2.1 <strong>–</strong> TOP COVERINGS<br />

There are different types of floor coverings available, but not all of them are suitable for raised floor.<br />

This is due to the following reasons:<br />

• the dimensions: since an access floor module is 60 x 60 cm, it is not possible to manufacture with<br />

coverings of smaller dimensions. It is also not advisable to use coverings whose dimensions are not<br />

compatible with the floor module, because of waste excess and/or an unsuccessful final design (for<br />

example studded rubber with module differing from 60 cm).<br />

• not all materials are suitable for being glued to an access floor panel, such as certain floor spongebottomed<br />

carpets; other materials can not even be cut successfully, such as certain bouclè carpet,<br />

because they fray.<br />

ELECTRICAL CHARACTERISTICS<br />

What ever concerning may be, PVC, needle-punch carpet, plastic laminate etc., coverings possess transversal<br />

electric insulation characteristics, (through their thickness), known as electrical resistance. The unit of<br />

measurement is ohm (Ω).<br />

If this value is >1x10 9 ≤2 x 10 10 Ω, we talk about antistatic coverings, if the value is ≥1x10 7 ≤1x10 9 Ω we talk<br />

about static-dissipative coverings, and if the value is >1.5 x 10 5 2 x 10 10 Ω, such as parquet or<br />

some kinds of rubber, but these coverings are not suitable for computer rooms or electronic instrument rooms.<br />

Carpet<br />

Spongy back not<br />

resisting to tear<br />

Panel<br />

On the above drawing, the spongy back does not resist to tear.<br />

<strong>Rev</strong>. 01.08.07<br />

NESITE S.p.A. <strong>–</strong> Via L. Da Vinci, 20 <strong>–</strong> 35028 PIOVE DI SACCO <strong>–</strong> Z.I. Tognana (Padova) Italy <strong>–</strong> Tel. +39.049.9713311 <strong>–</strong> Fax +39.049.9713313<br />

NESITE S.p.A. reserves the right to change technical data without notice<br />

www.nesite.com e-mail : nesite@nesite.com<br />