1 Application and short <strong>de</strong>scription <strong>Motor</strong> <strong>Protection</strong> <strong>MS</strong> <strong>220</strong> <strong>DA</strong><br />

1.4 Block Diagram<br />

1.5 Detailed Description<br />

A current monitors continuously the resistance of the sensors. In cold state, the resistance is < 250 Ω per sensor (sensor circuit < 1.5 kΩ). The output<br />

to X44/12 is high = 1. The resistance of the sensor rises rapidly at nominal response temperature TNF. At a resistance of 3…4 kΩ output to X44/12<br />

changes to low = 0. The <strong>de</strong>vices also switches off in the case of sensor or line short-circuit 1) (< 20 Ω) or sensor or line interruption. It switches on<br />

automatically when the temperature has <strong>de</strong>creased approx. 5 °C.<br />

Attention ! 2) : trip status is not stored and not non-volatile.<br />

Depending on the number of sensors the following tripping and release<br />

temperatures will be achieved with respect of TNF (nominal response<br />

temperature of the sensors):<br />

Trip temperature Release temperature<br />

3 sensors in series TNF + 5 K TNF – 5 K<br />

6 sensors in series TNF TNF – 20 K<br />

4 MG33V102 - VLT ® is a regisered Danfoss tra<strong>de</strong>mark