Return T limit (return temp. limitation) 4000<br />

The <strong>control</strong>ler automatically changes the desired flow <strong>temperature</strong> to obtain an<br />

acceptable return <strong>temperature</strong> when the return <strong>temperature</strong> falls below or gets higher<br />

than the set limit.<br />

Influence<br />

‘Gain - min.’ > 0<br />

‘Limit’<br />

‘Gain max.’ > 0<br />

Return <strong>temperature</strong><br />

‘Gain - max.’ < 0<br />

‘Gain - min.’ < 0<br />

This limitation is based on a PI regulation where P (Gain) responds quickly to deviations<br />

and I (Intgr. time) responds slower and over time removes the small <strong>of</strong>fsets between the<br />

reference and actual measured values. This is done by changing the flow <strong>temperature</strong><br />

reference.<br />

If the ‘Gain’ is too high and / or the ‘Intgr. time’ too low, there is a risk <strong>of</strong> unstable <strong>control</strong>.<br />

Limit (return temp. limitation) 4030<br />

Setting range Factory setting<br />

10 ... <strong>110</strong> °C 50 °C<br />

Set the return <strong>temperature</strong> you accept for the system.<br />

Set the acceptable return <strong>temperature</strong> limit.<br />

When the return <strong>temperature</strong> falls below or gets higher than the set value, the <strong>control</strong>ler<br />

automatically changes the desired flow <strong>temperature</strong> to obtain an acceptable return<br />

<strong>temperature</strong>. The influence is set in lines 4035 and 4036.<br />

12 VI.KT.F1.02 © Danfoss 05/2007 DH-SMT/DK<br />

Gain - max. (return temp. limitation - max. influence) 4035<br />

Setting range Factory setting<br />

-9.9 ... 9.9 0.0<br />

Determines how much the flow(DHW) <strong>temperature</strong> will be influenced if the return <strong>temperature</strong> is<br />

higher than the desired ‘Limit’ (line 4030) (P <strong>control</strong>).<br />

Influence higher than 0:<br />

The desired flow <strong>temperature</strong> is increased, when the return <strong>temperature</strong> gets higher<br />

than the set limit.<br />

Influence lower than 0:<br />

The desired flow <strong>temperature</strong> is decreased, when the return <strong>temperature</strong> gets higher<br />

than the set limit.<br />

Example<br />

The return limit is active above 50 °C.<br />

The influence is set to -2.0.<br />

The actual return <strong>temperature</strong> is 2 degrees too high.<br />

Result:<br />

The desired flow <strong>temperature</strong> is changed by -2.0 x 2 = -4.0 degrees.<br />

Normally, the setting in line 4035 is lower than 0 in district heating systems to avoid a too<br />

high return <strong>temperature</strong>.<br />

Typically, the setting in line 4035 is 0 in boiler systems because a higher return <strong>temperature</strong><br />

is acceptable (see also line 4036).<br />

DH-SMT/DK VI.KT.F1.02 © Danfoss 05/2007 13