Description<br />

3.3 Measured variables<br />

Connection types<br />

See also<br />

Five connection types have been provided for connecting two-wire, three-wire or four-wire<br />

systems with balanced or unbalanced load.<br />

Table 3- 2 Available connection types<br />

Short code Connection type<br />

3P4W 3 phases, 4 conductors, unbalanced load<br />

3P3W 3 phases, 3 conductors, unbalanced load<br />

3P4WB 3 phases, 4 conductors, balanced load<br />

3P3WB 3 phases, 3 conductors, balanced load<br />

1P2W Single-phase AC<br />

The input circuit of the device must correspond to one of the connection types listed. Select<br />

the suitable connection type for the purpose.<br />

You can find connection examples in the chapter "Connecting".<br />

CAUTION<br />

Local power supply conditions<br />

Before connecting <strong>SENTRON</strong> <strong>PAC4200</strong>, you must ensure that the local power supply<br />

conditions agree with the specifications on the type plate.<br />

The short code of the connection type must be entered in the device settings at startup. You<br />

can find the instructions for parameterizing the connection type in the chapter "Starting up".<br />

Connecting (Page 67)<br />

Set the connection type (Page 90)<br />

Apply the measuring voltage (Page 95)<br />

Apply the measuring current (Page 95)<br />

3.3 Measured variables<br />

Measured variables - overview<br />

The table below lists all measured variables that the device records or derives from basic<br />

variables. You can find more information on measured variables in the Appendix.<br />

Inst Instantaneous value<br />

Min Minimum value<br />

Max Maximum value<br />

DMD Demand value<br />

Σ Total<br />

<strong>SENTRON</strong> <strong>PAC4200</strong><br />

22 <strong>Manual</strong>, 09/2008, A5E02316180B-01