<strong>System</strong> Description<br />

1.5.6 Additional Signal Processing with Freely-Programmable Logic Modules<br />

If you need any other additional functions for your application, you can use<br />

the freely-<strong>pro</strong>grammable logic modules. These can be used, for example, to<br />

implement logical functions, time relay functions and counter functions.<br />

Furthermore, limit monitors can monitor any value in <strong>SIMOCODE</strong> <strong>pro</strong> for<br />

undershooting or overshooting of a freely selected limit.<br />

Depending on the device series, the system offers several, freelyparameterizable<br />

logic modules:<br />

Logic module <strong>pro</strong> C (BU1)<br />

1) Only for basic unit 2 from <strong>pro</strong>duct version *E<strong>03</strong>*<br />

Detailed description: See Chapter 11 "Logic Modules".<br />

Number<br />

<strong>SIMOCODE</strong><br />

<strong>pro</strong> V (BU2)<br />

Number<br />

Truth tables 3 inputs / 1 output 3 6<br />

Truth tables 2 inputs / 1 output — 2<br />

Truth tables 5 inputs / 2 outputs — 1<br />

Timer 2 4<br />

Counter 2 4<br />

Signal conditionings 2 4<br />

Non-volatile elements 2 4<br />

Flashing 3 3<br />

Flickering 3 3<br />

Limit monitor — 4<br />

Calculation module (calculator) 1)<br />

Table 1-5: Freely-<strong>pro</strong>grammable logic modules<br />

— 2<br />

<strong>SIMOCODE</strong> <strong>pro</strong><br />

GWA 4NEB 631 6050-22 DS 02 1-15