3. Simulated Loads:<br />
All simulated loads shall be accomplished through the<br />
control system by introducing a false slgnal to the<br />
control device. The controls on ths Job are existing<br />
pneumatic, and the various control valves can be<br />
positioned ether fully open or closed by varying the<br />
control air pressure to the device with a pneumatic<br />
"squeeze bulb" The performance of the equipment can<br />
then be measured to establish its full heating and<br />
cooling capabilities.<br />
4. Seasonal Restrictions:<br />
The TAB work will be performed during August which will<br />
fully demonstrate theequlpment performance during the<br />
cooling season. At some time during the month of<br />
February, the TAB Contractor shall re-vlslt the facility<br />
and check the operation of the new HVAC equipment (AHU-I,<br />
AHU-2, FC-1 thru FC-5, steam-HW converter). A11<br />
necessary adjustments and TAB should be accomplished<br />
within a three day period. It should be noted that the<br />
TAB contractor is not responsible for the TAB of the<br />
existing equipment but will so notify the owner of any<br />
problems found so discovered.<br />
Support Required:<br />
During the TAB operations the TAB Contractor will need<br />
assistance from the government personnel the chiller and<br />
boiler plants and some one to make necessary adjustments<br />
to the existing AHU that may be required.