4.5 Inverter disturbance<br />
Mains<br />
Load<br />
“Inverter disturbance mode” is triggered by a disturbance<br />
in one or more inverters.<br />
Q2<br />
K6<br />
Q4<br />
K3<br />
SSM<br />
K7<br />
Q1<br />
As long as the output of the remaining single units<br />
is sufficient to sustain the load, RPA remains in online<br />
mode – but the system may become “parallel”<br />
and is no longer “redundant”.<br />
Q2<br />
K6<br />
Q4<br />
SSM<br />
K7<br />
Q1<br />
The inverter output contactor (K7) of the disturbed<br />
unit opens automatically to isolate the disturbed<br />
unit from the load.<br />
Q2<br />
K6<br />
Q4<br />
4.6 Bypass mode<br />
Mains<br />
Q2<br />
K6<br />
Q4<br />
Q2<br />
K6<br />
Q4<br />
Q2<br />
K3<br />
K3<br />
K3<br />
K3<br />
SSM<br />
SSM<br />
SSM<br />
K7<br />
K7<br />
K7<br />
Q1<br />
The rectifiers of the disturbed units, depending on<br />
the nature of the disturbance, will continue to<br />
charge the batteries.<br />
The disturbed units can also be completely separated<br />
from the utility and from the load, as illustrated,<br />
to enable repair work to be carried out.<br />
TEMPORARY<br />
Q1<br />
Q1<br />
Load<br />
“Bypass mode” is triggered when all the available<br />
inverters are unable to sustain the load (e.g. in the<br />
case of disturbance of several inverters or severe<br />
overload).<br />
If the load exceeds 110% of the sum of the rated<br />
outputs of all inverters, the load will be sustained<br />
directly from the utility via the static bypasses.<br />
All inverter output contactors (K7) are opened automatically<br />
and the inverters, depending on the<br />
type of disturbance, continue to operate and the<br />
rectifiers continue to charge the batteries.<br />
K6<br />
Q4<br />
K3<br />
SSM<br />
K7<br />
Q1<br />
If the load level once again returns below 100% of<br />
the sum of the outputs of all the available inverters,<br />
RPA will close all K7 and automatically switches<br />
back to “On-line mode”.<br />