Description<br />

3.4 Load profile<br />

Calculation of the power demand and the cumulated power<br />

See also<br />

Arithmetic power demand:<br />

Arithmetic calculation of the power demand referred to the actual length of the demand<br />

period. The arithmetic power demand in the instantaneous period remains constant providing<br />

the power is constant.<br />

Cumulated power:<br />

Cumulative calculation of the power referred to the configured length of the subperiod. The<br />

cumulated power in the instantaneous period increases linearly providing the power is<br />

constant.<br />

The energy can be calculated from the cumulated power as follows:<br />

Energy = (cumulated power) • (configured period length)<br />

<strong>Power</strong> demand (Page 125)<br />

3.4.2 Historical load profile<br />

Measured variables recorded<br />

<strong>SENTRON</strong> <strong>PAC4200</strong> records the following measured variables:<br />

Table 3- 4 Historical load profile<br />

Measured variable Cumulated<br />

power<br />

<strong>Power</strong><br />

demand<br />

Minimum<br />

instantaneous<br />

value<br />

Maximum<br />

instantaneous<br />

value<br />

Active power import X X<br />

±X ±X<br />

Active power export X X<br />

Reactive power import X X<br />

±X ±X<br />

Reactive power export X X<br />

Apparent power X X X X<br />

The values are recorded per demand period or subperiod:<br />

● Fixed block method<br />

All values are recorded per demand period.<br />

● Rolling block method<br />

Arithmetic power demand values are recorded per demand period.<br />

Cumulated power demand values and maximum / minimum values are recorded per<br />

subperiod.<br />

<strong>SENTRON</strong> <strong>PAC4200</strong><br />

32 <strong>Manual</strong>, 09/2008, A5E02316180B-01