substations is faulty.<br />

<strong>Schneider</strong> <strong>Electric</strong> has recently launched a new<br />

communicating fault passage indica<strong>to</strong>r, the<br />

Flair 200C, combining in a single cost-effective<br />

product the phase-<strong>to</strong>-phase <strong>and</strong> phase-<strong>to</strong>-earth<br />

fault detection <strong>and</strong> the GPRS communication<br />

functions. This would suit the above purpose<br />

particularly well. It should be noted that this new<br />

Flair 200C embeds a new algorithm for detection<br />

of phase-<strong>to</strong>-earth faults on compensated networks<br />

not requiring voltage sensing. This allows the<br />

commissioning of such devices <strong>to</strong> be drastically<br />

simplified, especially for retrofit in existing<br />

substations, <strong>and</strong> it reduces the global cost.<br />

Additionally, the Flair 200C can optionally provide<br />

measurements, further increasing the knowledge<br />

of network load.<br />

An <strong>Alternative</strong> <strong>Approach</strong> <strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

F200C: Possible further enhancement<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 8-11 June 2009<br />

Paper 0635 | 8


Conclusion<br />

Increasing pressure on <strong>SAIDI</strong>/<strong>SAIFI</strong> improvement<br />

usually requires more performance from DMS,<br />

<strong>and</strong> at the same time the management of<br />

more <strong>and</strong> more information. A complementary<br />

solution involves the use of local au<strong>to</strong>mation<br />

able <strong>to</strong> perform simple actions quickly. By this<br />

means, when a fault occurs, a rough but fast<br />

reconfiguration is done while the operation is<br />

simplified.<br />

References<br />

The implementation of this requires a dedicated<br />

device <strong>to</strong> prevent complex commissioning from<br />

spoiling the solution, <strong>and</strong> therefore the Return On<br />

Investment.<br />

[1] Peter Vinter, Henrik Vikelgaard, 2005, "A novel approach <strong>to</strong> distribution grid au<strong>to</strong>mation at NESA A/S",<br />

CIRED Conference 18th international conference on electricity distribution.<br />

Session 3.<br />

[2] Kåre Seest Rasmussen, 2009, "A real case of self healing distribution network", CIRED Conference 20 th international<br />

conference on electricity distribution.<br />

Session 3.<br />

An <strong>Alternative</strong> <strong>Approach</strong> <strong>to</strong> <strong>Improving</strong> <strong>SAIDI</strong> <strong>and</strong> <strong>SAIFI</strong> Indica<strong>to</strong>rs<br />

C I R E D - 20th International Conference on <strong>Electric</strong>ity Distribution<br />

Prague, 8-11 8-11 June 2009<br />

Paper 0635 | 9


Reserved.<br />

Rights All<br />

<strong>Schneider</strong> <strong>Electric</strong> Industries SAS<br />

35, rue Joseph Monier<br />

<strong>Electric</strong>.<br />

CS 30323<br />

F- 92506 Rueil Malmaison Cedex<br />

<strong>Schneider</strong><br />

RCS Nanterre 954 503 439<br />

This document has been<br />

Capital social 896 313 776<br />

printed on ecological paper 2011<br />

www.schneider-electric.com ©<br />

998-5592<br />

09-2011

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!