Case Studies & Awards<br />
Siemens S7-300 range of PLCs fitted with appropriate input <strong>and</strong> output cards control a total of 71 motor<br />
control panels. The supervisory software is a Siemens WINCC SCADA Package. This is used to monitor<br />
these panels <strong>and</strong> on local panel mounted Human Machine Interfaces (HMIs) <strong>and</strong> the Supervisory PC. The<br />
BMS system also interfaces with the fire system via a dedicated Siemens PLC through a Modbus interface.<br />
Each panel is fed from the essential electrical supply that is backed up by the hospital generators. Within<br />
each panel is an Uninterruptible Power Supply (UPS) that provides continuous data logging <strong>and</strong> system<br />
monitoring during a power failure <strong>and</strong> while the panel awaits power to be restored via the generators.<br />
Each main panel has a local panel-mounted UPS-backed Human Machine Interface (HMI). Their purpose<br />
is to monitor measured values, start/stop of equipment, monitor <strong>and</strong> adjust set points <strong>and</strong> time settings.<br />
All motors in the cubicles are controlled by Siemens Simocode 3UF50<br />
DP Intelligent Overload devices. These devices are configurable <strong>and</strong><br />
reside on the respective panel Profibus DP network. They have four<br />
digital inputs <strong>and</strong> four digital outputs that can provide monitoring data<br />
on the status of the motor that it controls. All variable speed drives<br />
are Seimens Micromaster 440 type <strong>and</strong> are mounted externally from<br />
the panels with a fitted Profibus DP interface card. These cards<br />
are supplied with a separate UPS backed 24V DC supply from the<br />
control cubicle where they receive their motor power. This ensures<br />
that the drive can be monitored at all times including power failure.