Description<br />

3.5 Tariffs<br />

3.5 Tariffs<br />

Impact of the tariff change<br />

Control of the tariff change<br />

<strong>SENTRON</strong> <strong>PAC4200</strong> supports two tariffs for the integrated energy counters (on-peak and<br />

off-peak).<br />

The tariff change affects all energy counters for active energy, reactive energy, and apparent<br />

energy.<br />

A tariff change between off-peak and on-peak can be requested by means of a digital input<br />

or via the communication interfaces.<br />

Time-related switching is only possible using a higher-level system.<br />

Activation of a tariff change at the end of a period<br />

The old tariff remains valid until the end of the instantaneous period. The new tariff takes<br />

effect at the start of the next period. The energy counters of <strong>SENTRON</strong> <strong>PAC4200</strong> are<br />

switched to the other tariff at the end of the instantaneous demand period.<br />

Without synchronization, the tariff change takes effect immediately.<br />

3.6 Technical features of the supply quality<br />

The following measured variables are supplied by <strong>SENTRON</strong> <strong>PAC4200</strong> for evaluating<br />

supply quality:<br />

● Harmonics up to the 31st harmonic<br />

● THD for voltage and current:<br />

● Displacement angle φ<br />

● Cosine of the displacement angle φ<br />

● Phase angle<br />

● Unbalance voltage and unbalance current<br />

Harmonics up to the 31st harmonic referred to the fundamental<br />

<strong>SENTRON</strong> <strong>PAC4200</strong> measures the 3rd to 31st odd harmonics referred to the fundamental<br />

for:<br />

● Voltage ph-ph<br />

● Voltage ph-n<br />

● Current<br />

<strong>SENTRON</strong> <strong>PAC4200</strong> measures the instantaneous and maximum values.<br />

The values are represented on the display and can be called via the communication<br />

interfaces.<br />

<strong>SENTRON</strong> <strong>PAC4200</strong><br />

36 <strong>Manual</strong>, 09/2008, A5E02316180B-01