250A-160VDC in-line DC Fuse.<br />

Fuse - West Marine Model# 215089<br />

Fuse Block - West Marine Model# 10093813<br />

FlexWare Mounting Plate<br />

2 rows of 8 Batteries in series.<br />

Batteries are Sun Xtender 3050T Batteries.<br />

(See Sheet DS-03:04 for Battery Specifications).<br />

12.75"<br />

10.25"<br />

250A Inline DC Fuse<br />

Ground Anchor<br />

and Strap<br />

To positive DC Busbar in<br />

FlexMax 1000 Power<br />

Distribution Panel<br />

#2/0 To Negative DC<br />

Terminals Of<br />

Inverters<br />

# 4/0 From Battery<br />

Negative<br />

Conduit Tie Down bracket<br />

Wood Subfloor<br />

#4/0 battery cable<br />

Must be equal length 4/0 Battery Cables<br />

Battery Temperature Sensor Wire to one Charge Controller<br />

#4/0 battery cable<br />

Must be equal length<br />

4/0 Pos Battery<br />

Cable<br />

Battery Temp<br />

Sensor Wire<br />

Skids<br />

Sun-Xtender<br />

PVX-3050T<br />

6V AGM Battery<br />

Concrete Block<br />

Sun-Xtender<br />

PVX-3050T<br />

6V AGM Battery<br />

#2/0 To Positive DC<br />

Terminals Of<br />

Inverters<br />

175 ADC<br />

# 4/0 From Battery<br />

Positive<br />

DC Busbar Detail in FlexMax 1000 Power Distribution Panel<br />

2" Flexible Metal<br />

Conduit<br />

Plastic Bushing<br />

4/0 Neg Battery<br />

Cable<br />

96.00"<br />

Battery Bank to DC Enclosure connection Detail<br />

Battery Wiring Detail<br />

SCALE: NTS<br />

2" Flexible Metal<br />

Conduit Connector<br />

Sun-Xtender<br />

PVX-3050T<br />

6V AGM Battery<br />

Battery Temperature<br />

Sensor<br />

29"<br />

Sun-Xtender<br />

PVX-3050T<br />

6V AGM Battery<br />

Sun-Xtender<br />

PVX-3050T<br />

6V AGM Battery<br />

Sun-Xtender<br />

PVX-3050T<br />

6V AGM Battery<br />

Battery Connection Detail<br />

Batteries are Concorde SunExtender PVX-3050T<br />

6V, 354Ah @ C/100 Battery bank supplies 27.0KWh @ 80% DOD<br />

Wiring Method:<br />

Battery System Wiring. Connect eight<br />

batteries in series to create a 48V array.<br />

Connect two groups in parallel. The<br />

batteries will deliver 27.0 kWh. Use only<br />

UL listed cables and lugs and UL listed<br />

crimp tools. Use 4/0 cables for battery to<br />

battery connections.<br />

Use only UL listed cables and lugs and UL<br />

listed crimp tool. Do not use fine stranded<br />

wire under the set screws inside the<br />

Outback Inverter.<br />

Sun-Xtender<br />

PVX-3050T<br />

6V AGM Battery<br />

Notes:<br />

Sun-Xtender<br />

PVX-3050T<br />

6V AGM Battery<br />

To negative DC Busbar in<br />

FlexMax 1000 Power<br />

Distribution Panel<br />

1. Batteries are Sun-Xtender PVX-3050T; 6<br />

volt batteries. Total battery capacity:<br />

27.0KWh @ (C/100) and 80% DOD.<br />

2. Positive and Negative battery cable<br />

length between batteries and busbar<br />

must be equal.<br />

3. Use heat shrink on all crimp lugs<br />

4. Disconnects for batteries are located on<br />

the FlexWare 1000 DC Power Distibution<br />

Panel.<br />

5. Install all batteries in accordance to NEC.<br />

6. Install Batteries in a well ventilated area<br />

to keep them as cool as possible.<br />

7. Fuse Information<br />

Fuse Rating: 250A@160VDC<br />

Manufacturer: Blue Sea Systems<br />

Manufacturer part #: 5118<br />

West Marine part #: 215089<br />

Fuse Block<br />

Model #: 10093813<br />

Manufacturer part #: 5502<br />

3232 Moss Hill Road, <strong>Vernon</strong>, FL 32462<br />

Design for:<br />

I CERTIFY THAT THIS PV<br />

SYSTEM FULLY COMPLIES<br />

WITH THE REQUIREMENTS<br />

OF NEC 690.<br />

PV SYSTEM<br />

Total Output:<br />

# Modules:<br />

Manufacturer:<br />

Model:<br />

<strong>Vernon</strong> <strong>High</strong> <strong>School</strong><br />

<strong>Solar</strong> <strong>School</strong> Shelters<br />

Battery Backup PV System<br />

Battery Wiring Detail<br />

SCALE: NTS<br />

DRAWN BY: RB,HB<br />

CHECKED BY: EC<br />

DATE: 10/03/11<br />

SHEET 8 OF 20<br />

Revision:<br />

00<br />

10.08 kW<br />

42<br />

<strong>Solar</strong> World<br />

240<br />

Sheet:<br />

E.E. Castillo, PE<br />

Licensed Engineer #: PE52590<br />

Certification of Authorization #28406<br />

3601 N. DIXIE HWY, BAY 16 BOCA RATON, FL 33431<br />

PHONE: 561.750.8677 FAX:561.750.0518<br />