factor prescribed by the man(Jfactnrer for u.re in<br />

conJunclion wilh a pnrlicHlar Inslrumenle In addilion<br />

il is often necessn thai Ihe rending !<br />

grilles, regislers nnd dillusers bn Inkon in a<br />

posilion or number of positions prescribed by<br />

Ihe manulaclurer of lhe air lerminal device.<br />

9) Repeal Ihe branch bnlmcing unlil Iho system is<br />

in balance.<br />

10) Verify Ihe fan cnpacily nnd operating con(lilion<br />

again and make a final adjuslmenl in the fan<br />

ddve If necessaw.<br />

11) Veri Ihe action of all fnn shul down conlrols<br />

and aldlow safely conlrols.<br />

12) Prepare all TAB reporl forms and sbmil as<br />

required, using Ihe NEBB TAB Repeat Forms<br />

SYSTEMS WitH<br />

ECONOMIZERS<br />

Follow Ihe procedures oullined for exhausl and relurn<br />

air syslems, excepl Ihal allot balancing Ihe relure<br />

air syslem and tile associaled supply air syslem<br />

Ihe relurn air damper should be closed; Ihe inletlocked<br />

relief air damper should be opened and the<br />

relurn air fan, slalic pressure and clm should be<br />

checked again. If il is necessary to increase tile system<br />

static pressure and Ihereby reduce tile fan cfm,<br />

adjust lhe exhausl air damper 1o a maximum position<br />

less Ihan 100% open. Recheck lhe supply fan airflow<br />

with Ihe oulside air damper In Ihe full open position.<br />

OPTIONAL PROCEDURE<br />

RATIO METHOD<br />

This Is one of the olher melhods Ihal has been developed<br />

for Ihe final balancing process.<br />

1) Do all of tile TAB work un(ler Sul)-oecliofl A of<br />

tills section entitled "Basic Air System Procedures."<br />

2) Then begin balancing Ihe supply syslem al Ihe<br />

las! outlet of Ihe branch lmlhest from lhe fan<br />

(branch number 1). This is oullel number 1,<br />

number 2 is Ihe next Io lhe last oullel. Measure<br />

Ihe airflow al oullel number (Q,.) and compare<br />

wilh tile design airflow for Ihat oullet (Q,), recold<br />

the ratio (Q,./Qd).<br />

3) Measf=re Ihe airflow al outlet number 2 and<br />

delormine Ihe ratio (QJ(3d). Compare<br />

mid (Q/Q,),. If Ihese rations are eel Wilhln 10%<br />

of each olher, adjust oullel number 2 1o bring<br />

ratios Inlo closer agreement. DO NOT ADJUST<br />

OIITI ET NUMBER 1.<br />

Measme and again determine (Q,./Q,)= and<br />

(Q,,,/Q,), and compare. If lhese are wilhin 10%<br />

of each olher, no further adjuslmenl is necessary.<br />

Proceed to oullel number 3.<br />

4) Delermlne (Q.,/Qd)= and compare with (Q,,J<br />

Q.). If necessary, adjust number 3 so that<br />

(O,,,IOe) end (Q,./O,)=’db not vary by more Ihari<br />

10%. DO NOT ADJUST OUTLETS 1 OR.2.<br />

(Adjushnonl of oullel 3 aulomalically changes<br />

the (Q,JOe) ratios of oullets 2 and 1. The ratios<br />

for all Ihese oullel9 approach lhe same values.<br />

For this reason, once Ihe oullel has been adjusled,<br />

il does eel require fudher adjustment).<br />

5) Proceed to oullel number 4 and adjusl Io oblain<br />

nflmemenl between (Q.,IQ) and (Q,.IQe)=.<br />

6) Aller all oullels on branch number are propoHionalely<br />

balanced to each olher, proceed Io<br />

branch number 2, elc.<br />

Upon complelion of propodionate balancing of<br />

all outlets, the branches should .be propoHionalely<br />

balanced.<br />

7) Select typical oullels in branches 1 and 2 ..."<br />

djusl number 2 branch damper Io obtain<br />

agreement of Ihe (Q,./Qe) ratios for Ihe two<br />

branches. Proceed in like manner to obtain<br />

agreemenl between bran;hes 2 and 3, 3 and 4,<br />

elc.<br />

8) Upon completion of proportionate balancing,<br />

recheck Ihe fan,capacily. Adjust Ihe fan.speed<br />

to obtain a (Q,./Q.) ratio of 1.0 al the fan. Since<br />

the system has. been propodtonately adjusted,<br />

lhe ((.),,JO,) ratio Ihroughogt the system will be<br />

approximately 1.0 and lhe flow from each outlet<br />

will be Ihe design airflow rale.<br />

9) Then continue lhe TAB work by following all of<br />

the steps lisled under Sub-Section B--"Supply<br />

Air Syslems Procedures" found earlier in this<br />

section.