Electrical Shock Hazard<br />

D<strong>is</strong>connect power before servicing.<br />

Replace all parts and panels before operating.<br />

Failure to do so can result in death or electrical shock.<br />

OVERLOAD PROTECTOR<br />

Refer to page 4-14 for the procedure for servicing<br />

the overload protector.<br />

1. Unplug <strong>air</strong> conditioner or d<strong>is</strong>connect power.<br />

2. D<strong>is</strong>connect the overload protector wires.<br />

3. Set the ohmmeter to the R x 1 scale.<br />

4. Touch the ohmmeter test leads to the<br />

overload protector <strong>terminal</strong> and connector.<br />

5. The meter should indicate continuity (0 Ω).<br />

5-7<br />

COMPRESSOR<br />

Compressor<br />

Terminals<br />

Blue<br />

R<br />

(U)<br />

C<br />

(W)<br />

Black<br />

S<br />

(V)<br />

Red<br />

Refer to page 4-14 for the procedure for servicing<br />

the compressor.<br />

1. Unplug <strong>air</strong> conditioner or d<strong>is</strong>connect power.<br />

2. D<strong>is</strong>connect the three wires from the compressor<br />

<strong>terminal</strong>s.<br />

3. Set the ohmmeter to the R x 1 scale.<br />

4. Clip an ohmmeter test lead to the overload<br />

protector <strong>terminal</strong> C (W).<br />

5. Touch the free test lead to the following<br />

compressor <strong>terminal</strong>s. The meter should<br />

indicate as shown:<br />

Terminal R (U) = 0.5 Ω<br />

Terminal S (V) = 3.16 Ω<br />

Terminal S (V) to R (U) = 3.65 Ω